HomeMy WebLinkAboutDAQ-2025-0002011
DAQC-1261-24
Site ID 10790 (B4)
MEMORANDUM
TO: STACK TEST FILE – BRIGHAM YOUNG UNIVERSITY – Main Campus
– Utah County
THROUGH: Rik Ombach, Minor Source Oil and Gas Compliance Section Manager
FROM: Kyle Greenberg, Environmental Scientist
DATE: December 26, 2024
SUBJECT: Sources: Boiler #4 and Boiler #6
Location: Brigham Young University, Provo, UT 84602
Contact: Brian Harris: (801) 422-2804
Tester: TETCO
Site ID #: 10790
Permit/AO #: Approval Order DAQE-AN107900021-23, dated May 24, 2023
Subject: Review of Pretest Protocol dated December 19, 2024
On December 19, 2024, DAQ received a protocol for testing of Boiler #4 and Boiler #6 at the Brigham
Young University Main Campus in Utah County, UT. Testing will be performed the week of February 3,
2025, to determine compliance with the emission limits found in condition II.B.2.b of Approval Order
DAQE-AN107900021-23 and 40 CFR Part 60 Subpart Db.
PROTOCOL CONDITIONS:
1. RM 1 used to determine sample velocity traverses: OK
2. RM 2 used to determine stack gas velocity and volumetric flow rate: OK
3. RM 3A used to determine dry molecular weight of the gas stream: OK
4. RM 4 used to determine moisture content: OK
5. RM 7E used to determine NOx emissions: OK
DEVIATIONS: None.
CONCLUSION: The protocol appears to be acceptable.
RECOMMENDATION: The methods proposed in the pretest protocol are sufficient to
determine NOx emissions from Boiler #4 and Boiler #6. It is
recommended that the pretest protocol be determined as
acceptable.
ATTACHMENTS: BYU’s Test Notification Letter and Pretest Protocol
4 ' - ) - "
NOX COMPLIANCE EMISSION TESTING PROTOCOL
BRIGHAM YOUNG UNIVERSITY, PROVO, UTAH
CENTRAL HEATING PLANT BAGHOUSE
BOILERS #4 AND #6
Project Organization and Responsibility
The following personnel and the testing contractor are presently anticipated to be involved in the
testing program. Utah Department of Environmental Quality, Division of Air Quality (DAQ)
may have their own personnel or contractor to observe all phases including the process.
Company Contacts
Brigham Young University Brian Harris (801) 422-2804
Risk Management Department Environmental Manager
105 CBM
Provo, UT 84602
Test Contractor
TETCO Dean A. Kitchen (801) 492-9106
391 East 620 South
American Fork, UT 84003
During these tests only Brigham Young University (BYU) personnel listed above or assigned
personnel from the operation are authorized to answer or obtain answers to pertinent questions on
the process conditions or the test protocol.
Test Schedule
It is planned to complete this test project January 9-11, 2023. The testing crew will arrive and set
up the test equipment January 9, 2023. It is anticipated that testing will begin the morning of
January 10th and continue until all testing has been completed. A pretest meeting may be held at
the request of BYU or DAQ.
Project Description
This test project will be conducted to comply with the requirements of BYU’s Approval Order,
DAQE-AN107900019-20, dated January 29, 2020, which requires testing Boilers #4 and #6 for
NOx emissions every three years. Testing will be performed according to EPA Methods 1-4, and
7E and will include accumulating process and production data.
Test Procedures
Three tests runs will be conducted on each unit for NOx emissions. Testing will be EPA
Methods 1-4 and 7E as specified in 40 CFR 60, Appendix A. One Method 4 test may span up to
three Method 7E test runs. Specific test procedures are as follows:
EPA Methods 1-4
1.Boilers #4 and #6 have a common exhaust duct with inside dimensions of 48 inches by 84
inches. The sample ports are located approximately 18.5 feet downstream and 6 feet
upstream from any flow disturbance and conform to EPA Method 1. Sample points will
be selected according to EPA Method 1 for a non-particulate traverse.
