HomeMy WebLinkAboutDDW-2024-006653
March 19, 2024
Max Covey
Jordanelle Special Service District
P.O. Box 519
Heber City, Utah 84032
Subject:Plan Approval, 6800 Pump Station (PF017);
Jordanelle Special Service District, System #26086, File #13623
Dear Max Covey:The Division of Drinking Water (the Division) received the plans and specifications for the proposed 6800 Pump Station project from your consultant, Jason Bradford, P.E.
with BT Engineering, on February 7, 2024. Written review comments were provided to your consultant on February 16, 2024. The Division received the revised plans and specifications on
February 28. 2024. This project has met the conditions for receiving a plan approval.
Our understanding of the project is the construction of a new pump station called the 6800 Pump Station (identified as PF017 in the Division’s database). The pump station will be equipped
with four (4), 250-horsepower vertical turbine pumps, each with a capacity of 1,000 gallons per minute (gpm). The design includes redundancy with a total design flow of 3,000 gpm. The
pump station will deliver water from the 6800 Tank (ST018) to the Lady Monument Tank (ST010), which will serve a new development with approximately 2,850 equivalent residential connections
for the first phase. The proposed Benlock Pump Station (PF018) will serve as a second feed into the Lady Monument Tank. Jordanelle Special Service District completed a Master Plan in
2022 which included an evaluation of the capacity needs for the Lady Monument Tank Zone and outlined plans for an additional 2-million-gallon tank to support additional connections.
We have completed our review of the plans and specifications, stamped, and signed byJason Bradford, P.E., dated January 31, 2024, and find they basically comply with the applicable portions
of Utah’s Administrative Rules for Public Drinking Water Systems in R309. On this basis, the plans for the 6800 Pump Station (PF017) are hereby approved.
This approval pertains to construction only. An Operating Permit must be obtained from the Director before the 6800 Pump Station (PF017) may be put into service. A checklist outlining
the items required for operating permit issuance is enclosed for your information.Approvals or permits from the local authority or the county may be necessary before beginning construction
of this project. As the project proceeds, notice of any changes in the approved design, as well as any change affecting the quantity or quality of the delivered water, must be submitted
to the Division. We may also conduct interim and final inspections of this project. Please notify us when actual construction begins so that these inspections can be scheduled.
This approval must be renewed if construction has not begun or if substantial equipment has not been ordered within one year of the date of this letter.
If you have any questions regarding this approval, please contact Julie Cobleigh, of this office, at (385) 214-9770, or me at (385) 515-1464.
Sincerely,
Michael Newberry, P.E.
Permitting and Engineering Support Manager
JJC/mrn/mdbEnclosures –Operating Permit Checklistcc:Dwight Hill, Wasatch County Health Department, dhill@wasatch.utah.govJason Bradford, P.E., BT Engineering, jason@b-t-eng.comSteve
Jackson, P.E., Jackson Engineering, steve@jackson-engineering.comMax Covey, Jordanelle Special Service District, mcovey@jssd.usJulie Cobleigh, Division of Drinking Water, jjcobleigh@utah.govRebecca
Yoo, Division of Drinking Water, ryoo@utah.govDanielle Zebelean, Division of Drinking Water, dzebelean@utah.govjcobleigh 26086 13623 PF017 PA
Utah Division of Drinking Water ― Checklist for Issuing Operating PermitsWater System Name:System Number: Project Description:File Number:
Items 1 through 8 below must be submitted to the Division and found to be acceptable prior to operating permit issuance (unless a water line project meets the requirements of R309-500-7
and is not required to obtain an Operating Permit).
Distribution lines (not including in-line booster pump stations) requiring Plan Approval may be placed into service prior to submitting all of the following items and receipt of Operating
Permit if the water system has received items 1 and 4 below.☐1.Certification of Rule Conformance by a professional engineer (P.E.) that all conditions of Plan Approval were accomplished,
and if applicable, changes made during construction were in conformance with rules R309-500 through 550☐2.As-built or record drawings incorporating all changes to approved plans and
specifications (unless no changes were made to the previously approved plans during construction)☐3.Confirmation that as-built or record drawings have been received by the water system☐4.Satisfactory
bacteriological samples as evidence of proper disinfection and flushing in accordance with the appropriate ANSI/AWWA standards:
☐ANSI/AWWA C651-14 AWWA Standard for Disinfecting Water MainsTwo consecutive sample sets at least 16 hours apart, none positive (e.g., every 1,200 feet, end-of-line, each branch)☐ANSI/AWWA
C652-11 AWWA Standard for Disinfection of Water-Storage FacilitiesOne or more samples, none positive☐ANSI/AWWA C653-13 AWWA Standard for Disinfection of Water Treatment PlantsTwo consecutive
samples per unit, none positive, no less than 30 minutes apart☐ANSI/AWWA C654-13 AWWA Standard for Disinfection of WellsTwo consecutive samples, none positive, no less than 30 minutes
apart☐5.Water quality data, where appropriate [For example, include raw and finished water data that demonstrate satisfactory performance of the treatment facility; sample should be
taken from a storage tank for residual volatile organic compounds after tank interior re-coating; etc.]☐6.If applicable, all other documentation that may have been required during the
plan review process☐7.If applicable, confirmation that the water system owner has received the O&M manual for the new facility☐8.If applicable, location data of new storage tank, treatment
facility, or source