HomeMy WebLinkAboutDERR-2025-000367PV VENT CAP STAGE 1 PD 11000 N. MoPac Expressway, Suite 500 Austin, Texas 78759 Phone: (512) 451-6334 Fax: (512) 459-1459 Date Printed and Mailed: 11/15/2023 7-Eleven Air Quality Report P.O. Box 711 Dallas, TX 75221 Test Date: 11/14/2023 Order Number: 2363161 Dear Regulator, Enclosed are the results of recent testing performed at the following facility: 7-ELEVEN 38710 405 E Layton Pkwy State ID 3000546 Layton, UT 84041 Testing performed: Sincerely, Dawn Kohlmeyer Manager, Field Reporting 2 inch Pressure Decay Test TP201.3 Store Information Testing Company Site Name :7-ELEVEN 38710 Name :TANKNOLOGY INC. Address :405 E Layton Pkwy State ID 3000546 Layton, UT 84041 Address :11000 N. MoPac Expressway Suite 500 Austin, TX 78759 Phone :801-200-0648 Phone :(800) 800-4633 Stage I System?DUAL Stage II System?NONE Total # of Nozzles :12 Products per Nozzle :3 Tanks Manifolded ?No Drop-Out tank present?NO Total # of Tanks Tested :2 Tank Information : Product Grade : Tank Capacity, gallons : Gasoline, gallons : Ullage, gallons : Testing Information : Start Time : Initial Pressure, wcg : Pressure @ 1 minute(s) : Pressure @ 2 minutes : Pressure @ 3 minutes : Pressure @ 4 minutes : Pressure @ 5 minutes : Allowable Final Pressure : Pass/Fail (Enter "GF" Gross Failure) TN1 RUL 19930 15030 4900 11:34 2.00 2.00 2.00 2.00 1.99 1.99 1.81 Pass TNK2 PUL 8039 5759 2280 12:06 2.00 1.99 1.98 1.97 1.96 1.95 1.61 Pass Total 27969 20789 7180 All Comments: Tester :David Mathie Test Date :11/14/2023 Signature :Work Order :2363161 WO: 2363161 PVVC tested ==>RUL Manifolded Final Test Result (Pass / Fail) ==>Fail PVVC Manuf. ==>OPW Model Number ==>623V-2203 Is this Original or Replacement? Original If this cap is being replaced, check here: Manf Spec (CFH) Measured Leak Rate in ml/Min; Cracking (in H2O) Calc CFH (ml/min x .00212) Result (Pass /Fail) Pos Leak Rate(CFH)0.05 20 0.0424 Pass Low High Measured Pos Cracking (in H2O)2.50 6.00 2.08 Fail Neg Leak Rate (CFH)0.21 100 0.2120 Fail Low High Measured Neg Cracking (in H2O)-10.00 -6.00 -4.20 Fail PVVC tested ==>RUL Manifolded Final Test Result (Pass / Fail) ==>Pass PVVC Manuf. ==>OPW Model Number ==>723V Is this Original or Replacement? Replacement Manf Spec (CFH) Measured Leak Rate in ml/Min; Cracking (in H2O) Calc CFH (ml/min x .00212) Result (Pass /Fail) Pos Leak Rate(CFH)0.05 5 0.0106 Pass Low High Measured Pos Cracking (in H2O)2.50 6.00 3.62 Pass Neg Leak Rate (CFH)0.21 16 0.0339 Pass Low High Measured Neg Cracking (in H2O)-10.00 -6.00 -7.97 Pass PVVC tested ==>PUL Manifolded Final Test Result (Pass / Fail) ==>Fail PVVC Manuf. ==>OPW Model Number ==>623V-2203 Is this Original or Replacement? Original If this cap is being replaced, check here: Manf Spec (CFH) Measured Leak Rate in ml/Min; Cracking (in H2O) Calc CFH (ml/min x .00212) Result (Pass /Fail) Pos Leak Rate(CFH)0.05 20 0.0424 Pass Low High Measured Pos Cracking (in H2O)2.50 6.00 2.11 Fail Neg Leak Rate (CFH)0.21 100 0.2120 Fail Low High Measured Neg Cracking (in H2O)-10.00 -6.00 -4.30 Fail PVVC tested ==>PUL Manifolded Final Test Result (Pass / Fail) ==>Pass PVVC Manuf. ==>OPW Model Number ==>723V Is this Original or Replacement? Replacement Manf Spec (CFH) Measured Leak Rate in ml/Min; Cracking (in H2O) Calc CFH (ml/min x .00212) Result (Pass /Fail) Pos Leak Rate(CFH)0.05 6 0.0127 Pass Low High Measured Pos Cracking (in H2O)2.50 6.00 3.67 Pass Neg Leak Rate (CFH)0.21 18 0.0382 Pass Low High Measured Neg Cracking (in H2O)-10.00 -6.00 -8.02 Pass PVVC tested ==> Manifolded Final Test Result (Pass / Fail) ==> PVVC Manuf. ==>Model Number ==> Is this Original or Replacement? Manf Spec (CFH) Measured Leak Rate in ml/Min; Cracking (in H2O) Calc CFH (ml/min x .00212) Result (Pass /Fail) Pos Leak Rate(CFH) Low High Measured Pos Cracking (in H2O) Neg Leak Rate (CFH) Low High Measured Neg Cracking (in H2O) PVVC tested ==> Manifolded Final Test Result (Pass / Fail) ==> PVVC Manuf. ==>Model Number ==> Is this Original or Replacement? Manf Spec (CFH) Measured Leak Rate in ml/Min; Cracking (in H2O) Calc CFH (ml/min x .00212) Result (Pass /Fail) Pos Leak Rate(CFH) Low High Measured Pos Cracking (in H2O) Neg Leak Rate (CFH) Low High Measured Neg Cracking (in H2O) 11000 N. MOPAC EXPRESSWAY, SUITE 500, AUSTIN, TX 78759 (800) 800-4633 QP-08-03-FF-02 Pressure Vacuum Vent Cap TP-201.1E Field Form Rev C 1/27/2011 Site Overall Test Results: Pass Total +ve LR: 0.0233 Total -ve LR: 0.0721 Test Date 11/14/2023 Technician Name David Mathie WO #2363161 Facility Name / Loc #7-ELEVEN 38710 38710 Street 405 E Layton Pkwy State ID 3000546 City, St, Zip Layton, UT 84041 Pressure Vacuum Vent Cap Test Form TP-201.1E Site Diagram (This site diagram is for reference only and is not drawn to scale) Work Order:2363161 Site ID / Name:38710 / 7-ELEVEN 38710 Address:405 E Layton Pkwy State ID 3000546 City:Layton State:UT Zip:84041