HomeMy WebLinkAboutDDW-2024-014842DDW Reports <ddwreports@utah.gov>
Fwd: Webb Well 18051 Sanitary Survey Corrections
1 message
Jennifer Yee <jyee@utah.gov>Tue, Dec 17, 2024 at 8:25 AM
To: DDW Reports <ddwreports@utah.gov>
Please import into the site visit folder title 18051 SS-2024 Updates
Jennifer Yee
Environmental Scientist | Division of Drinking Water
M: (385) 515-1501
drinkingwater.utah.gov
(801) 536-4200
Emails to and from this email address may be considered public records and thus subject to Utah GRAMA
requirements.
---------- Forwarded message ---------
From: Ryan Dearing <rdearing@utah.gov>
Date: Mon, Dec 16, 2024 at 1:42 PM
Subject: Webb Well 18051 Sanitary Survey Corrections
To: Roger Empey <roger@propertymedicsut.com>, Ben Barlow (benjaminbarlow86@gmail.com)
<benjaminbarlow86@gmail.com>
Cc: Chris Bowles <chrisbowles@utah.gov>, Jennifer Yee <jyee@utah.gov>
Roger and Ben, thank you for meeting with us on 12/07/2024 for a site visit of your water system.
As we discussed during our visit, you had concerns and questions about the prior sanitary survey completed on
8/29/2024. As a result of our site visit we can make the following corrections to the results of the sanitary survey:
M003, M004, M005 can all be removed.
M006 and M007 will remain until a log of applicable activities has been established.
S015 - This deficiency can be removed for both WS001 and WS002. The other deficiencies on WS001 and WS002 will
remain as we cannot verify that there is a check valve, meter or pressure gauge on either well.
All of the deficiencies for ST001 can be removed as this tank has now been abandoned.
V035, V009 can be removed, however V007 will remain on ST002 as gaps in the #14 mesh screen can be seen in the
attached photo.
T006 can be removed as the sample tap for finished water in the tap at each home.
As we discussed, I will continue to investigate the history and legitimacy of the requirement to have a certified treatment
operator for your POU arsenic treatment.
12/27/24, 9:26 AM State of Utah Mail - Fwd: Webb Well 18051 Sanitary Survey Corrections
https://mail.google.com/mail/b/AEoRXRTEo9BVkyH_orvWHDvCX0am7TXJ52k6dGwWYeZV961SyVQ_/u/0/?ik=2401283fbe&view=pt&search=all&per…1/2
Also as a result of the inspection, we will need to add a deficiency on WS001 SOUTH WELL #1 due to the fact the hatch
lid needs a gasket. SIG - 50pts - SO - S013 - WELL LACKS THE REQUIRED WELL SEAL: R309-515-6(6)(i) -
R309-515-6(6)(i) and R309-515-6(12)(b,c,d)require a sanitary seal be installed and maintained at the
wellhead and discharge piping.
See attached photo.
Thank you again for taking the time to meet with us and for your patience as we resolve these issues.
--
Ryan Dearing | Field Services Manager
801.419.6785 (cell)
195 North 1950 West, Salt Lake City, UT 84116
Emails to and from this email address may be considered public records and thus subject to Utah GRAMA requirements.
2 attachments
Webb Well.jpg
168K
BB8E66AE-4303-4C5E-A1F7-2EE21D7C32AD (1).JPG
10156K
12/27/24, 9:26 AM State of Utah Mail - Fwd: Webb Well 18051 Sanitary Survey Corrections
https://mail.google.com/mail/b/AEoRXRTEo9BVkyH_orvWHDvCX0am7TXJ52k6dGwWYeZV961SyVQ_/u/0/?ik=2401283fbe&view=pt&search=all&per…2/2