RE:Request for Petroleum Storage Tank Records
UTAH STATE ITS, located at 350 S 900 W, RICHFIELD
Facility Identification No. 2000689
Dear TODD KING:
PST operators are required to ensure that certain tests are conducted for their tank system.
Dates highlighted in "Yellow" - tests are due soon.
Dates highlighted in "Red" - tests are due and you are out of compliance.
Tank ID/Alt
ID
Description LTT
--------------------
LLD
Spill Bucket
--------------------
Overfill
Tank or Flex
--------------------
Pipe CP
ATG
--------------------
Sump
1/1 Diesel-Diesel #2 (U.L.S.)-12000 N/A N/A N/A 3/9/2024
N/A 2/9/2024 N/A N/A
LTT - Line Tightness Test
LLD - Line Leak Detector
Overfill ±Overfill Device
Tank or Flex/Pipe CP - Corrosion Tests
ATG ±Automatic Tank Gauging
Sump - Tank Top Sump and applicable Dispenser Sumps
Please note that UDC tests are not listed, but are required on your facility's next sump test
cycle starting July 1, 2023, if applicable. Also, effective immediately pressure vent valves
must be tested every three years for gasoline tanks.
Please submit a copy of the required tests to the DERR within 30 days of the date due.
If you have any questions please call Sean Warner at 801-536-4100.
195 North 1950 West - Salt Lake City, UT
Mailing Address: - P.O. Box 144840 - Salt Lake City, UT 84114-4840
Telephone (801) 536-4100 - Fax (801) 359-8853 - T.D.D. (801) 536-4414
www.deq.utah.gov
Printed on 100% recycled paper
March 11, 2024
State of Utah
SPENCER J. COX
Governor
DEIDRE HENDERSON
Lieutenant Governor
Department of
Environmental Quality
Kimberly D. Shelley
Executive Director
DIVISION OF ENVIRONMENTAL
RESPONSE AND REMEDIATION
Brent H. Everett
Director
UST OVERFILL EQUIPMENT INSPECTION
AUTOMATIC SHUTOFF DEVICE AND BALL FLOAT VALVE
Facility Name:
Address:
City, State, Zip Code:
Facility I.D. #
Testing Company:
This data sheet is for inspecting automatic shutoff devices and ball float valves. See PEI/RP 1200, Section 7 for inspection procedures.
Owner:
Address:
City, State, Zip Code:
Phone#
Tester Phone#
Product Grade:
Tank Number:
Tank Volume, gallons:
Tank Diameter, inches:
Overfill Prevention Device Brand:
Overfill Type
AUTOMATIC SHUTOFF DEVICE INSPECTION
1. Drop tube removed from tank?
2. Drop tube and float mechanisms
are free of debris?
3. Float moves freely without
binding and poppet moves into
flow path?
4. Bypass valve in the drop
tube is open and free of
blockage (if present)?
5. Flapper is adjusted to shut off
flow at 95% ?*
A "NO" to any item in Lines 1-5 indicates a test failure.
BALL FLOAT VALVE INSPECTION * *
1. Tank top fittings are
vapor-tight and leak free?
2. Ball float cage free of debris?
3. Ball free of holes and cracks
and moves freely in cage?
4. Vent hole in pipe open and
near top of tank?
5. Ball float pipe is proper length
to restrict flow at 90% capacity?***
A "NO" to any item in Lines 1-5 indicates a test failure.
Test Results:
* Use manufacturer's suggested proceedure for determining if automatic shutoff device will shut off flow at 95% capacity.
Tester's Name:
RICHFIELD DTS DATA CENTER
350 SOUTH 900 WEST
RICHFIELD, UTAH
2000689
AES UTAH LICENCE # UT 0121
STATE FUEL NETWORK
PO BOX 841152
SALT LAKE CITY, UTAH 84141-1152
BRETT GURNEY 385-602-4872
801-540-9258
Date: 3-14-2024
DSL
1
12031
95.75
FRANKLIN
AUTOMATIC
YES
YES
YES
YES
Steven B. Martin Testers Signature:
* * If a ball float is found to fail the inspection , another method of overfill must be used.
* * * Use manufacturer's suggested procedure for determining if flow restriction device will restrict flow at 90% capacity.
Comments
PASS
Digitally signed by STEVEN B MARTIN
cn=STEVEN B MARTIN, o=AES, c=US
Date: 2024.03.19 16:36:34 -07'00'
Reason: I am the author of this document
RICHFIELD DATA CENTER
350 SOUTH 900 WEST
RICHFIELD, UTAH
200689
APPLIED ENVIRONMENTAL SERVICES
STATE FUEL NETWORK
PO BOX 141152
SALT LAKE CITY, UTAH 84141-1152
BRETT GURNEY 385-602-4872
801-540-9258 3-14-2024
PIPING SMP
DSL
X
X
X
X
X
X
X
X
TK INTER
DSL
X
X
X
X
X
X
X
X
STEVEN B MARTIN
APPLIED ENVIRONMENTAL SERVICES, L.C. PO BOX 1073 BOUNTIFUL, UTAH 84011
801-540-9258 AESUTAH@AOL.COM
Digitally signed by STEVEN B MARTIN
cn=STEVEN B MARTIN, o=AES, c=US
Date: 2024.03.19 16:34:35 -07'00'
Reason: I am the author of this document
AUTOMATIC TANK GAUGE OPERATION INSPECTION
Facility Name:
Address:
City, State, Zip Code:
Facility I.D. #
Testing Company:
Owner:
Address:
City, State, Zip Code:
Phone #
Testers Phone #
Date:
This procedure is to determine whether the ( ATG) is operating properly. See PEI/RP1200 Section 8.2 for the proper inspection procedure.
This procedure is applicable to tank level monitor stems that touch the botom of the tank when in place.
Tank Number
Product Stored:
ATG Brand and Model
1. Tank Volume, gallons
2. Tank Diameter, inches
3. After removing the ATG from the tank, has it
been inspected and any damaged or missing
parts replaced?
4. Float moves freely on the stem without
5. Fuel float level agrees with the
value programmed into the console?
6. Water float level agrees with the value
programmed into the console?
7. Inch level from bottom of stem when 90%
alarm is triggered.
8. Inch level at which the overfill alarm
activates corresponds with value programmed
in the gauge?
9. Inch level from the bottom when the water
float first triggers an alarm.
10. Inch level at which the float alarm activates
corresponds with value programmed in the
gauge?
If any answers in Lines 3,4,5, or 6 are "NO" the system has failed the test.
TEST RESULTS
Comments:
Testers Name: Steven B. Martin Testers Signature:
RICHFIELD - DTS SERVICE CENTER
350 SOUTH 900 WEST
RICHFIELD, UTAH
2000689
APPLIED ENVIRONMENTAL, L.C.
STATE FUEL NETWORK
PO BOX 141152
SALT LAKE CITY, UTAH 84141-1152
BRETT GURNEY 385-602-4872
801-540-9258
3-14-2024
1
DSL
TLS-350
12031
95.75
YES
YES
YES
YES
81
YES
2.0
YES
PASS
TANK MONITOR BACKUP BATTERY FUNCTIONS PROPERLY, SETUP REPORT PRINTED