HomeMy WebLinkAboutDDW-2007-000935Date: 06/26/07
Kearns Improvement District
attn: John Lawson
P.O. Box 18608
Kearns, UT 84118
Individual pages or sections of this report may not be separated when using the information for
regulatory compliance.
The analyses presented on this report were performed in accordance with National Environmental
Laboratory Accreditation Program (NELAP), Section 5.13.
Please feel free to contact us at (801) 262-7299 or (801) 262-7378 (fax) if you have questions or
comments regarding this report. Our web site is located at www.chemtechford.com.
Dave Gayer
Laboratory Director
dave@chemtechford.com
Linda Daniels
Customer Representative
linda@chemtechford.com
Page 1 of 9
This is the final report for project: 84716
Chemtech-Ford Laboratories
Serving the Intermountain West since 1953
6100 South Stratler
Murray, UT 84107
Phone: 801-262-7299
Fax: 801-262-7378
Dave Gayer, Laboratory Director
Approved By:
Certificate of Analysis
Lab Group No.:
Lab No.:07 05748
84716
Chemtech-Ford Laboratories
Name:
Sample Site:
Sample ID:
System No:
Sample Type:
Kearns Improvement District
Well #1
07 05748
18011
Drinking Water
Sample Date:
Receipt Date:
Sampler:
Sample Source:
Project:
6/7/2007 1:39 PM
6/8/2007 9:35 AM
LAWSON
Sample
Result
Analysis
Date
Mimimum
Reporting
Limit
Parameter Units Method FlagAnalysis
Time
Analyst
Initials
Group A - Inorganic
ND mg/LCyanide, Total 0.002 ASTM D2036 6/13/2007 16:00 TP
0.3 mg/LFluoride, IC 0.1 EPA 300.0 6/8/2007 15:00 TSM
530 mg/LSolids, Total Dissolved (TDS) 5 SM 2540C 6/13/2007 12:00 JSH
25 mg/LSulfate, IC 1 EPA 300.0 6/8/2007 15:00 TSM
0.20 NTUTurbidity0.02 EPA 180.1 6/8/2007 16:00 JSH
Group B - Metals
ND mg/LAntimony, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
0.0095 mg/LArsenic, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
0.079 mg/LBarium, Total, ICP 0.005 EPA 200.7 6/11/2007 16:16 MJB
ND mg/LBeryllium, Total, ICP 0.001 EPA 200.7 6/11/2007 16:16 MJB
ND mg/LCadmium, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
0.0031 mg/LChromium, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
ND mg/LMercury, Total, ICP/MS 0.0002 EPA 200.8 6/13/2007 14:30 MJB
0.0075 mg/LNickel, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
0.0029 mg/LSelenium, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
31.7 mg/LSodium, Total, ICP 0.5 EPA 200.7 6/11/2007 16:16 MJB
0.0016 mg/LThallium, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
ND = Not detected at the corresponding Minimum Reporting Limit.
1 mg/L = one milligram per liter = 1 part per million.
1 ug/L = one microgram per liter = 1 part per billion.
APH = The test was performed past the EPA specified holding time.
H = A high bias is suspected.
I = The analysis experienced a matrix interference which may have affected the results.
J = The result is positive and estimated. The result falls between the Minimum Reporting Limit and the Method Detection Limit.
L = A low bias is suspected.
O = The analysis was performed by an outside contract laboratory.
R = The value represents a reanalysis.
SPH = The sample was submitted for analysis past the EPA specified holding time.
