7-Eleven Air Quality Report
P.O. Box 711
Dallas, TX 75221
Test Date: 12/13/2023
Order Number: 2363626
Dear Regulator,
Enclosed are the results of recent testing performed at the following facility:
7-ELEVEN 34991 MKT 1606
7953 SOUTH AIRPORT ROAD
State ID 4002224
WEST JORDAN, UT 84088
Testing performed:
Sincerely,
Dawn Kohlmeyer
Manager, Field Reporting
2 inch Pressure Decay Test
TP201.3
Store Information Testing Company
Site Name
:7-ELEVEN 34991 MKT 1606 Name :TANKNOLOGY INC.
Address :7953 SOUTH AIRPORT ROAD State ID
4002224
WEST JORDAN, UT 84088
Address
:
11000 N. MoPac Expressway Suite
500
Austin, TX 78759
Phone :801-280-6687 Phone :(800) 800-4633
Stage I System?DUAL
Stage II System?STUB UP
Total # of Nozzles :10
Products per Nozzle :3
Tanks Manifolded ?Yes
Drop-Out tank present?NO
Total # of Tanks Tested :2
Tank Information :
Product Grade :
Tank Capacity, gallons :
Gasoline, gallons :
Ullage, gallons :
Testing Information :
Start Time :
Initial Pressure, wcg :
Pressure @ 1 minute(s) :
Pressure @ 2 minutes :
Pressure @ 3 minutes :
Pressure @ 4 minutes :
Pressure @ 5 minutes :
Allowable Final Pressure :
Pass/Fail (Enter "GF" Gross Failure)
RUL
REG UNLEAD
19164
11427
7737
PREM
PREMIUM
11594
6427
5167
13:33
2.00
1.99
1.98
1.97
1.96
1.95
1.92
Pass
Total
30758
17854
12904
All
13:33
2.00
1.99
1.98
1.97
1.96
1.95
1.92
Pass
Comments:
Tester :David Mathie Test Date :12/13/2023
Signature :Work Order :2363626
WO: 2363626
PVVC tested ==>RUL Manifolded
Final Test Result (Pass / Fail) ==>Fail
PVVC Manuf. ==>OPW Model Number ==>723V
Is this Original or
Replacement?
Original
If this cap is being
replaced, check here:
Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)0.05 25 0.0530 Fail
Low High Measured
Pos Cracking (in H2O)2.50 6.00 1.29 Fail
Neg Leak Rate (CFH)0.21 100 0.2120 Fail
Low High Measured
Neg Cracking (in H2O)-10.00 -6.00 -1.26 Fail
PVVC tested ==>RUL Manifolded
Final Test Result (Pass / Fail) ==>Pass
PVVC Manuf. ==>OPW Model Number ==>723V
Is this Original or
Replacement?
Replacement Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)0.05 5 0.0106 Pass
Low High Measured
Pos Cracking (in H2O)2.50 6.00 3.91 Pass
Neg Leak Rate (CFH)0.21 16 0.0339 Pass
Low High Measured
Neg Cracking (in H2O)-10.00 -6.00 -8.03 Pass
PVVC tested ==>PUL Manifolded
Final Test Result (Pass / Fail) ==>Fail
PVVC Manuf. ==>OPW Model Number ==>723V
Is this Original or
Replacement?
Original
If this cap is being
replaced, check here:
Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)0.05 20 0.0424 Pass
Low High Measured
Pos Cracking (in H2O)2.50 6.00 2.42 Fail
Neg Leak Rate (CFH)0.21 100 0.2120 Fail
Low High Measured
Neg Cracking (in H2O)-10.00 -6.00 -5.50 Fail
PVVC tested ==>PUL Manifolded
Final Test Result (Pass / Fail) ==>Pass
PVVC Manuf. ==>OPW Model Number ==>723V
Is this Original or
Replacement?
Replacement Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)0.05 6 0.0127 Pass
Low High Measured
Pos Cracking (in H2O)2.50 6.00 3.72 Pass
Neg Leak Rate (CFH)0.21 18 0.0382 Pass
Low High Measured
Neg Cracking (in H2O)-10.00 -6.00 -7.94 Pass
PVVC tested ==> Manifolded
Final Test Result (Pass / Fail) ==>
PVVC Manuf. ==>Model Number ==>
Is this Original or
Replacement?
Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)
Low High Measured
Pos Cracking (in H2O)
Neg Leak Rate (CFH)
Low High Measured
Neg Cracking (in H2O)
PVVC tested ==> Manifolded
Final Test Result (Pass / Fail) ==>
PVVC Manuf. ==>Model Number ==>
Is this Original or
Replacement?
Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)
Low High Measured
Pos Cracking (in H2O)
Neg Leak Rate (CFH)
Low High Measured
Neg Cracking (in H2O)
11000 N. MOPAC EXPRESSWAY, SUITE 500, AUSTIN, TX 78759
(800) 800-4633
QP-08-03-FF-02 Pressure Vacuum Vent Cap TP-201.1E Field Form
Rev C 1/27/2011
Site Overall Test Results: Pass
Total +ve LR: 0.0233
Total -ve LR: 0.0721
Test Date 12/13/2023
Technician Name David Mathie
WO #2363626
Facility Name / Loc #7-ELEVEN 34991 MKT 1606 34991
Street 7953 SOUTH AIRPORT ROAD State ID 4002224
City, St, Zip WEST JORDAN, UT 84088
Pressure Vacuum Vent Cap Test Form TP-201.1E
Site Diagram
(This site diagram is for reference only and is not drawn to scale)
Work Order:2363626
Site ID / Name:34991 / 7-ELEVEN 34991 MKT 1606
Address:7953 SOUTH AIRPORT ROAD State ID 4002224
City:WEST JORDAN State:UT Zip:84088