HomeMy WebLinkAboutDERR-2025-000380PV VENT CAP STAGE 1 PD 11000 N. MoPac Expressway, Suite 500 Austin, Texas 78759 Phone: (512) 451-6334 Fax: (512) 459-1459 Date Printed and Mailed: 9/28/2023 7-Eleven Air Quality Report P.O. Box 711 Dallas, TX 75221 Test Date: 9/27/2023 Order Number: 2362359 Dear Regulator, Enclosed are the results of recent testing performed at the following facility: 7-ELEVEN 38848 7269 UNION PARK AVE State ID 4002578 COTTONWOOD HEIGHTS, UT 84047 Testing performed: Sincerely, Dawn Kohlmeyer Manager, Field Reporting 2 inch Pressure Decay Test TP201.3 Store Information Testing Company Site Name :7-ELEVEN 38848 Name :TANKNOLOGY INC. Address :7269 UNION PARK AVE State ID 4002578 COTTONWOOD HEIGHTS, UT 84047 Address :11000 N. MoPac Expressway Suite 500 Austin, TX 78759 Phone :385-253-1965 Phone :(800) 800-4633 Stage I System?DUAL Stage II System?NONE Total # of Nozzles :8 Products per Nozzle :3 Tanks Manifolded ?No Drop-Out tank present?NO Total # of Tanks Tested :2 Tank Information : Product Grade : Tank Capacity, gallons : Gasoline, gallons : Ullage, gallons : Testing Information : Start Time : Initial Pressure, wcg : Pressure @ 1 minute(s) : Pressure @ 2 minutes : Pressure @ 3 minutes : Pressure @ 4 minutes : Pressure @ 5 minutes : Allowable Final Pressure : Pass/Fail (Enter "GF" Gross Failure) Regular RUL 19782 14885 4897 10:52 2.00 2.00 2.00 2.00 1.99 1.99 1.79 Pass Premium PUL 7901 6236 1665 11:04 2.00 1.99 1.98 1.97 1.96 1.95 1.49 Pass Total 27683 21121 6562 All Comments: Tester :David Mathie Test Date :9/27/2023 Signature :Work Order :2362359 WO: 2362359 PVVC tested ==>RUL Manifolded Final Test Result (Pass / Fail) ==>Fail PVVC Manuf. ==>OPW Model Number ==>623V-2203 Is this Original or Replacement? Original If this cap is being replaced, check here: Manf Spec (CFH) Measured Leak Rate in ml/Min; Cracking (in H2O) Calc CFH (ml/min x .00212) Result (Pass /Fail) Pos Leak Rate(CFH)0.05 20 0.0424 Pass Low High Measured Pos Cracking (in H2O)2.50 6.00 2.30 Fail Neg Leak Rate (CFH)0.21 100 0.2120 Fail Low High Measured Neg Cracking (in H2O)-10.00 -6.00 -5.42 Fail PVVC tested ==>RUL Manifolded Final Test Result (Pass / Fail) ==>Pass PVVC Manuf. ==>OPW Model Number ==>723V Is this Original or Replacement? Replacement Manf Spec (CFH) Measured Leak Rate in ml/Min; Cracking (in H2O) Calc CFH (ml/min x .00212) Result (Pass /Fail) Pos Leak Rate(CFH)0.05 5 0.0106 Pass Low High Measured Pos Cracking (in H2O)2.50 6.00 3.72 Pass Neg Leak Rate (CFH)0.21 12 0.0254 Pass Low High Measured Neg Cracking (in H2O)-10.00 -6.00 -8.47 Pass PVVC tested ==>PUL Manifolded Final Test Result (Pass / Fail) ==>Fail PVVC Manuf. ==>OPW Model Number ==>623V-2203 Is this Original or Replacement? Original If this cap is being replaced, check here: Manf Spec (CFH) Measured Leak Rate in ml/Min; Cracking (in H2O) Calc CFH (ml/min x .00212) Result (Pass /Fail) Pos Leak Rate(CFH)0.05 20 0.0424 Pass Low High Measured Pos Cracking (in H2O)2.50 6.00 2.28 Fail Neg Leak Rate (CFH)0.21 100 0.2120 Fail Low High Measured Neg Cracking (in H2O)-10.00 -6.00 -5.31 Fail PVVC tested ==>PUL Manifolded Final Test Result (Pass / Fail) ==>Pass PVVC Manuf. ==>OPW Model Number ==>723V Is this Original or Replacement? Replacement Manf Spec (CFH) Measured Leak Rate in ml/Min; Cracking (in H2O) Calc CFH (ml/min x .00212) Result (Pass /Fail) Pos Leak Rate(CFH)0.05 7 0.0148 Pass Low High Measured Pos Cracking (in H2O)2.50 6.00 3.66 Pass Neg Leak Rate (CFH)0.21 19 0.0403 Pass Low High Measured Neg Cracking (in H2O)-10.00 -6.00 -8.14 Pass PVVC tested ==> Manifolded Final Test Result (Pass / Fail) ==> PVVC Manuf. ==>Model Number ==> Is this Original or Replacement? Manf Spec (CFH) Measured Leak Rate in ml/Min; Cracking (in H2O) Calc CFH (ml/min x .00212) Result (Pass /Fail) Pos Leak Rate(CFH) Low High Measured Pos Cracking (in H2O) Neg Leak Rate (CFH) Low High Measured Neg Cracking (in H2O) PVVC tested ==> Manifolded Final Test Result (Pass / Fail) ==> PVVC Manuf. ==>Model Number ==> Is this Original or Replacement? Manf Spec (CFH) Measured Leak Rate in ml/Min; Cracking (in H2O) Calc CFH (ml/min x .00212) Result (Pass /Fail) Pos Leak Rate(CFH) Low High Measured Pos Cracking (in H2O) Neg Leak Rate (CFH) Low High Measured Neg Cracking (in H2O) 11000 N. MOPAC EXPRESSWAY, SUITE 500, AUSTIN, TX 78759 (800) 800-4633 QP-08-03-FF-02 Pressure Vacuum Vent Cap TP-201.1E Field Form Rev C 1/27/2011 Site Overall Test Results: Pass Total +ve LR: 0.0254 Total -ve LR: 0.0657 Test Date 9/27/2023 Technician Name David Mathie WO #2362359 Facility Name / Loc #7-ELEVEN 38848 38848 Street 7269 UNION PARK AVE State ID 4002578 City, St, Zip COTTONWOOD HEIGHTS, UT 84047 Pressure Vacuum Vent Cap Test Form TP-201.1E Site Diagram (This site diagram is for reference only and is not drawn to scale) Work Order:2362359 Site ID / Name:38848 / 7-ELEVEN 38848 Address:7269 UNION PARK AVE State ID 4002578 City:COTTONWOOD HEIGHTS State:UT Zip:84047