Abbreviations
Flag Descriptions
Page 2 of 9
6100 South Stratler
Murray, UT 84107
801-262-7299 Office
801-262-7378 Fax
Certificate of Analysis
Lab Group No.:
Lab No.:07 05749
84716
Chemtech-Ford Laboratories
Name:
Sample Site:
Sample ID:
System No:
Sample Type:
Kearns Improvement District
Well #3
07 05749
18011
Drinking Water
Sample Date:
Receipt Date:
Sampler:
Sample Source:
Project:
6/7/2007 1:47 PM
6/8/2007 9:35 AM
LAWSON
Sample
Result
Analysis
Date
Mimimum
Reporting
Limit
Parameter Units Method FlagAnalysis
Time
Analyst
Initials
Group A - Inorganic
ND mg/LCyanide, Total 0.002 ASTM D2036 6/13/2007 16:00 TP
0.3 mg/LFluoride, IC 0.1 EPA 300.0 6/8/2007 15:00 TSM
567 mg/LSolids, Total Dissolved (TDS) 5 SM 2540C 6/13/2007 12:00 JSH
27 mg/LSulfate, IC 1 EPA 300.0 6/8/2007 15:00 TSM
0.10 NTUTurbidity0.02 EPA 180.1 6/8/2007 16:00 JSH
Group B - Metals
ND mg/LAntimony, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
0.0056 mg/LArsenic, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
0.172 mg/LBarium, Total, ICP 0.005 EPA 200.7 6/11/2007 16:16 MJB
ND mg/LBeryllium, Total, ICP 0.001 EPA 200.7 6/11/2007 16:16 MJB
ND mg/LCadmium, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
0.0043 mg/LChromium, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
ND mg/LMercury, Total, ICP/MS 0.0002 EPA 200.8 6/13/2007 14:30 MJB
0.0042 mg/LNickel, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
0.0023 mg/LSelenium, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
44.1 mg/LSodium, Total, ICP 0.5 EPA 200.7 6/11/2007 16:16 MJB
ND mg/LThallium, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
ND = Not detected at the corresponding Minimum Reporting Limit.
1 mg/L = one milligram per liter = 1 part per million.
1 ug/L = one microgram per liter = 1 part per billion.
APH = The test was performed past the EPA specified holding time.
H = A high bias is suspected.
I = The analysis experienced a matrix interference which may have affected the results.
J = The result is positive and estimated. The result falls between the Minimum Reporting Limit and the Method Detection Limit.
L = A low bias is suspected.
O = The analysis was performed by an outside contract laboratory.
R = The value represents a reanalysis.
SPH = The sample was submitted for analysis past the EPA specified holding time.
Abbreviations
Flag Descriptions
Page 3 of 9
6100 South Stratler
Murray, UT 84107
801-262-7299 Office
801-262-7378 Fax
Certificate of Analysis
Lab Group No.:
Lab No.:07 05750
84716
Chemtech-Ford Laboratories
Name:
Sample Site:
Sample ID:
System No:
Sample Type:
Kearns Improvement District
Well #4
07 05750
18011
Drinking Water
Sample Date:
Receipt Date:
Sampler:
Sample Source:
Project:
6/7/2007 1:58 PM
6/8/2007 9:35 AM
LAWSON
Sample
Result
Analysis
Date
Mimimum
Reporting
Limit
Parameter Units Method FlagAnalysis
Time
Analyst
Initials
Group A - Inorganic
ND mg/LCyanide, Total 0.002 ASTM D2036 6/13/2007 16:00 TP
0.5 mg/LFluoride, IC 0.1 EPA 300.0 6/8/2007 15:00 TSM
741 mg/LSolids, Total Dissolved (TDS) 5 SM 2540C 6/13/2007 12:00 JSH
36 mg/LSulfate, IC 1 EPA 300.0 6/8/2007 15:00 TSM
0.15 NTUTurbidity0.02 EPA 180.1 6/8/2007 16:00 JSH
Group B - Metals
ND mg/LAntimony, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
0.0116 mg/LArsenic, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
0.107 mg/LBarium, Total, ICP 0.005 EPA 200.7 6/11/2007 16:16 MJB
ND mg/LBeryllium, Total, ICP 0.001 EPA 200.7 6/11/2007 16:16 MJB
ND mg/LCadmium, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
0.0013 mg/LChromium, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
ND mg/LMercury, Total, ICP/MS 0.0002 EPA 200.8 6/13/2007 14:30 MJB
0.0032 mg/LNickel, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
0.0025 mg/LSelenium, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
61.5 mg/LSodium, Total, ICP 0.5 EPA 200.7 6/11/2007 16:16 MJB
ND mg/LThallium, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
ND = Not detected at the corresponding Minimum Reporting Limit.
1 mg/L = one milligram per liter = 1 part per million.
1 ug/L = one microgram per liter = 1 part per billion.
APH = The test was performed past the EPA specified holding time.
H = A high bias is suspected.
I = The analysis experienced a matrix interference which may have affected the results.
J = The result is positive and estimated. The result falls between the Minimum Reporting Limit and the Method Detection Limit.
L = A low bias is suspected.
O = The analysis was performed by an outside contract laboratory.
R = The value represents a reanalysis.
SPH = The sample was submitted for analysis past the EPA specified holding time.