2.EPA Method 2 will be used to determine gas stream velocity. Type “S” pitot tubes will
be used with a Cp factor of 0.84. Dual inclined/vertical manometers with graduations in
0.01 inches of water will be used. If flows are below 0.05 inches of water a more
sensitive manometer will be used. The graduations marks on int are 0.005 inches of
water. Direction of gas flow will be checked for cyclonics prior to testing.
3.A barometer will be used to measure the barometric pressure. It is periodically checked
against a mercury barometer. Prior to testing it will be checked to assure an accurate
barometric pressure.
4.EPA Method 3, or 3A, will be used to determine the gas stream dry molecular weight.
For Method 3 an integrated flue gas sample would be taken from the exhaust line after the
dry gas meter orifice during each run and analyzed at the completion of the test with an
Orsat to determine the molecular weight of the effluent gas stream.
5.All Method 4 test run durations will be sufficient to sample at least 21 dscf as required by
Method 4.
6.The probe liners will be 316 stainless steel.
7.Preparation and clean-up by the contractor will be performed in the contractor's testing
trailer. Laboratory work and analysis will be performed by the testing contractor as soon
as possible after all tests have been completed.
8.If plant maintenance or operating problems arise during the test, the test may be stopped.
This determination will be made by the Brigham Young University representatives or
operating personnel in consultation with agency representatives.
2
9.Current calibration data is submitted in Appendix A of this protocol. Any equipment
calibration that fall past due prior to the test date will be recalibrated prior to use.
Gaseous Analyzer Measurements
The following procedures will be used fo the Method 7E tests:
1.A gaseous analyzer will be used to measure the NOx concentrations during the emissions
test project. It is planned to run the NOx machine on the 0-250 ppm range. EPA Protocol
1 gases will be used as calibration standards with dry nitrogen as a zero gas.
2.A gaseous analyzer may be used to measure the O2 and CO2 concentrations in place of an
Orsat analysis during the emissions test project. If operated, the O2 and CO2 analyzer
would be run on the 0-10, or 0-20, percent range. EPA Protocol 1 gases would be used
as calibration standards with dry nitrogen as a zero gas.
3.The gas analyzer sampling train will consist of the following: an in-stack glass fiber
filter, heated stainless steel probe, Teflon heated sampling line to the water removal
system, water removal system, Teflon transport lines, gas manifold, and out of stack
Teflon filter after the gas manifold but prior to analyzers. The sampling train is built such
that the sampled gas only comes in contact with inert materials, i.e., Teflon, stainless
steel, and glass.
4.The number of sample points for the Method 7E sampling train will be determined
according to the results of a stratification check as per Method 7E, section 8.1.2.
5 The NOx converter efficiency check will be completed according to Method 7E, section
16.2.2.
6.Bias checks, calibration drift, zero drift and calibration error will follow the specified
guidelines of EPA Method 7E. Interference responses were determined in the factory and
no alterations have been done, therefore, factory specifications are satisfactory.
7.A data logger will be used to record measured concentrations. Gas analyzer data during
port changes will not be considered valid data.
Test Area
The test area shall include the Heating Plant control room, main floor, and stack areas, and the
area around the contractors testing trailer.
3
Process Data
Process parameters are available via computer in the Heating Plant control room. Pertinent
process parameters will be made available to DAQ personnel and included in the test report.
Quality Assurance
All testing and analysis in these tests will be conducted according to Methods 4 and 7E as
specified in this protocol, and appropriate sections of the EPA Quality Assurance Handbook for
Air Pollution Measurement Systems Vol. III.
Reporting
Complete copies of raw data, calculations and summary of test will be included in reports. All
process and production data will be recorded and retained for inspection and copying by DAQ.
The contractor will furnish copies of the test report to Brian Harris, Environmental Manager,
BYU.
