Loading...
HomeMy WebLinkAboutDERR-2025-000279If any answers in Questions 3,4,5,6,7,11,13 or 14 are No, the system has failed the test. Overfill Alarm Inspection Facility Information Name:Fast Stop 1125 Certification/Inspection #:56251 Address:5590 S 900 E, Murray, UT, 84117 State ID:4000224 Phone Number:Form Completed By:Larry Vasquez Date:11/04/2024 Overfill Alarm Information This procedure is to determine wheather the high level alarm is operational and will trigger when the tank is no more than 90% full. See PEI/RP1200 Section 7.3 for inspection procedure. This procedure is applicable to tank level monitor stems that touch the bottom of the tank when in place. Tank #T1 DSL T2 PUL T3 RUL Tank Facility ID T1 DSL T2 PUL T3 RUL Product Stored Diesel Premium Unleaded Tank Level Brand Veeder Root Veeder Root Veeder Root Tank Level Model TLS-350 TLS-350 TLS-350 1. Tank Diameter, in 91.000 91.000 91.000 2. Actual Tank Capacity, gal 9842 9842 9842 3.Overfill alarm activates in the test mode at the console? Y Y Y 4.When activated, overfill alarm can be heard or seen while delivering to the tank? Y Y Y 5.After removing the probe, it has been inspected and any damage or missing parts replaced? Y Y Y 6. Float moves freely on stem without binding?Y Y Y 7. Moving product level float up stem triggers alarm?Y Y Y 8.Inch level from bottom of stem when 90% alarm is triggered 82 82 82 9. Calculated tank volume from Question 8 8856 8856 8556 10. Tank % full 89.98 89.98 86.93 11. Is Question 10 less than 90%Y Y Y 12.Fuel float level on the console agrees with the gauge stick reading? Y Y Y 13. Overfill activates at 90% or less of tank capacity?Y Y Y 14.Fuel float level on the console agrees with the gauge stick reading Y Y Y Test Results Pass Pass Pass Comments Operator Certification Contractor Printed Name:Larry Vasquez Contractor Signature: 12/5/24, 3:51 PM Overfill Alarm Inspection about:blank 1/1 UST Overfill Equipment Inspection Facility Information Name:Fast Stop 1125 Certification/Inspection #:56247 Address:5590 S 900 E, Murray, UT, 84117, Murray, UT, 84117 State ID:4000224 Phone Number:Form Completed By:Larry Vasquez Date:11/04/2024 Tank Information 1.Tank #T1 DSL T2 PUL T3 RUL 2.Tank Facility ID T1 DSL T2 PUL T3 RUL 3.Product Diesel Premium Unleaded 4.Nominal Capacity, gallons 9842 9842 9842 5.Actual Capacity, gallons 9816 9816 9816 6.Req. Shutoff %95 95 95 7.Calculated Shutoff Vol., gallons 9325.20 9325.20 9325.20 8.Calculated Shut-off Level, inches 81.5 81.5 81.5 9.Drop Tube Length, inches 120.5 123.5 117 10.Top of Droptube to Shutoff Level, inches 41 44.5 38 11.Tank Dia/depth, inches 91 91 91 12.Riser Length, inches 9 9.5 10 13.Measured Shut-off Level, inches 59 56 63 14.Overfill Prevention Device Brand Franklin fueling systems Franklin fueling systems Franklin fueling systems 15.Overfill Type External Overfill Alarm External Overfill Alarm External Overfill Alarm Automatic Shutoff Device Inspection 16.Drop tube removed from tank?Yes Yes Yes 17.Drop tube and float mechanisms are free of debris?Yes Yes Yes 18.Float moves freely without binding and poppet moves into flow path?Yes Yes Yes 19.Bypass valve in the drop tube is open and free of blockage (if present)?Yes Yes Yes 20.Flapper is adjusted to shut off flow at required shutoff capacity?Yes Yes Yes Ball Float Valve Inspection 21.Tank top fittings are vapor-tight and leak-free?Yes Yes Yes 22.Ball float cage free of debris?Yes Yes Yes 23.Ball is free of holes and cracks and moves freely in cage?Yes Yes Yes 24.Vent hole in pipe is open and near top of tank?Yes Yes Yes 25.Ball float pipe is proper length to restrict flow at required shutoff capacity?Yes Yes Yes 26.Test Result Pass Pass Pass Manufacture's suggested procedures were used. Comments Operator Certification 12/5/24, 3:51 PM UST OverFill about:blank 1/2 Contractor Printed Name:Larry Vasquez Contractor Signature: Certification Number: 12/5/24, 3:51 PM UST OverFill about:blank 2/2