Loading...
HomeMy WebLinkAboutDERR-2025-000385 WESTECH EQUIPMENT 195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307 801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054 PRESSURE/VACUUM VENT CAP LEAK RATES AND OPENING PRESSURES Facility Name: 7-Eleven 16345 Owner: 7-Eleven Inc. Address: 10580 South 700 East Address: P.O. Box 711 City, State, Zip: Sandy, Utah 84070 City, State, Zip: Dallas, Texas 75221 Facility I.D.#: 4001419 Phone #: 801-571-2662 Testing Company: Westech Phone #: 801-266-2545 Date: 4/10/24 This procedure is to determine pressure/vent cap specifications. See 40 CFR 63 CCCCCC for the inspection procedure. Tank Number 1 (West) 2 (Middle) 3 (East) Product Grade RUL RUL PUL PV Manufacturer OPW OPW OPW Model Number 623V 623V 623V PRESSURE TEST Passing 2” Leak Rate (CFH) <0.05 Measured 2” Leak Rate (CFH) New Cap New Cap New Cap Passing Positive Opening Pressure (Inches WC) 2.5 – 6.0 Measured Positive Opening Pressure (Inches WC) New Cap New Cap New Cap VACUUM TEST Passing -4” Leak Rate (CFH) <0.21 Measured -4” Leak Rate (CFH) New Cap New Cap New Cap Passing Negative Opening Pressure (Inched WC) 6.0 – 10.0 Measured Negative Opening Pressure (Inched WC) New Cap New Cap New Cap Test Results ☒Pass ☐Fail ☒Pass ☐Fail ☒Pass ☐Fail ☐Pass ☐Fail Comments: New PV Caps installed. Tester’s Name Taber DeHart, UT-0394 Tester’s Signature