Loading...
HomeMy WebLinkAboutDERR-2024-005146 WESTECH EQUIPMENT 195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307 801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054 PRODUCT PIPING INTEGRITY TESTING Facility Name: Canyon Sinclair Owner: Don Roberts Address: 215 North Main Street Address: P.O. Box 1780 City, State, Zip: Beaver, Utah 84713 City, State, Zip: Beaver, Utah 84713 Facility I.D.#: 6000009 Phone #: 385-418-2206 Testing Company: Westech Phone #: 801-266-2545 Date: 11/8/23 This procedure is to test the integrity of product piping. Tests were performed with Petro-Tite line tester. Tank Number 4 5 2 Product Stored PUL DSL Red DSL Piping Run Only Only Only Piping Type FRP FRP FRP Test Pressure (PSI) 50 50 50 Test Duration (minutes) 30 30 30 Leak Rate (GPH) 0.000 0.003 0.000 Test Results ☒Pass ☐Fail ☒Pass ☐Fail ☒Pass ☐Fail ☐Pass ☐Fail Comments: Tester’s Name Taber DeHart, UT-0394 Tester’s Signature #1 RUL #2 Red DSL #4 PUL #5 DSL #3 Non-Ethanol WESTECH EQUIPMENT 195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307 801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054 PRODUCT PIPING INTEGRITY TESTING Facility Name: Canyon Sinclair Owner: Don Roberts Address: 215 North Main Street Address: P.O. Box 1780 City, State, Zip: Beaver, Utah 84713 City, State, Zip: Beaver, Utah 84713 Facility I.D.#: 6000009 Phone #: 385-418-2206 Testing Company: Westech Phone #: 801-266-2545 Date: 11/8/23 This procedure is to test the integrity of product piping. Tests were performed with Petro-Tite line tester. Tank Number 1 3 Product Stored RUL Nonethanol Piping Run Only Only Piping Type FRP FRP Test Pressure (PSI) Test Duration (minutes) Leak Rate (GPH) Test Results ☐Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail Comments: Tank1 (RUL) not tested due to damaged functional element. Tank 3 (non-ethanol) not tested due to excess head pressure at test port. Tester’s Name Taber DeHart, UT-0394 Tester’s Signature #1 RUL #2 Red DSL #4 PUL #5 DSL #3 Non-Ethanol WESTECH EQUIPMENT 195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307 801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054 MECHANICAL AND ELECTRONIC LINE LEAK DETECTOR PERFORMANCE TESTS Facility Name: Canyon Sinclair Owner: Don Roberts Address: 215 North Main Street Address: P.O. Box 1780 City, State, Zip: Beaver, Utah 84713 City, State, Zip: Beaver, Utah 84713 Facility I.D.#: 6000009 Phone #: 385-418-2206 Testing Company: Westech Phone #: 801-266-2545 Date: 11/8/23 This data sheet can be used to test the mechanical line leak detector (MLLD) and electronic line leak detector (ELLD) with submersible turbine pump (STP) systems. See PEI/RP 1200 Sections 9.1 and 9.2 for test procedures. Line Number 1 4 5 2 Product Stored RUL PUL DSL Red DSL Leak Detector Manufacturer FE Petro Fe Petro Fe Petro Fe Petro Leak Detector Model MLD MLD MLD MLD Type Of leak Detector ☒MLLD ☐ELLD ☒MLLD ☐ELLD ☒MLLD ☐ELLD ☒MLLD ☐ELLD MLLD (ALL PRESSURE MEASURMENTS ARE MADE IN PSIG) STP full operating pressure 29 31 40 34 Check valve holding pressure 16 24 28 24 Line resiliency (ml) (line bleedback volume as measured from check valve holding pressure to 0 psig) 245 135 130 160 Step through time in seconds (time the MLLD hesitates at metering pressure before going to full operating pressure as measured from 0 sig with no leak induced on the line) 1 2 2 1 Metering pressure (STP pressure when simulated leak rate 3 gph at 10 psig) 9 15 19 15 Opening time in seconds (the time the MLLD opens to allow full pressure after simulated leak is stopped) 4 1 1 1 Does the STP pressure remain at or below the metering pressure for at least 60 seconds when the simulated leak is induced? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No Does the leak detector reset (trip) when the line pressure is bled off to zero psig? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No Does STP properly clycle on/off under normal fuel system operating conditions? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No A "No" answer to any of the above questions indicates that the MLLD fails the test. ELLD (ALL PRESSURE MEASURMENTS ARE MADE IN PSIG) STP full operating pressure How many test cycles are observed before alarm/shutdown occurs? Does the simulated leak cause on alarm? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No A "No" answer to the above question indicates that the ELLD fails the test. Does the simulated leak cause an STP shutdown? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No Test Results ☒Pass ☐Fail ☒Pass ☐Fail ☒Pass ☐Fail ☒Pass ☐Fail Comments: Tester’s Name Taber DeHart, UT-0394 Tester’s Signature WESTECH EQUIPMENT 195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307 801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054 MECHANICAL AND ELECTRONIC LINE LEAK DETECTOR PERFORMANCE TESTS Facility Name: Canyon Sinclair Owner: Don Roberts Address: 215 North Main Street Address: P.O. Box 1780 City, State, Zip: Beaver, Utah 84713 City, State, Zip: Beaver, Utah 84713 Facility I.D.#: 6000009 Phone #: 385-418-2206 Testing Company: Westech Phone #: 801-266-2545 Date: 11/8/23 This data sheet can be used to test the mechanical line leak detector (MLLD) and electronic line leak detector (ELLD) with submersible turbine pump (STP) systems. See PEI/RP 1200 Sections 9.1 and 9.2 for test procedures. Line Number 3 Product Stored Nonethanol Leak Detector Manufacturer FE Petro Leak Detector Model MLD Type Of leak Detector ☐MLLD ☐ELLD ☐MLLD ☐ELLD ☐MLLD ☐ELLD ☐MLLD ☐ELLD MLLD (ALL PRESSURE MEASURMENTS ARE MADE IN PSIG) STP full operating pressure Check valve holding pressure Line resiliency (ml) (line bleedback volume as measured from check valve holding pressure to 0 psig) Step through time in seconds (time the MLLD hesitates at metering pressure before going to full operating pressure as measured from 0 sig with no leak induced on the line) Metering pressure (STP pressure when simulated leak rate 3 gph at 10 psig) Opening time in seconds (the time the MLLD opens to allow full pressure after simulated leak is stopped) Does the STP pressure remain at or below the metering pressure for at least 60 seconds when the simulated leak is induced? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No Does the leak detector reset (trip) when the line pressure is bled off to zero psig? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No Does STP properly clycle on/off under normal fuel system operating conditions? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No A "No" answer to any of the above questions indicates that the MLLD fails the test. ELLD (ALL PRESSURE MEASURMENTS ARE MADE IN PSIG) STP full operating pressure How many test cycles are observed before alarm/shutdown occurs? Does the simulated leak cause on alarm? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No A "No" answer to the above question indicates that the ELLD fails the test. Does the simulated leak cause an STP shutdown? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No Test Results ☐Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail Comments: Line 3, non-ethanol not tested due to excess head pressure. Tester’s Name Taber DeHart, UT-0394 Tester’s Signature WESTECH EQUIPMENT 195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307 801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054 AUTOMATIC TANK GAUGE OPERATION INSPECTION Facility Name: Canyon Sinclair Owner: Don Roberts Address: 215 North Main Street Address: P.O. Box 1780 City, State, Zip: Beaver, Utah 84713 City, State, Zip: Beaver, Utah 84713 Facility I.D.#: 6000009 Phone #: 385-418-2206 Testing Company: Westech Phone #: 801-266-2545 Date: 11/8/23 This procedure is to determine whether the automatic tank gauge (ATG) is operating properly. See PEI/RP1200 Section 8.2 for the inspection procedure. This procedure is applicable to tank monitor stems that touch the bottom of the tank when in place. Tank Number 1 2 3 4 Product Stored RUL Red DSL Nonethanol PUL ATG Brand and Model TLS 350 TLS 350 TLS 350 TLS 350 1. Tank Volume, gallons 10,000 10,000 6,000 6,000 2. Tank Diameter, inches 96 96 96 96 3. After removing the ATG from the tank, it has been inspected and any damaged or missing parts replaced? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No 4. Float moves freely on the stem without binding? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No 5. Fuel float level agree with the value programmed into the console? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No 6. Water float level agree with the value programmed into the console? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No 7. Inch level from the bottom of the stem when 90% alarm is triggered? 80 7/8 80 7/8 80 7/8 8. Inch level at which the overfill alarm activates corresponds with the value programmed in the gauge? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No 9. Inch level from the bottom when the water float first triggers an alarm? 1 1 1 10. Inch level at which the water float alarm activates corresponds with the value programmed in the gauge? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No If any answers in Lines 3, 4, 5, or 6 are "No" the system has failed the test. Test Results ☒Pass ☐Fail ☒Pass ☐Fail ☒Pass ☐Fail ☐Pass ☐Fail Comments: Battery OK Tank 4 (PUL) not tested due to inability to remove probe. Tester’s Name Taber DeHart, UT-0394 Tester’s Signature WESTECH EQUIPMENT 195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307 801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054 AUTOMATIC TANK GAUGE OPERATION INSPECTION Facility Name: Canyon Sinclair Owner: Don Roberts Address: 215 North Main Street Address: P.O. Box 1780 City, State, Zip: Beaver, Utah 84713 City, State, Zip: Beaver, Utah 84713 Facility I.D.#: 6000009 Phone #: 385-418-2206 Testing Company: Westech Phone #: 801-266-2545 Date: 11/8/23 This procedure is to determine whether the automatic tank gauge (ATG) is operating properly. See PEI/RP1200 Section 8.2 for the inspection procedure. This procedure is applicable to tank monitor stems tha touch the bottom of the tank when in place. Tank Number 5 Product Stored DSL ATG Brand and Model TLS 350 1. Tank Volume, gallons 6,000 2. Tank Diameter, inches 96 3. After removing the ATG from the tank, it has been inspected and any damaged or missing parts replaced? ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No 4. Float moves freely on the stem without binding? ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No 5. Fuel float level agree with the value programmed into the console? ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No 6. Water float level agree with the value programmed into the console? ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No 7. Inch level from the bottom of the stem when 90% alarm is triggered? 80 7/8 8. Inch level at which the overfill alarm activates corresponds with the value programmed in the gauge? ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No 9. Inch level from the bottom when the water float first triggers an alarm? 1 10. Inch level at which the water float alarm activates corresponds with the value programmed in the gauge? ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No If any answers in Lines 3, 4, 5, or 6 are "No" the system has failed the test. Test Results ☒Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail Comments: Battery OK Tester’s Name Taber DeHart, UT-0394 Tester’s Signature