4
Appendix A
Facility Schematic
A
Facility:
Stack Identification:
W E
b
Control Unit Type
None
Process Type
Natural Gas, or Oil, Fired Boilers
a
Brigham Young University
6"
35'
48.0" x 84.0"
Boilers 4 and 6
10.0%
300
700
5
18.5'
b: Distance downstream from last disturbance, feet
Estimated Temperature, oF
Estimated Velocity, fpm
Estimated Moisture, percent
a: Distance upstream from next disturbance, feet
Stack Inside Diameter, inches
g: Distance of Sample Level to Ground, feet
Number of Ports
ag
Figure 1. Facility Schematic Representation
Appendix B
Calibration Data
B
METHOD 5 DRY GAS METER CALIBRATION USING CRITICAL ORIFICES
1) Select three critical orifices to calibrate the dry gas meter which bracket the expected operating range.
2) Record barometric pressure before and after calibration procedure.
3) Run at tested vacuum (from Orifice Calibration Report), for a period of time
necessary to achieve a minimum total volume of 5 cubic feet.
4) Record data and information in the GREEN cells, YELLOW cells are calculated.
TECHNICIAN:INITIAL FINAL AVG (Pbar)
DATE:12/17/21 METER SERIAL #:26144 BAROMETRIC PRESSURE (in Hg):25.50 25.50 25.50 IF Y VARIATION EXCEEDS 2.00%,
METER PART #:Console 5 CRITICAL ORIFICE SET SERIAL #:1453S EQUIPMENT ID #:ORIFICE SHOULD BE RECALIBRATED
K'TESTED TEMPERATURES °F ELAPSED
FACTOR VACUUM DGM READINGS (FT3)AMBIENT DGM INLET DGM OUTLET DGM TIME (MIN)DGM DH (1)(2)(3)Y
ORIFICE #RUN #(AVG)(in Hg)INITIAL FINAL NET (Vm)INITIAL FINAL INITIAL FINAL AVG q (in H2O)Vm (STD)Vcr (STD)Y VARIATION (%)DH@
1 0.8137 10 77.883 83.067 5.184 69 81 86 76 77 80.0 4.75 2.70 4.3544 4.2864 0.984 1.567
2 0.8137 10 83.067 88.261 5.194 69 85 90 77 78 82.5 4.75 2.70 4.3427 4.2864 0.987 1.559
3 0.8137 10 88.261 95.662 7.401 69 89 93 78 79 84.8 6.75 2.70 6.1624 6.0913 0.988 1.553
AVG = 0.987 -0.71
1 0.5317 13 57.832 62.902 5.070 66 67 69 67 68 67.8 7.25 1.10 4.3376 4.2873 0.988 1.514
2 0.5317 13 62.902 71.487 8.585 66 69 77 68 72 71.5 12.25 1.10 7.2930 7.2440 0.993 1.503
3 0.5317 13 71.487 77.105 5.618 66 76 82 72 76 76.5 8.00 1.10 4.7280 4.7308 1.001 1.489
AVG = 0.994 0.04
1 0.3307 13 95.699 100.878 5.179 70 86 84 79 78 81.8 11.75 0.41 4.3077 4.3053 0.999 1.429
2 0.3307 13 100.878 106.169 5.291 70 83 84 78 79 81.0 12.00 0.41 4.4070 4.3969 0.998 1.431
3 0.3307 13 106.169 111.326 5.157 70 83 86 78 81 82.0 11.75 0.41 4.2874 4.3053 1.004 1.428
AVG = 1.000 0.68
AVERAGE DRY GAS METER CALIBRATION FACTOR, Y = 0.994
AVERAGE DH@ = 1.497
(1)=Net volume of gas sample passed through DGM, corrected to standard conditions
K1 =17.64 oR/in. Hg (English), 0.3858 oK/mm Hg (Metric)
Tm =Absolute DGM avg. temperature (oR - English, oK - Metric) DH@ = 0.75 q DH Vm(std)
Vcr(std) Vm
(2)=Volume of gas sample passed through the critical orifice, corrected to standard conditions
Tamb =Absolute ambient temperature (oR - English, oK - Metric)
K' = Average K' factor from Critical Orifice Calibration REFERENCE IN OUT
(3)=DGM calibration factor 32 33 32
72 73 73
203 203 202
TEMPERATURE SENSORS oF
2022 Pre-Calibration
Console #5
30
19
12
R Kitchen
ENVIRONMENTAL SUPPLY COMPANY
USING THE CRITICAL ORIFICES AS CALIBRATION STANDARDS:The following equations are used to calculate the standard volumes of air passed through the DGM, Vm (std), and the critical orifice, Vcr(std), and the DGM calibration factor, Y. These equations are automatically calculated in the spreadsheet above.
