Loading...
HomeMy WebLinkAboutDERR-2025-000280Spill Bucket Test Facility Information Name:Fast Stop 1125 Certification/Inspection #:56248 Address:5590 S 900 E, Murray, UT, 84117 State ID:4000224 Phone Number:Form Completed By:Larry Vasquez Date:11/04/2024 Spill Bucket Information Tank #Spill Bucket T1 DSL Spill Bucket T2 PUL Spill Bucket T3 RUL Tank Facility ID:T1 DSL T2 PUL T3 RUL Product:Diesel Premium Unleaded Spill Bucket Capacity:5 gal 5 gal 5 gal Manufacture:EBW EBW EBW Construction:DW DW DW Spill Bucket Type?Product Product Product Liquid and debris removed from spill bucket?Yes Yes Yes Visual Inspection (No cracks, loose parts or separation of the bucket from fill pipe) Pass Pass Pass Tank riser cap included in test?Yes Yes Yes Is drain valve included in test?N/A N/A N/A Start Level 15 15 15 End Level 14.9 14.95 15.01 Test Duration (hh:mm)01:00 01:00 01:00 Level Change -0.1000 -0.0500 0.0100 Pass/Fail Criteria (Test Method):Vacuum: maintain at least 12in WC Vacuum: maintain at least 12in WC Vacuum: maintain at least 12in WC Test Result:Pass Pass Pass Comments Operator Certification Contractor Printed Name:Larry Vasquez Contractor Signature: Certification Number: 12/5/24, 3:50 PM Spill Bucket Test about:blank 1/1