Abbreviations
Flag Descriptions
Page 4 of 9
6100 South Stratler
Murray, UT 84107
801-262-7299 Office
801-262-7378 Fax
Certificate of Analysis
Lab Group No.:
Lab No.:07 05751
84716
Chemtech-Ford Laboratories
Name:
Sample Site:
Sample ID:
System No:
Sample Type:
Kearns Improvement District
Well #5
07 05751
18011
Drinking Water
Sample Date:
Receipt Date:
Sampler:
Sample Source:
Project:
6/7/2007 2:05 PM
6/8/2007 9:35 AM
LAWSON
Sample
Result
Analysis
Date
Mimimum
Reporting
Limit
Parameter Units Method FlagAnalysis
Time
Analyst
Initials
Group A - Inorganic
ND mg/LCyanide, Total 0.002 ASTM D2036 6/13/2007 16:00 TP
0.5 mg/LFluoride, IC 0.1 EPA 300.0 6/8/2007 15:00 TSM
718 mg/LSolids, Total Dissolved (TDS) 5 SM 2540C 6/13/2007 12:00 JSH
34 mg/LSulfate, IC 1 EPA 300.0 6/8/2007 15:00 TSM
0.10 NTUTurbidity0.02 EPA 180.1 6/8/2007 16:00 JSH
Group B - Metals
ND mg/LAntimony, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
0.0118 mg/LArsenic, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
0.106 mg/LBarium, Total, ICP 0.005 EPA 200.7 6/11/2007 16:16 MJB
ND mg/LBeryllium, Total, ICP 0.001 EPA 200.7 6/11/2007 16:16 MJB
ND mg/LCadmium, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
0.0011 mg/LChromium, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
ND mg/LMercury, Total, ICP/MS 0.0002 EPA 200.8 6/13/2007 14:30 MJB
0.0035 mg/LNickel, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
0.0022 mg/LSelenium, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
59.2 mg/LSodium, Total, ICP 0.5 EPA 200.7 6/11/2007 16:16 MJB
ND mg/LThallium, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
ND = Not detected at the corresponding Minimum Reporting Limit.
1 mg/L = one milligram per liter = 1 part per million.
1 ug/L = one microgram per liter = 1 part per billion.
APH = The test was performed past the EPA specified holding time.
H = A high bias is suspected.
I = The analysis experienced a matrix interference which may have affected the results.
J = The result is positive and estimated. The result falls between the Minimum Reporting Limit and the Method Detection Limit.
L = A low bias is suspected.
O = The analysis was performed by an outside contract laboratory.
R = The value represents a reanalysis.
SPH = The sample was submitted for analysis past the EPA specified holding time.
Abbreviations
Flag Descriptions
Page 5 of 9
6100 South Stratler
Murray, UT 84107
801-262-7299 Office
801-262-7378 Fax
Certificate of Analysis
Lab Group No.:
Lab No.:07 05752
84716
Chemtech-Ford Laboratories
Name:
Sample Site:
Sample ID:
System No:
Sample Type:
Kearns Improvement District
Well #9
07 05752
18011
Drinking Water
Sample Date:
Receipt Date:
Sampler:
Sample Source:
Project:
6/8/2007 9:17 AM
6/8/2007 9:35 AM
LAWSON
Sample
Result
Analysis
Date
Mimimum
Reporting
Limit
Parameter Units Method FlagAnalysis
Time
Analyst
Initials
Group A - Inorganic
ND mg/LCyanide, Total 0.002 ASTM D2036 6/13/2007 16:00 TP
0.8 mg/LFluoride, IC 0.1 EPA 300.0 6/8/2007 15:00 TSM
729 mg/LSolids, Total Dissolved (TDS) 5 SM 2540C 6/13/2007 12:00 JSH
73 mg/LSulfate, IC 1 EPA 300.0 6/8/2007 15:00 TSM
0.15 NTUTurbidity0.02 EPA 180.1 6/8/2007 16:00 JSH
Group B - Metals
ND mg/LAntimony, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
0.0132 mg/LArsenic, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
0.081 mg/LBarium, Total, ICP 0.005 EPA 200.7 6/11/2007 16:16 MJB
ND mg/LBeryllium, Total, ICP 0.001 EPA 200.7 6/11/2007 16:16 MJB
ND mg/LCadmium, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
0.0009 mg/LChromium, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
ND mg/LMercury, Total, ICP/MS 0.0002 EPA 200.8 6/13/2007 14:30 MJB
0.0025 mg/LNickel, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
0.0024 mg/LSelenium, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
108 mg/LSodium, Total, ICP 0.5 EPA 200.7 6/11/2007 16:16 MJB
ND mg/LThallium, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
ND = Not detected at the corresponding Minimum Reporting Limit.