()2 ()
Type S Pitot Tube Inspection Data
Date:Pitot Tube Identification:
Technician:
Dt=0.375 Is PA = PB ?
Is 1.05 • Dt PA & PB 1.50 • Dt ?
PA = 0.478
PB =0.478
a1 < 10o a1 = o
a2 < 10o a2 = o
b1 < 5o b1 = o
b2 < 5o b2 = o
Z 0.125 in.Z = in.
W W 0.03125 in.W = in.
W > 3 inches W = in.
Z > 3/4 inch Z = in.
Y ≥ 3 inches Y = in.
The pitot tube meets the specifications for a calibration factor of 0.84?Yes
Reference:
TemperatureSource Reference Sensor
(Medium)(oF)(oF)
Probe AIR 68 70
AIR 68 70
ICE WATER 33 33
BOIL WATER 203 203
SILICONE OIL
Heat Check 248
Temperature Sensor Calibration
2
0
0Stack
Omega CL3512A
Probe Yes
Yes
Continuity Check
Temperature TemperatureDifference
(oF)
2
in.
in.
Yes
Yes
0.004
5
1
3 1/2
12/28/21 51 G
M. McNamara
in.
0.008
0
0
1
1
b2
b1
B
A
w
Dt
PA
PB
Type S Pitot Tube Inspection Data
Date:Pitot Tube Identification:
Technician:
Dt=0.375 Is PA = PB ?
Is 1.05 • Dt PA & PB 1.50 • Dt ?
PA = 0.463
PB =0.463
a1 < 10o a1 = o
a2 < 10o a2 = o
b1 < 5o b1 = o
b2 < 5o b2 = o
Z 0.125 in.Z = in.
W W 0.03125 in.W = in.
W > 3 inches W = in.
Z > 3/4 inch Z = in.
Y ≥ 3 inches Y = in.
The pitot tube meets the specifications for a calibration factor of 0.84?Yes
Reference:
TemperatureSource Reference Sensor
(Medium)(oF)(oF)
Probe AIR 68 70
AIR 68 70
ICE WATER 33 33
BOIL WATER 203 202
SILICONE OIL
Heat Check 248
Temperature Sensor Calibration
2
0
1Stack
Omega CL3512A
Probe Yes
Yes
Continuity Check
Temperature TemperatureDifference
(oF)
2
in.
in.
Yes
Yes
0.002
5
1.5
3 3/4
12/29/21 60 G-1
M. McNamara
in.
