HomeMy WebLinkAboutDERR-2024-005104 WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
SPILL BUCKET INTEGRITY TESTING HYDROSTATIC TEST METHOD
SINGLE- AND DOUBLE-WALLED VACUUM TEST METHOD
Facility Name: Smith’s #94 Owner: Smith’s Food and Drug Centers, Inc.
Address: 479 South 600 East Address: P.O. Box 305103
City, State, Zip: Salt Lake City, Utah 84102 City, State, Zip: Nashville, Tennessee 37230
Facility I.D.#: 4002468 Phone #: 801-977-2012
Testing Company: Westech Phone #: 801-266-2545 Date: 2/7/24
This procedure is to test the leak integrity of single- and double-walled spill buckets. See PEI/RP1200 Section 6.2 for hydrostatic test
method, Section 6.3 for single-walled vacuum test method and Section 6.4 for double-walled vacuum test method.
Tank Number 1 1
Product Stored RUL RUL
Spill Bucket
Capacity 5-Gallon 5-Gallon
Manufacturer OPW OPW
Construction ☒Double-walled
☐Single-walled
☒Double-walled
☐Single-walled
☐Double-walled
☐Single-walled
☐Double-walled
☐Single-walled
Test Type
☒Hydrostatic
☐Vacuum
☐Double-walled
☐Single-walled
☒Hydrostatic
☐Vacuum
☐Double-walled
☐Single-walled
☐Hydrostatic
☐Vacuum
☐Double-walled
☐Single-walled
☐Hydrostatic
☐Vacuum
☐Double-walled
☐Single-walled
Spill Bucket Type ☒Product
☐Vapor
☐Product
☒Vapor
☐Product
☐Vapor
☐Product
☐Vapor
Liquid and debris remove from spill
bucket?* ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No
Visual Inspection (no cracks, loose
parts or separation of the bucket from
the fill pipe.)
☒Yes ☐No ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No
Tank Riser cap included in test? ☒Yes ☐No
☐NA
☒Yes ☐No
☐NA
☐Yes ☐No
☐NA
☐Yes ☐No
☐NA
Drain valve included in test? ☐Yes ☐No
☒NA
☐Yes ☐No
☒NA
☐Yes ☐No
☐NA
☐Yes ☐No
☐NA
Starting Level 12” 12 1/16”
Test Start Time 1:56 1:56
Ending Level 12” 12 1/16”
Test End Time 2:56 2:56
Test Period 1 Hour 1 Hour
Level Change 0” 0”
Pass/fail criteria: Must pass visual inspection. Hydrostatic: Water level drop of less than 1/8 inch; Vacuum single-walled only: Maintain at least 26 inches water
column; Vacuum double-walled: maintain at least 12 inches water column.
Test Results ☒Pass ☐Fail ☒Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail
Comments: Buckets tested were newly replaced.
*All liquids and debris must be disposed of properly
Tester’s Name Sean Jardine, UT-0397 Tester’s Signature
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
UST OVERFILL EQUIPMENT INSPECTION
AUTOMATIC SHUTOFF DEVICE AND BALL FLOAT VALVE
Facility Name: Smith’s #94 Owner: Smith’s Food and Drug Centers, Inc.
Address: 479 South 600 East Address: P.O. Box 305103
City, State, Zip: Salt Lake City, Utah 84102 City, State, Zip: Nashville, Tennessee 37230
Facility I.D.#: 4002468 Phone #: 801-977-2012
Testing Company: Westech Phone #: 801-266-2545 Date: 2/7/24
This data sheet is for inspecting automatic shutoff devices and ball float valve. See PEI/RP1200 Section 7 for inspection procedures.