1 mg/L = one milligram per liter = 1 part per million.
1 ug/L = one microgram per liter = 1 part per billion.
APH = The test was performed past the EPA specified holding time.
H = A high bias is suspected.
I = The analysis experienced a matrix interference which may have affected the results.
J = The result is positive and estimated. The result falls between the Minimum Reporting Limit and the Method Detection Limit.
L = A low bias is suspected.
O = The analysis was performed by an outside contract laboratory.
R = The value represents a reanalysis.
SPH = The sample was submitted for analysis past the EPA specified holding time.
Abbreviations
Flag Descriptions
Page 6 of 9
6100 South Stratler
Murray, UT 84107
801-262-7299 Office
801-262-7378 Fax
Certificate of Analysis
Lab Group No.:
Lab No.:07 05753
84716
Chemtech-Ford Laboratories
Name:
Sample Site:
Sample ID:
System No:
Sample Type:
Kearns Improvement District
Well #10
07 05753
18011
Drinking Water
Sample Date:
Receipt Date:
Sampler:
Sample Source:
Project:
6/7/2007 2:20 PM
6/8/2007 9:35 AM
LAWSON
Sample
Result
Analysis
Date
Mimimum
Reporting
Limit
Parameter Units Method FlagAnalysis
Time
Analyst
Initials
Group A - Inorganic
ND mg/LCyanide, Total 0.002 ASTM D2036 6/13/2007 16:00 TP
0.4 mg/LFluoride, IC 0.1 EPA 300.0 6/8/2007 15:00 TSM
860 mg/LSolids, Total Dissolved (TDS) 5 SM 2540C 6/13/2007 12:00 JSH
102 mg/LSulfate, IC 1 EPA 300.0 6/8/2007 15:00 TSM
0.15 NTUTurbidity0.02 EPA 180.1 6/8/2007 16:00 JSH
Group B - Metals
ND mg/LAntimony, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
0.0104 mg/LArsenic, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
0.058 mg/LBarium, Total, ICP 0.005 EPA 200.7 6/11/2007 16:16 MJB
ND mg/LBeryllium, Total, ICP 0.001 EPA 200.7 6/11/2007 16:16 MJB
ND mg/LCadmium, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
0.0025 mg/LChromium, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
ND mg/LMercury, Total, ICP/MS 0.0002 EPA 200.8 6/13/2007 14:30 MJB
0.0039 mg/LNickel, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
0.0045 mg/LSelenium, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
68.3 mg/LSodium, Total, ICP 0.5 EPA 200.7 6/11/2007 16:16 MJB
ND mg/LThallium, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
ND = Not detected at the corresponding Minimum Reporting Limit.
1 mg/L = one milligram per liter = 1 part per million.
1 ug/L = one microgram per liter = 1 part per billion.
APH = The test was performed past the EPA specified holding time.
H = A high bias is suspected.
I = The analysis experienced a matrix interference which may have affected the results.
J = The result is positive and estimated. The result falls between the Minimum Reporting Limit and the Method Detection Limit.
L = A low bias is suspected.
O = The analysis was performed by an outside contract laboratory.
R = The value represents a reanalysis.
SPH = The sample was submitted for analysis past the EPA specified holding time.
Abbreviations
Flag Descriptions
Page 7 of 9
6100 South Stratler
Murray, UT 84107
801-262-7299 Office
801-262-7378 Fax
Certificate of Analysis
Lab Group No.:
Lab No.:07 05754
84716
Chemtech-Ford Laboratories
Name:
Sample Site:
Sample ID:
System No:
Sample Type:
Kearns Improvement District
Well #11
07 05754
18011
Drinking Water
Sample Date:
Receipt Date:
Sampler:
Sample Source:
Project:
6/7/2007 2:34 PM
6/8/2007 9:35 AM
LAWSON
Sample
Result
Analysis
Date
Mimimum
Reporting
Limit
Parameter Units Method FlagAnalysis
Time
Analyst
Initials
Group A - Inorganic
ND mg/LCyanide, Total 0.002 ASTM D2036 6/13/2007 16:00 TP
0.3 mg/LFluoride, IC 0.1 EPA 300.0 6/8/2007 15:00 TSM
1070 mg/LSolids, Total Dissolved (TDS) 5 SM 2540C 6/13/2007 12:00 JSH
97 mg/LSulfate, IC 1 EPA 300.0 6/8/2007 15:00 TSM
0.10 NTUTurbidity0.02 EPA 180.1 6/8/2007 16:00 JSH
Group B - Metals
ND mg/LAntimony, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
0.0093 mg/LArsenic, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
0.076 mg/LBarium, Total, ICP 0.005 EPA 200.7 6/11/2007 16:16 MJB
ND mg/LBeryllium, Total, ICP 0.001 EPA 200.7 6/11/2007 16:16 MJB
ND mg/LCadmium, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
0.0027 mg/LChromium, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
ND mg/LMercury, Total, ICP/MS 0.0002 EPA 200.8 6/13/2007 14:30 MJB
0.0054 mg/LNickel, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
0.0062 mg/LSelenium, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
99.3 mg/LSodium, Total, ICP 0.5 EPA 200.7 6/11/2007 16:16 MJB
ND mg/LThallium, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
ND = Not detected at the corresponding Minimum Reporting Limit.