0.014
1
0
1
2
b2
b1
B
A
w
Dt
PA
PB
Date:1/4/22 Calibrator:Reference:
Temperature Temperature
Source Difference
(Medium)(oF)
Water 0
Water 0
Water 0
Water 0
Water 0
Water 0
Water 0
Water 0
Water 1
Water 0
Water 0
Water 0
Water 0
Water 0
Water 0
Water 0
Water 0
Water 0
Water 0
Water 0
Water 0
Water 0
Water 0
Water 1
Water 0
Water 0
Water 0
Water 0
Water 1
Water 0
Water 0
Water -2
Water 1
Water -2
Water 1
Water 0
Water 0
Water -2
Water 0
Water -2
Water 1
Water -2
Water 1
Water -1
Water 0
Water -1
Water 1
Water -1
202
33 33
Impinger Out K 33 34
204 203
33 33
Impinger Out J
Impinger Out H
Impinger Out I
34
203
34
202
33
204
33
204
204
204
33
G
H
Oven (3)33 33
204 204
Oven (4)33
204
Oven 33 33
204 204
Oven 33 33
33
204 204
Oven (3)
A
203203
33
Oven (3)33 33
Oven (4)
Thermocouple
Location
203 203
Impinger Out F 33 33
203
204
204
203 204
204 204
33
32
Impinger Out G
204 202
Oven (3)32
204 204
32 32
204Oven (4)
204
Impinger Out D 33 34
204 202
Impinger Out E 33 34
204 204
204
33 34
204Impinger Out B
Impinger Out C 33 33
204 202
204
Impinger Out A 33 33
204
Oven (3)
Oven (4)
TETCO
Sample Box Temperature Sensor Calibration
B
C 203 203
32 32
33 33
204
33 34
Mike McNamara Omega CL3512A
Unit ID Reference
(oF)
Sensor
(oF)
Temperature
33
D
E
Oven 33 33
204 204F
Oven (4)
..
Making our world
more productive I
DocNumber: 451254
Certificate /ssuand~ Date: 0410512022
Linde Order N,aml)er: 72001747
Linde Gas & Equipment Inc.
5700 S. Alameda Street
Los Angeles CA 90058
Tel: 3.23-585-2154
Fax: 714-542-6689
PGVP ID: F22022
Lot Number: 70086208302 LGEPKG SALT LAKE CITY UT H
6880 S 2300 E Part Number: NI CO47.5MN1EAS I Cylinder Style,& Outlet: AS CGA 660
SALT LAKE CITY UT 84121-3183 Customer PO Number: 80004083 Cylinder Pressure and Volume: 2000 psig 140 ft3
Certified Cof1;Centration
Expiration Date:
Cylinder Number:
For Reference,Only:
47.9 ppm
47.2 ppm
Balance
NOx47.4ppm
04/05/2025
. DT0009759
.Carbon monoxide
Nitric oxide
Nitrogen
Certification Information: Certification Date: 04/05/2022
I I l.-
:
NIST Traceable
Expanded Uncertainty
Term: 36 Months
±0.4 ppm
± 0.3 ppm
Expiration Date: 04/05/2025
This cylinder was certified according to the 2012 EPA Traceability Protocol, Document #EPA-1:i00IR-12/531, using Procedure G1. Uncertainty above is expressed as absolute expanded
uncertainty at a level of confidence of approximately 95% with a coverage factor k = 2. Do Not µse this Standard If Pressure Is less than 100 PSIG.
Ana(vtical Data: (R=Reference Standard, Z=Zero Gas, C=Gas Candid~te)
1. Component: ' Carbon monoxide . t'' eference Standard: Type I Cylinder#: NTRM / CC78493
Requested Concentrafion: ·47 .5 ppm Concentrafion / Uncertainty: 100.1 ppm ±0.8 ppm
Certified Concentration: 47.9 ppm •, Expirafion Date: 07/0912027
Instrument Used: Honba VIA-510 SIN 43627990042 ' raceable to: SRM #/Sample#/ Cylinder It NlRM / 190703 / CC8737
Anatyfical Method: NDIR \'· SRM Concenlration / Uncef1ainly: 100.1 ppm/ ±0.8 ppm
·--~---~, ,, LastM~l::~::~:::~:~~:=~'k' •:~~us:,,.~!:t\~~;';,,::1:912g22, '.k" ~F~-~~~~~': 2~.
Z: 0 R: 100.1 C:
2.
