7-Eleven Air Quality Report
P.O. Box 711
Dallas, TX 75221
Test Date: 7/19/2022
Order Number: 2356076
Dear Regulator,
Enclosed are the results of recent testing performed at the following facility:
7-Eleven 38442
200 S 1000 West
State ID 3000540
Syracuse, UT 84075
Testing performed:
Sincerely,
Dawn Kohlmeyer
Manager, Field Reporting
2 inch Pressure Decay Test
TP201.3
Store Information Testing Company
Site Name :7-Eleven 38442 Name :TANKNOLOGY INC.
Address :200 S 1000 West State ID 3000540
Syracuse, UT 84075
Address :11000 N. MoPac Expressway Suite 500
Austin, TX 78759
Phone :385-320-4199 Phone :(800) 800-4633
Stage I System?DUAL
Stage II System?NONE
Total # of Nozzles :12
Products per Nozzle :3
Tanks Manifolded ?No
Drop-Out tank present?NO
Total # of Tanks Tested :2
Tank Information :
Product Grade :
Tank Capacity, gallons :
Gasoline, gallons :
Ullage, gallons :
Testing Information :
Start Time :
Initial Pressure, wcg :
Pressure @ 1 minute(s) :
Pressure @ 2 minutes :
Pressure @ 3 minutes :
Pressure @ 4 minutes :
Pressure @ 5 minutes :
Allowable Final Pressure :
Pass/Fail (Enter "GF" Gross Failure)
TNK1 RUL
RUL
19782
6384
13398
10:33
2.00
1.99
1.98
1.97
1.96
1.96
1.93
Pass
TNK2 PUL
PUL
7901
2995
4906
10:40
2.00
2.00
2.00
2.00
2.00
2.00
2.00
Pass
Total
27683
9379
18304
All
Comments:
Tester :David Mathie Test Date :7/19/2022
Signature :Work Order :2356076
WO: 2356076
PVVC tested ==>RUL Manifolded
Final Test Result (Pass / Fail) ==>Fail
PVVC Manuf. ==>OPW Model Number ==>623V-2203
Is this Original or
Replacement?
Original
If this cap is being
replaced, check here:
Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)0.05 25 0.0530 Fail
Low High Measured
Pos Cracking (in H2O)2.50 6.00 2.12 Fail
Neg Leak Rate (CFH)0.21 100 0.2120 Fail
Low High Measured
Neg Cracking (in H2O)-10.00 -6.00 -5.04 Fail
PVVC tested ==>RUL Manifolded
Final Test Result (Pass / Fail) ==>Pass
PVVC Manuf. ==>OPW Model Number ==>723V
Is this Original or
Replacement?
Replacement Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)0.05 10 0.0212 Pass
Low High Measured
Pos Cracking (in H2O)2.50 6.00 3.60 Pass
Neg Leak Rate (CFH)0.21 60 0.1272 Pass
Low High Measured
Neg Cracking (in H2O)-10.00 -6.00 -8.72 Pass
PVVC tested ==>PUL Manifolded
Final Test Result (Pass / Fail) ==>Fail
PVVC Manuf. ==>OPW Model Number ==>623V-2203
Is this Original or
Replacement?
Original
If this cap is being
replaced, check here:
Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)0.05 25 0.0530 Fail
Low High Measured
Pos Cracking (in H2O)2.50 6.00 2.15 Fail
Neg Leak Rate (CFH)0.21 100 0.2120 Fail
Low High Measured
Neg Cracking (in H2O)-10.00 -6.00 -5.08 Fail
PVVC tested ==>PUL Manifolded
Final Test Result (Pass / Fail) ==>Pass
PVVC Manuf. ==>OPW Model Number ==>723V
Is this Original or
Replacement?
Replacement Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)0.05 10 0.0212 Pass
Low High Measured
Pos Cracking (in H2O)2.50 6.00 3.66 Pass
Neg Leak Rate (CFH)0.21 60 0.1272 Pass
Low High Measured
Neg Cracking (in H2O)-10.00 -6.00 -8.75 Pass
PVVC tested ==> Manifolded
Final Test Result (Pass / Fail) ==>
PVVC Manuf. ==>Model Number ==>
Is this Original or
Replacement?
Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)
Low High Measured
Pos Cracking (in H2O)
Neg Leak Rate (CFH)
Low High Measured
Neg Cracking (in H2O)
PVVC tested ==> Manifolded
Final Test Result (Pass / Fail) ==>
PVVC Manuf. ==>Model Number ==>
Is this Original or
Replacement?
Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)
Low High Measured
Pos Cracking (in H2O)
Neg Leak Rate (CFH)
Low High Measured
Neg Cracking (in H2O)
11000 N. MOPAC EXPRESSWAY, SUITE 500, AUSTIN, TX 78759
(800) 800-4633
QP-08-03-FF-02 Pressure Vacuum Vent Cap TP-201.1E Field Form
Rev C 1/27/2011
Site Overall Test Results: Pass
Total +ve LR: 0.0424
Total -ve LR: 0.2544
Test Date 7/19/2022
Technician Name David Mathie
WO #2356076
Facility Name / Loc #7-Eleven 38442 38442
Street 200 S 1000 West State ID 3000540
City, St, Zip Syracuse, UT 84075
Pressure Vacuum Vent Cap Test Form TP-201.1E
Site Diagram
(This site diagram is for reference only and is not drawn to scale)
Work Order:2356076
Site ID / Name:38442 / 7-Eleven 38442
Address:200 S 1000 West State ID 3000540
City:Syracuse State:UT Zip:84075