7-Eleven Air Quality Report
P.O. Box 711
Dallas, TX 75221
Test Date: 9/27/2023
Order Number: 2362359
Dear Regulator,
Enclosed are the results of recent testing performed at the following facility:
7-ELEVEN 38848
7269 UNION PARK AVE
State ID 4002578
COTTONWOOD HEIGHTS, UT 84047
Testing performed:
Sincerely,
Dawn Kohlmeyer
Manager, Field Reporting
2 inch Pressure Decay Test
TP201.3
Store Information Testing Company
Site Name :7-ELEVEN 38848 Name :TANKNOLOGY INC.
Address :7269 UNION PARK AVE State ID 4002578
COTTONWOOD HEIGHTS, UT 84047
Address :11000 N. MoPac Expressway Suite 500
Austin, TX 78759
Phone :385-253-1965 Phone :(800) 800-4633
Stage I System?DUAL
Stage II System?NONE
Total # of Nozzles :8
Products per Nozzle :3
Tanks Manifolded ?No
Drop-Out tank present?NO
Total # of Tanks Tested :2
Tank Information :
Product Grade :
Tank Capacity, gallons :
Gasoline, gallons :
Ullage, gallons :
Testing Information :
Start Time :
Initial Pressure, wcg :
Pressure @ 1 minute(s) :
Pressure @ 2 minutes :
Pressure @ 3 minutes :
Pressure @ 4 minutes :
Pressure @ 5 minutes :
Allowable Final Pressure :
Pass/Fail (Enter "GF" Gross Failure)
Regular
RUL
19782
14885
4897
10:52
2.00
2.00
2.00
2.00
1.99
1.99
1.79
Pass
Premium
PUL
7901
6236
1665
11:04
2.00
1.99
1.98
1.97
1.96
1.95
1.49
Pass
Total
27683
21121
6562
All
Comments:
Tester :David Mathie Test Date :9/27/2023
Signature :Work Order :2362359
WO: 2362359
PVVC tested ==>RUL Manifolded
Final Test Result (Pass / Fail) ==>Fail
PVVC Manuf. ==>OPW Model Number ==>623V-2203
Is this Original or
Replacement?
Original
If this cap is being
replaced, check here:
Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)0.05 20 0.0424 Pass
Low High Measured
Pos Cracking (in H2O)2.50 6.00 2.30 Fail
Neg Leak Rate (CFH)0.21 100 0.2120 Fail
Low High Measured
Neg Cracking (in H2O)-10.00 -6.00 -5.42 Fail
PVVC tested ==>RUL Manifolded
Final Test Result (Pass / Fail) ==>Pass
PVVC Manuf. ==>OPW Model Number ==>723V
Is this Original or
Replacement?
Replacement Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)0.05 5 0.0106 Pass
Low High Measured
Pos Cracking (in H2O)2.50 6.00 3.72 Pass
Neg Leak Rate (CFH)0.21 12 0.0254 Pass
Low High Measured
Neg Cracking (in H2O)-10.00 -6.00 -8.47 Pass
PVVC tested ==>PUL Manifolded
Final Test Result (Pass / Fail) ==>Fail
PVVC Manuf. ==>OPW Model Number ==>623V-2203
Is this Original or
Replacement?
Original
If this cap is being
replaced, check here:
Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)0.05 20 0.0424 Pass
Low High Measured
Pos Cracking (in H2O)2.50 6.00 2.28 Fail
Neg Leak Rate (CFH)0.21 100 0.2120 Fail
Low High Measured
Neg Cracking (in H2O)-10.00 -6.00 -5.31 Fail
PVVC tested ==>PUL Manifolded
Final Test Result (Pass / Fail) ==>Pass
PVVC Manuf. ==>OPW Model Number ==>723V
Is this Original or
Replacement?
Replacement Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)0.05 7 0.0148 Pass
Low High Measured
Pos Cracking (in H2O)2.50 6.00 3.66 Pass
Neg Leak Rate (CFH)0.21 19 0.0403 Pass
Low High Measured
Neg Cracking (in H2O)-10.00 -6.00 -8.14 Pass
PVVC tested ==> Manifolded
Final Test Result (Pass / Fail) ==>
PVVC Manuf. ==>Model Number ==>
Is this Original or
Replacement?
Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)
Low High Measured
Pos Cracking (in H2O)
Neg Leak Rate (CFH)
Low High Measured
Neg Cracking (in H2O)
PVVC tested ==> Manifolded
Final Test Result (Pass / Fail) ==>
PVVC Manuf. ==>Model Number ==>
Is this Original or
Replacement?
Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)
Low High Measured
Pos Cracking (in H2O)
Neg Leak Rate (CFH)
Low High Measured
Neg Cracking (in H2O)
11000 N. MOPAC EXPRESSWAY, SUITE 500, AUSTIN, TX 78759
(800) 800-4633
QP-08-03-FF-02 Pressure Vacuum Vent Cap TP-201.1E Field Form
Rev C 1/27/2011
Site Overall Test Results: Pass
Total +ve LR: 0.0254
Total -ve LR: 0.0657
Test Date 9/27/2023
Technician Name David Mathie
WO #2362359
Facility Name / Loc #7-ELEVEN 38848 38848
Street 7269 UNION PARK AVE State ID 4002578
City, St, Zip COTTONWOOD HEIGHTS, UT 84047
Pressure Vacuum Vent Cap Test Form TP-201.1E
Site Diagram
(This site diagram is for reference only and is not drawn to scale)
Work Order:2362359
Site ID / Name:38848 / 7-ELEVEN 38848
Address:7269 UNION PARK AVE State ID 4002578
City:COTTONWOOD HEIGHTS State:UT Zip:84047