HomeMy WebLinkAboutDERR-2025-000476PV VENT CAP
STAGE 1 PD
11000 N. MoPac Expressway, Suite 500
Austin, Texas 78759
Phone: (512) 451-6334
Fax: (512) 459-1459 Date Printed and Mailed: 4/1/2022
7-Eleven Air Quality Report
P.O. Box 711
Dallas, TX 75221
Test Date: 3/31/2022
Order Number: 2355404
Dear Regulator,
Enclosed are the results of recent testing performed at the following facility:
7-ELEVEN 47166/9445
897 EAST 6600 SOUTH
MURRAY, UT 84107
Testing performed:
Sincerely,
Dawn Kohlmeyer
Manager, Field Reporting
2 inch Pressure Decay Test
TP201.3
Store Information Testing Company
Site Name :7-ELEVEN 47166/9445 Name :TANKNOLOGY INC.
Address :897 EAST 6600 SOUTH
MURRAY, UT 84107
Address :11000 N. MoPac Expressway Suite 500
Austin, TX 78759
Phone :-Phone :(800) 800-4633
Stage I System?DUAL
Stage II System?NONE
Total # of Nozzles :8
Products per Nozzle :3
Tanks Manifolded ?No
Drop-Out tank present?NO
Total # of Tanks Tested :2
Tank Information :
Product Grade :
Tank Capacity, gallons :
Gasoline, gallons :
Ullage, gallons :
Testing Information :
Start Time :
Initial Pressure, wcg :
Pressure @ 1 minute(s) :
Pressure @ 2 minutes :
Pressure @ 3 minutes :
Pressure @ 4 minutes :
Pressure @ 5 minutes :
Allowable Final Pressure :
Pass/Fail (Enter "GF" Gross Failure)
T1-Regular
RUL
15041
3612
11429
10:54
2.00
2.00
2.00
1.99
1.99
1.98
1.92
Pass
T2-Premium
PUL
8050
3324
4726
11:06
2.00
1.97
1.95
1.93
1.92
1.91
1.80
Pass
Total
23091
6936
16155
All
Comments:
Tester :David Mathie Test Date :3/31/2022
Signature :Work Order :2355404
WO: 2355404
PVVC tested ==>RUL Manifolded
Final Test Result (Pass / Fail) ==>Fail
PVVC Manuf. ==>Husky Model Number ==>5885
Is this Original or
Replacement?
Original
If this cap is being
replaced, check here:
Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)0.05 25 0.0530 Fail
Low High Measured
Pos Cracking (in H2O)2.50 6.00 2.16 Fail
Neg Leak Rate (CFH)0.21 100 0.2120 Fail
Low High Measured
Neg Cracking (in H2O)-10.00 -6.00 -5.12 Fail
PVVC tested ==>RUL Manifolded
Final Test Result (Pass / Fail) ==>Pass
PVVC Manuf. ==>OPW Model Number ==>723V
Is this Original or
Replacement?
Replacement Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)0.05 10 0.0212 Pass
Low High Measured
Pos Cracking (in H2O)2.50 6.00 3.52 Pass
Neg Leak Rate (CFH)0.21 60 0.1272 Pass
Low High Measured
Neg Cracking (in H2O)-10.00 -6.00 -8.61 Pass
PVVC tested ==>PUL Manifolded
Final Test Result (Pass / Fail) ==>Fail
PVVC Manuf. ==>Husky Model Number ==>5885
Is this Original or
Replacement?
Original
If this cap is being
replaced, check here:
Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)0.05 25 0.0530 Fail
Low High Measured
Pos Cracking (in H2O)2.50 6.00 2.10 Fail
Neg Leak Rate (CFH)0.21 100 0.2120 Fail
Low High Measured
Neg Cracking (in H2O)-10.00 -6.00 -5.05 Fail
PVVC tested ==>PUL Manifolded
Final Test Result (Pass / Fail) ==>Pass
PVVC Manuf. ==>OPW Model Number ==>723V
Is this Original or
Replacement?
Replacement Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)0.05 10 0.0212 Pass
Low High Measured
Pos Cracking (in H2O)2.50 6.00 3.48 Pass
Neg Leak Rate (CFH)0.21 60 0.1272 Pass
Low High Measured
Neg Cracking (in H2O)-10.00 -6.00 -8.56 Pass
PVVC tested ==> Manifolded
Final Test Result (Pass / Fail) ==>
PVVC Manuf. ==>Model Number ==>
Is this Original or
Replacement?
Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)
Low High Measured
Pos Cracking (in H2O)
Neg Leak Rate (CFH)
Low High Measured
Neg Cracking (in H2O)
PVVC tested ==> Manifolded
Final Test Result (Pass / Fail) ==>
PVVC Manuf. ==>Model Number ==>
Is this Original or
Replacement?
Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)
Low High Measured
Pos Cracking (in H2O)
Neg Leak Rate (CFH)
Low High Measured
Neg Cracking (in H2O)
11000 N. MOPAC EXPRESSWAY, SUITE 500, AUSTIN, TX 78759
(800) 800-4633
QP-08-03-FF-02 Pressure Vacuum Vent Cap TP-201.1E Field Form
Rev C 1/27/2011
Site Overall Test Results: Pass
Total +ve LR: 0.0424
Total -ve LR: 0.2544
Test Date 3/31/2022
Technician Name David Mathie
WO #2355404
Facility Name / Loc #7-ELEVEN 47166/9445 47166/9445
Street 897 EAST 6600 SOUTH
City, St, Zip MURRAY, UT 84107
Pressure Vacuum Vent Cap Test Form TP-201.1E
Site Diagram
(This site diagram is for reference only and is not drawn to scale)
Work Order:2355404
Site ID / Name:47166/9445 / 7-ELEVEN 47166/9445
Address:897 EAST 6600 SOUTH
City:MURRAY State:UT Zip:84107
W.O.# NW1-2355404
LD C9