7-Eleven Air Quality Report
P.O. Box 711
Dallas, TX 75221
Test Date: 12/15/2023
Order Number: 2364860
Dear Regulator,
Enclosed are the results of recent testing performed at the following facility:
7-11 #35035
5687 S. HARRISON BLVD
State ID 1200561
SOUTH OGDEN, UT 84403
Testing performed:
Sincerely,
Dawn Kohlmeyer
Manager, Field Reporting
PVVC tested ==>RUL Manifolded
Final Test Result (Pass / Fail) ==>Fail
PVVC Manuf. ==>OPW Model Number ==>623V-3203
Is this Original or
Replacement?
Original
If this cap is being
replaced, check here:
Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)0.05 25 0.0530 Fail
Low High Measured
Pos Cracking (in H2O)2.50 6.00 0.13 Fail
Neg Leak Rate (CFH)0.21 100 0.2120 Fail
Low High Measured
Neg Cracking (in H2O)-10.00 -6.00 -0.16 Fail
PVVC tested ==>RUL Manifolded
Final Test Result (Pass / Fail) ==>Pass
PVVC Manuf. ==>OPW Model Number ==>723V
Is this Original or
Replacement?
Replacement Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)0.05 5 0.0106 Pass
Low High Measured
Pos Cracking (in H2O)2.50 6.00 3.63 Pass
Neg Leak Rate (CFH)0.21 14 0.0297 Pass
Low High Measured
Neg Cracking (in H2O)-10.00 -6.00 -7.41 Pass
PVVC tested ==>PUL Manifolded
Final Test Result (Pass / Fail) ==>Fail
PVVC Manuf. ==>OPW Model Number ==>623V-2203
Is this Original or
Replacement?
Original
If this cap is being
replaced, check here:
Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)0.05 25 0.0530 Fail
Low High Measured
Pos Cracking (in H2O)2.50 6.00 0.11 Fail
Neg Leak Rate (CFH)0.21 100 0.2120 Fail
Low High Measured
Neg Cracking (in H2O)-10.00 -6.00 -0.14 Fail
PVVC tested ==>PUL Manifolded
Final Test Result (Pass / Fail) ==>Pass
PVVC Manuf. ==>OPW Model Number ==>723V
Is this Original or
Replacement?
Replacement Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)0.05 7 0.0148 Pass
Low High Measured
Pos Cracking (in H2O)2.50 6.00 3.66 Pass
Neg Leak Rate (CFH)0.21 16 0.0339 Pass
Low High Measured
Neg Cracking (in H2O)-10.00 -6.00 -7.38 Pass
PVVC tested ==> Manifolded
Final Test Result (Pass / Fail) ==>
PVVC Manuf. ==>Model Number ==>
Is this Original or
Replacement?
Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)
Low High Measured
Pos Cracking (in H2O)
Neg Leak Rate (CFH)
Low High Measured
Neg Cracking (in H2O)
PVVC tested ==> Manifolded
Final Test Result (Pass / Fail) ==>
PVVC Manuf. ==>Model Number ==>
Is this Original or
Replacement?
Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)
Low High Measured
Pos Cracking (in H2O)
Neg Leak Rate (CFH)
Low High Measured
Neg Cracking (in H2O)
11000 N. MOPAC EXPRESSWAY, SUITE 500, AUSTIN, TX 78759
(800) 800-4633
QP-08-03-FF-02 Pressure Vacuum Vent Cap TP-201.1E Field Form
Rev C 1/27/2011
Site Overall Test Results: Pass
Total +ve LR: 0.0254
Total -ve LR: 0.0636
Test Date 12/15/2023
Technician Name David Mathie
WO #2364860
Facility Name / Loc #7-11 #35035 35035
Street 5687 S. HARRISON BLVD State ID 1200561
City, St, Zip SOUTH OGDEN, UT 84403
Pressure Vacuum Vent Cap Test Form TP-201.1E