R: 100 Z: 0 C: 47.8 Cone: 47.8 R: O Z: O C: 0 Cone; 0
Z: 0 C: 47.9 R: 100.2 Cone: 47.9 Z: O C: o R: o Cone: o
UOM: ppm Mean Test Assay: 47.9 ppm
Component: Nitric oxide
Requested Concentration: 47 .5 ppm
Certified Concentration: 47 .2 ppm
Instrument Used: Thermo Electron 42i-LS S/N 1030645077
Anatyfical Method: Chemiluminescence
Last Multipoint Calibration: 0312512022
First Analysis Data: Date 0312912022
Z: 0 R: 47.6 C: 47.2 Cone: 47.2
R: 47.6 Z: 0 C: 47.2 Cone: 47.2
Z: 0 C: 47.1 R: 47.5 Cone: 47.1
UOM: ppm Mean Test Assay:
Analyzed By Henry Koung
UOM: ppm Mean Test Assay:
Reference Standard: Type / Cylinder ii': GMIS / ND8755
Concentration/ Uncertainty: 47 .6 ppm ±02 ppm
E,q,:raoon Dale: D3/09/2025
Traceable to: SRM #/Sample Ii' I Cylinder#: PRM / C1765710.01 I APEX 1324323
SRM Concenlralion / Uncerlanty: 50.04 ppm I =fl.20 ppm
SRM E,cpira5o,n Dale: 12JD9.l2022
Second Analysis Data: Da:le 04/05/2022
Z: 0 R: 47.6 C: 472 Cone: 47.3
R: 47.5 Z: 0 C: 47.1 Cone:: 472
Z: 0 C: 47.1 R: ",7.S Cone:: '472
UOM: ppm llleanTestAssay: ifl2 ppm
Certified By
Information contained herein has been pn,pared alyounequest byqualiliied experts within 1.n1e Gas & Equipmentlla!:. 'ffl:>1e we beiieJe that the information is accurate within the \imils<f.lh:
analytical methods employed and Is complete to the extent of 11le spedlicarayses petformed. we make no·wanani,«~tion as to the suitability of the use of the information fci:'""'J' ~
The information is offered with the understanding that any use of !he~ is al the sole discretion and risk ofle_._ ~ no event shall the liability of Linde Gas & Equipmeotih::. .""'5b;ait
of the use of the information contained herein exceed the fee eslablished -~ such irn!om,ation.
..
Makingour world
more produ(tive
DocNumber: 443002
Certificate Issuance Date: 1210112021
Linde Orrie( Number: 55894134
Linde Gas & Equipment Inc .
5700 S. Alameda Street
Los Angeles CA 90058
Tel: 323-585-2154
Fax; 714-542-6689
PGVP ID: F22021
Fill Date: 11/22/2021
Lot Number: 70086132607
Customer & Order Information
TETCO
391 E 620S Part Number: NI CD4.7501E-AS
Customer PO Number: 0
Cylinder Style & Outlet: AS CGA 580
AMERICAN FORK UT 84003 Cylinder Pressure and Volume: 2000 pslg 140 ft3
Certified Concentration ProSpec EZ Cert
Expiration Date:
Cylinder Number:
4.57 %
4.99 %
Balance
11/30/2029
CC243835
Carbon dioxide
Oxygen
Nitrogen
NIST Traceable
Expanded Uncertainty
± 0.02 %
± 0.03 %
Certification Information: Certification Date: 11/30/2021 Term: 96 Months Expiration Date: 11/30/2029
This cylinder was ce'rti!ied according to the.2012 EPA Traceability Protocol, Document #EPA0600IR-12/531, using Procedure G1. Uncertainty above is expressed as absolute expanded
uncertainty at a level oftonfidence of approximately 95% with a coverage factor k = 2. Do Not Use this Standard If Pressure is less than 100 PSIG. .
CO2 responses have been cbrr.ected for Oxygen IR Broadening effect. 02 responses have been corrected for CO2 interference.
