HomeMy WebLinkAboutDERR-2025-000367PV VENT CAP
STAGE 1 PD
11000 N. MoPac Expressway, Suite 500
Austin, Texas 78759
Phone: (512) 451-6334
Fax: (512) 459-1459 Date Printed and Mailed: 11/15/2023
7-Eleven Air Quality Report
P.O. Box 711
Dallas, TX 75221
Test Date: 11/14/2023
Order Number: 2363161
Dear Regulator,
Enclosed are the results of recent testing performed at the following facility:
7-ELEVEN 38710
405 E Layton Pkwy
State ID 3000546
Layton, UT 84041
Testing performed:
Sincerely,
Dawn Kohlmeyer
Manager, Field Reporting
2 inch Pressure Decay Test
TP201.3
Store Information Testing Company
Site Name :7-ELEVEN 38710 Name :TANKNOLOGY INC.
Address :405 E Layton Pkwy State ID 3000546
Layton, UT 84041
Address :11000 N. MoPac Expressway Suite 500
Austin, TX 78759
Phone :801-200-0648 Phone :(800) 800-4633
Stage I System?DUAL
Stage II System?NONE
Total # of Nozzles :12
Products per Nozzle :3
Tanks Manifolded ?No
Drop-Out tank present?NO
Total # of Tanks Tested :2
Tank Information :
Product Grade :
Tank Capacity, gallons :
Gasoline, gallons :
Ullage, gallons :
Testing Information :
Start Time :
Initial Pressure, wcg :
Pressure @ 1 minute(s) :
Pressure @ 2 minutes :
Pressure @ 3 minutes :
Pressure @ 4 minutes :
Pressure @ 5 minutes :
Allowable Final Pressure :
Pass/Fail (Enter "GF" Gross Failure)
TN1
RUL
19930
15030
4900
11:34
2.00
2.00
2.00
2.00
1.99
1.99
1.81
Pass
TNK2
PUL
8039
5759
2280
12:06
2.00
1.99
1.98
1.97
1.96
1.95
1.61
Pass
Total
27969
20789
7180
All
Comments:
Tester :David Mathie Test Date :11/14/2023
Signature :Work Order :2363161
WO: 2363161
PVVC tested ==>RUL Manifolded
Final Test Result (Pass / Fail) ==>Fail
PVVC Manuf. ==>OPW Model Number ==>623V-2203
Is this Original or
Replacement?
Original
If this cap is being
replaced, check here:
Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)0.05 20 0.0424 Pass
Low High Measured
Pos Cracking (in H2O)2.50 6.00 2.08 Fail
Neg Leak Rate (CFH)0.21 100 0.2120 Fail
Low High Measured
Neg Cracking (in H2O)-10.00 -6.00 -4.20 Fail
PVVC tested ==>RUL Manifolded
Final Test Result (Pass / Fail) ==>Pass
PVVC Manuf. ==>OPW Model Number ==>723V
Is this Original or
Replacement?
Replacement Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)0.05 5 0.0106 Pass
Low High Measured
Pos Cracking (in H2O)2.50 6.00 3.62 Pass
Neg Leak Rate (CFH)0.21 16 0.0339 Pass
Low High Measured
Neg Cracking (in H2O)-10.00 -6.00 -7.97 Pass
PVVC tested ==>PUL Manifolded
Final Test Result (Pass / Fail) ==>Fail
PVVC Manuf. ==>OPW Model Number ==>623V-2203
Is this Original or
Replacement?
Original
If this cap is being
replaced, check here:
Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)0.05 20 0.0424 Pass
Low High Measured
Pos Cracking (in H2O)2.50 6.00 2.11 Fail
Neg Leak Rate (CFH)0.21 100 0.2120 Fail
Low High Measured
Neg Cracking (in H2O)-10.00 -6.00 -4.30 Fail
PVVC tested ==>PUL Manifolded
Final Test Result (Pass / Fail) ==>Pass
PVVC Manuf. ==>OPW Model Number ==>723V
Is this Original or
Replacement?
Replacement Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)0.05 6 0.0127 Pass
Low High Measured
Pos Cracking (in H2O)2.50 6.00 3.67 Pass
Neg Leak Rate (CFH)0.21 18 0.0382 Pass
Low High Measured
Neg Cracking (in H2O)-10.00 -6.00 -8.02 Pass
PVVC tested ==> Manifolded
Final Test Result (Pass / Fail) ==>
PVVC Manuf. ==>Model Number ==>
Is this Original or
Replacement?
Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)
Low High Measured
Pos Cracking (in H2O)
Neg Leak Rate (CFH)
Low High Measured
Neg Cracking (in H2O)
PVVC tested ==> Manifolded
Final Test Result (Pass / Fail) ==>
PVVC Manuf. ==>Model Number ==>
Is this Original or
Replacement?
Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)
Low High Measured
Pos Cracking (in H2O)
Neg Leak Rate (CFH)
Low High Measured
Neg Cracking (in H2O)
11000 N. MOPAC EXPRESSWAY, SUITE 500, AUSTIN, TX 78759
(800) 800-4633
QP-08-03-FF-02 Pressure Vacuum Vent Cap TP-201.1E Field Form
Rev C 1/27/2011
Site Overall Test Results: Pass
Total +ve LR: 0.0233
Total -ve LR: 0.0721
Test Date 11/14/2023
Technician Name David Mathie
WO #2363161
Facility Name / Loc #7-ELEVEN 38710 38710
Street 405 E Layton Pkwy State ID 3000546
City, St, Zip Layton, UT 84041
Pressure Vacuum Vent Cap Test Form TP-201.1E
Site Diagram
(This site diagram is for reference only and is not drawn to scale)
Work Order:2363161
Site ID / Name:38710 / 7-ELEVEN 38710
Address:405 E Layton Pkwy State ID 3000546
City:Layton State:UT Zip:84041