1 mg/L = one milligram per liter = 1 part per million.
1 ug/L = one microgram per liter = 1 part per billion.
APH = The test was performed past the EPA specified holding time.
H = A high bias is suspected.
I = The analysis experienced a matrix interference which may have affected the results.
J = The result is positive and estimated. The result falls between the Minimum Reporting Limit and the Method Detection Limit.
L = A low bias is suspected.
O = The analysis was performed by an outside contract laboratory.
R = The value represents a reanalysis.
SPH = The sample was submitted for analysis past the EPA specified holding time.
Abbreviations
Flag Descriptions
Page 8 of 9
6100 South Stratler
Murray, UT 84107
801-262-7299 Office
801-262-7378 Fax
Certificate of Analysis
Lab Group No.:
Lab No.:07 05755
84716
Chemtech-Ford Laboratories
Name:
Sample Site:
Sample ID:
System No:
Sample Type:
Kearns Improvement District
Well #12
07 05755
18011
Drinking Water
Sample Date:
Receipt Date:
Sampler:
Sample Source:
Project:
6/8/2007 8:00 AM
6/8/2007 9:35 AM
LAWSON
Sample
Result
Analysis
Date
Mimimum
Reporting
Limit
Parameter Units Method FlagAnalysis
Time
Analyst
Initials
Group A - Inorganic
ND mg/LCyanide, Total 0.002 ASTM D2036 6/13/2007 16:00 TP
0.8 mg/LFluoride, IC 0.1 EPA 300.0 6/8/2007 15:00 TSM
889 mg/LSolids, Total Dissolved (TDS) 5 SM 2540C 6/13/2007 12:00 JSH
81 mg/LSulfate, IC 1 EPA 300.0 6/8/2007 15:00 TSM
0.10 NTUTurbidity0.02 EPA 180.1 6/8/2007 16:00 JSH
Group B - Metals
ND mg/LAntimony, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
0.0116 mg/LArsenic, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
0.075 mg/LBarium, Total, ICP 0.005 EPA 200.7 6/11/2007 16:16 MJB
ND mg/LBeryllium, Total, ICP 0.001 EPA 200.7 6/11/2007 16:16 MJB
ND mg/LCadmium, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
0.0006 mg/LChromium, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
ND mg/LMercury, Total, ICP/MS 0.0002 EPA 200.8 6/13/2007 14:30 MJB
0.0031 mg/LNickel, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
0.0026 mg/LSelenium, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
130 mg/LSodium, Total, ICP 0.5 EPA 200.7 6/11/2007 16:16 MJB
ND mg/LThallium, Total, ICP/MS 0.0005 EPA 200.8 6/13/2007 14:30 MJB
ND = Not detected at the corresponding Minimum Reporting Limit.
1 mg/L = one milligram per liter = 1 part per million.
1 ug/L = one microgram per liter = 1 part per billion.
APH = The test was performed past the EPA specified holding time.
H = A high bias is suspected.
I = The analysis experienced a matrix interference which may have affected the results.
J = The result is positive and estimated. The result falls between the Minimum Reporting Limit and the Method Detection Limit.
L = A low bias is suspected.
O = The analysis was performed by an outside contract laboratory.
R = The value represents a reanalysis.
SPH = The sample was submitted for analysis past the EPA specified holding time.
Abbreviations
Flag Descriptions
Page 9 of 9
6100 South Stratler
Murray, UT 84107
801-262-7299 Office
801-262-7378 Fax