Anafvtical Data: . (R=Reference Standard, Z=Zero Gas, C=Gas-Candidate)
1. Component: Carbon dioxide
·Requested Concentration:
... Certified Concentration:
Instrument Used:
A~'alytical Methpd:
4.75%
4.57%
Horiba VIA-510 S/N 20C194WK
NDIR
Last Multipoint Calibration: 11/22/2021
Reference Standard: Type/ Cylinder#: GMIS / CC243646
Concentration/ Uncertainty: 6.91 % ±0.01 %
Expiration Date: 06/07/2026
Traceable to: SRM #/Sample# / Cylinder#: SRM 1674b"/'7-H-07 / FF10631
SRM Concentration/ Uncertainty: 6.944% / ±0.013%
SRM Expiration Date: 06/17/2019
First Analysis Data: D,ite 11/30/2021 ;; Second Analysis Data: Date
Z: 0 R,:" ~h---•·"· ... C: -.::4.57.
R: 6.91 Z: 0 C: 4.58
. ·"· .Conc.:~4'57""' ""'•~·v-.. J. , ....... ,"~"""""""''""i~iZ:•·'-· o · R: •0 -·
Cone: 4.58 R: O Z: O
·C: .. ··iJ
C: 0
"Ci,,..,; ·o--·-•·-·----·-
Conc: 0
C: 4.58 R: 6.92 Cone: 4.58 Z: 0
UOM: % Mean Test Assay: 4.57 %
2. Component: Oxygen
Requested Concentration: 4.75 %
Certified Concentration: 4.99 %
Instrument Used: Siemens Oxymat SE S/N 7MB20211MOOOCA1
Analytical Method: Paramagnetic
Last Multipoint Calibration: 11/1212021
First Analysis Data: Date 11/30/2021
Z: 0 R: 9.88 C: Cone: 4.99
R: 9.88 Z: 0 C: Cone: 4.99
Z: 0 C: 5 R: Cone: 5
UOM: % 4.99 o/o
Analyzed By
Z: 0 C: 0 R: 0 Co_nc: O
UOM: % Mean Test Assay:
Reference Standard: Type / Cylinder#: NTRM / DT0010262
Concentration I Uncertainty: 9.875 % ±0.040 %
Expiration Date: 11/18/2022
Traceable to: SRM #/Sample# /Cylinder#: NTRM / 170701 / DT0010262
SRM Concentration/ Uncertainty: 9.875% / ±0.040%
SRM Expiration Date: 11/18/2022
Second Analysis Data: Date
Z: 0 R: 0 C: 0 Cone: 0
R: 0 Z: 0 C: 0 Cone: 0
Z: 0 C: 0 R: 0 Cone: 0
UOM: % Mean Test Assay:
Certified By
%
%
Information contained herein has been prepared at your request by qualified experts within Linde Gas & Equipment Inc. While we believe that the information is accurate within the limits of the
analytical methods employed and is complete to the extent of the specific analyses performed, we make no warranty or representation as to the suitability of the use of the Information for any purpose.
The information is offered with the understanding that any use of the information is at the sole discretion and rtsk of the user. In no event shall the liability of Linde Gas & Equipment Inc. , artsing out
of the use of the information contained herein exceed the fee established for providing such information.
..
Making our world
more produdive
DocNumber: 442995
Certificate Issuance Date: 12101/2021
Linde Order Number: 55894134
Linde Gas & Equipment Inc .
5700 S. Alameda Street
Los Angeles CA 90058
Tel: 323-585-2154
Fax: 714-542-6689
PGVP ID: F22021
Fill Date: 1112212021
Lot Number: 70086132602
Customer & Order Information
TETCO
391 E 620 S Part Number: NI CD9.75O1E-AS
Customer PO Number: 0
Cylinder Style & Outlet: AS CGA 590
AMERICAN FORK UT 84003 Cylinder Pressure and Volume: 2000 psig 148 ft3
Expiration Date:
Cylinder Number:
9.74 %
9.71 %
Balance
Certified Concentration
11/30/2029
CC87769
Carbon dioxide
Oxygen
Nitrogen
NIST Traceable
Expanded _Uncertainty
± 0.05 %
±0.04%
Certification Information: Certification Date: 11/30/202t Term: 96 Month_s Expiration Date: 11/30/2029
This cylinder was certified according to the 2012 EPA Traceability Protocol, Document #EPA-600/R-12/531, using Procedure G1. Uncertainty above is expressed as absolute expanded
uncertainty at a level ·°',confidence of approximately 95% with a coverage factor k = 2. Do Nbt Use this Standard if Pressure is less than 100 PSIG.
