Loading...
HomeMy WebLinkAboutDERR-2024-005211APPLIED ENVIRONMENTAL SERVICES, L.C. PO BOX 1073 BOUNTIFUL, UTAH 84011 801-540-9258 T.E.I. SYSTEM 4000 / T.E.I. LT3 / T.E.I. ULLAGE PRECISION TANK & LINE TEST RESULTS SUMMARY INVOICE ADDRESS: TANK LOCATION: WORK ORDER # TECH # 94027 VAN # 8502 TECHNICIAN: SM STATE TECH # STATE FUEL NETWORK PO BOX 141152 SALT LAKE CITY, UTAH 84141-1152 PROVO CITY #1000228 424 EAST 1325 SOUTH PROVO, UTAH 24030 UT 0121 DATE:3-20-2024 TIME START: TIME END: GROUNDWATER DEPTH: TIME SYSTEM FILLED OR TOPPED: TANK TANK CAPACITY 12000 12000 PRODUCT R/UL DSL TANK AST AST FILL VENT VAPOR AST AST PRODUCT LINE PASS PASS LINE LEAK DETECTOR PASS PASS WATER IN TANK PUMP TYPE PRESS PRESS TANK MATERIAL AST AST 1 2 3 4 5 6 PRODUCT LINES TESTED AT 50 PSI FOR 15 MINUTES LINE RATES (GPH) 1 2 3 4 5 6 R/UL -.013 DSL -.017 ADDITIONAL INFORMATION:ABOVEGROUND FUEL TANKS WITH UNDERGROUND PRODUCT LINES MECHANICAL LINE LEAK DETECTORS PASS 3 GPH SIMULATED LEAK TEST THIS SYSTEM AND METHOD MEETS OR EXCEEDS THE CRITERIA IN USEPA 40, CFR PART 280, NFPA 329-87, AND ALL APPLICABLE STATE AND LOCAL CODES. CERTIFIED TECHNICIAN SIGNATURE: DATE:3-20-2024 Digitally signed by STEVEN B MARTIN cn=STEVEN B MARTIN, o=AES, c=US Date: 2024.03.20 13:06:23 -07'00' Reason: I am the author of this document