Loading...
HomeMy WebLinkAboutDERR-2024-005026APPENDIX C-4 CONTAINMENT SUMP INTEGRITY TESTING HYDROSTATIC TESTING METHOD Owner: Maverik Inc Address: 185 S State St Ste 800 City, State, Zip Code: SLC UT 84111 Phone#: 801-936-5557 Facility Name Address: 2875 S 3200 W City, State, Zip Code: WVC UT 84119 Facility I.D. #:4001122 Testing Company: Precision Testing Technologies Inc. Phone#: 801-886-9224 Date: 12/06/2023 This procedure is to test the leak integrity of containment sumps. See PEI/RP1200, Section 6.5 for the test method. Containment Sump ID DSL Containment Sump FRP Material Liquid and debris @Yes □No □Yes □No □Yes □No □Yes □ No □Yes □No □Yes □ Noremoved from sump?* Visual Inspection (No cracks, loose parts 121 Pass □ Fail □ Pass □ Fail □ Pass □ Fail □ Pass □ Fail □ Pass □ Fail □Pass □ Failor separation of the containment sump.) Containment Sump 44 Depth Height From Bottom to Top of Highest 25 Penetration Starting Water Level 11 Test Start Time 0 Ending Water Level 11 Test End Time 1 hr Test Period (Minimum 1 hr test time: 1 hour) Water Level Change 0 Pass/fail criteria: Must pass visual inspection. Water level drop of less than 1/8 inch. Test Results 121 Pass □ Fail □ Pass □ Fail □ Pass □Fail □Pass □Fail □ Pass □Fail □Pass □ Fail Comments: *All liquids and debris must be disposed of properly. Tester's Name Danny Jones UT 379 Tester's Signature ___________ _ Maverik #228