·CO2 responses have been corrected for Oxygen IR Broadening effect. 02 responses have been corrected for CO2 inter;ference.
Ana(vtical Data: (R=Reference Standard, Z=Zero Gas, C=Gas Candidate)
1. Component: Carbon dioxide
Requested Concentratio~: 9.75 %
Reference Standard: · Type/ Cylinder#: GMIS l'CC283571
Certified Concentration: 9.74%
Instrument Used: Horiba VIA-510 S/N 20C194WK
Concentration/ Uncertainty: 14.24 % ±0.04 %
Expiration Date: 07/15/2029
i\raceable to: SRM #/Sample #/Cylinder#: RGM / N/A / CC28033
Analytical Method: NDIR ii,
Last Multipoint Calibration: 11/22/2021
First Analysis Data: Date . 11130/2021
SRM Concentration/ Uncertainty: 19.67% / ±0.04%
SRM Expiration Date: 07/15/2021
Second Analysis Data: Date
... Z: 0 ...••••. R: 14.24--~C:.--.9_74,.:..,· .. ~.. CC:me::-, 9.74Y ~-·,· ·,,. ~"'"....,.;; ---z,··· .. o·· R: 0
0
0
·---c:· ·--1) --· ··--·--cono:·· ·a-· ---............ --·· ··
R: 14.24 Z: 0 C: 9.75 Cone: 9.75
Z: 0 C: 9.75 R: 14.25 Cone: 9.75
UOM: % Mean Test Assay: 9.74 %
2. Component: Oxygen
Requested Concentration: 9.75 %
Certified Concentration: 9.71 %
Instrument Used: Siemens Oxymat 6E S/N 7MB20211M000CA1
Analytical Method: Paramagnetic
Last Multipoint Calibration: 11/12/2021
First Analysis Data: Date 11/30/2021
Z: 0 R: 9.88 C: Cone: 9.7
R: 9.88 Z: 0 C: Cone: 9.7
Z: 0 ·C: 9.72 R: Cone: 9.71
UOM: % 9.71 %
Analyzed By
R: 0 Z:
Z: 0 C:
C: 0
R: 0
Cone: O
Cone: 0
l.lOM: % Mean Test Assay:
Reference Standard: Type/ Cylinder#: NTRM / DT0010262
Concentration / Uncertainty: 9.875 % ±0.040 %
Expiration Date: 11/18/2022
Traceable to: SRM #/Sample# / Cylinder#: NTRM / 170701 / DT0010262
SRM Concentration / Uncertainty: 9.875% I ±0.040%
SRM Expiratio~ Date: 11/18/2022
Second Analysis Data: Date
Z: 0 R: 0. C: 0 Cone: 0
R: 0 Z: 0 c: 0 Cone: 0
Z: 0 C: 0 R: 0 Cone: 0
UOM: % Mean Test Assay:
Certified By Nelson Ma
%
Information contained herein has been prepared at your request by qualified experts within Linde Gas & Equipment Inc. While we believe that the information is accurate within the limits of the
analytical methods employed and is complete to the extent of the specific analyses performed, we make no warranty or representation as to the suitability of the use of the information for any purpose.
The infonnation is offered with the understanding that any use of the infonnation is at the sole discretion and risk of the user. In no event shall the liability of Linde Gas & Equipment Inc. , arising out
of.the use of the information contained herein exceed the fee established for providing such infonnation.