Product Grade RUL
Tank Number 1
Tank Volume, gallons 19,782
Tank Diameter, inches 118 3/8
Overfill Prevention Device Brand OPW
Type ☒ Automatic
Shutoff Device☐
Ball Float
Valve
☐ Automatic
Shutoff Device
☐ Ball Float
Valve
☐ Automatic
Shutoff Device
☐ Ball Float
Valve
☐ Automatic
Shutoff Device
☐ Ball Float
Valve
AUTOMATIC SHUTOFF DEVICE INSPECTION
1. Drop tube removed from tank? ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
2. Drop tube and float mechanisms free of debris? ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
3. Float moves freely without binding and poppet moves
into flow path? ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
4. Bypass valve in the drop tube open and free of
blockage (if present)?
☒Yes ☐No
☐Not Present
☐Yes ☐No
☐Not Present
☐Yes ☐No
☐Not Present
☐Yes ☐No
☐Not Present
5. Flapper adjusted to shut off flow at 95% capacity? * ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
A "No" to any item in Lines 1-5 indicates a test failure.
BALL FLOAT VALVE INSPECTION**
1. Tank top fitting vapor-tight and leak free? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
2. Ball float cage free of debris? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
3. Ball free of holes and cracks and moves freely in cage? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
4. Vent hole in pipe open and near top of tank? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
5. Ball float pipe proper length to restrict flow to 90%
capacity? *** ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
A "No" to any item in Lines 1-5 indicates a test failure.
Test Results ☒Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail
Comments: Automatic shutoff device tested was newly replaced.
*Use manufacturer’s suggested procedure for determining if automatic shutoff device will shut off flow at 95% capacity.
**If a ball float valve is found to fail the inspection, another method of overfill must be used.
***Use manufacturer’s suggested procedure for determining if flow restriction device will restrict flow at 90% capacity.
Tester’s Name Sean Jardine, UT-0397 Tester’s Signature
Overfill Prevention Equipment Inspection
OPW 61 and 71 Series Overfill Prevention Device Inspection (Non Testable)
Customer Name:
Facility ID #:
Address:
Street
Date:
City, State
Tank Designation 1
Part 1 - Proper Height Setting Calculation YES NO PASS FAIL
OPW Installation Manual H15524PA Rev L 1/30/2014)
Maximum Tank Volume (Gallons) Shown on customers provided tank chart Gallons 19,782
Max Shut off requirement for flapper is 95% %95%
Multiply maximum tank volume by 95% (Gallons)95%Gallons 18,793
Find the dip stick number on the tank chart that corresponds with 95%X Inches 106.250''
Measure top of fill riser threads, or face seal adapter A Inches 55.250''
Find the Dip Stick Volume that corresponds with 100% (FROM TANK CHART)Y Inches 118.375''
Upper Tube in tank (Y) -(X) = (Z)Z Inches 12.125''
Subtract 2 inches from upper tube in tank Formula: (Z) - 2" = (C )C Inches 10.125''
Calculated minimum upper tube length Formula: (C ) + (A) = Upper Tube Length Calculated Inches 65.375''
Actual measured upper tube length (without fill adapter)Actual Inches 65.875''
Part 2 - Device Certification Citeria Evaluation
Criteria 1 Does the overfill prevention device meet the 95% requirement?YES
(If Actual is greater than or equal to calculated ( YES)
(If Actual is less than or equal to calculated ( NO)
Criteria 2 Is the actual measured upper tube length 6.5 inches or more than the fill riser?YES
(C must be 6.5" if not then the upper tube length is 6.5 plus measurement A)
(For testable models ending in "T" upper tube length is (C)+ (A) - 1 -1/2". If less than 6.5" than
it is 6.5" +(A) - 1-1/2")
Criteria 3 Does the overfill prevention device function function as required?YES
(Inspect the device for damage, contamination, freedom of
movement, weakening due to wear and corrosion)
Part 3 - Device Certification PASS / FAIL PASS
Technician certifies that the device is operationally compliant.
If the response to Criteria 1, 2, and 3 above are YES.
Date:
OPW 71SO-410C Overfill Drop
Tube Make
and Model
Tank
Chart
Comments:
2/7/2024
Signature of
Technician:
Tank Chart
Provided by Xerxes
Smith's 94
4002468
479 South 600 East
Salt Lake City, Utah 84102
Xerxes
2/7/2024