Loading...
HomeMy WebLinkAboutDERR-2024-013058UST Operator Inspection - Utah YEAR ________ Facility Name Facility ID Address Primary Class B Operator NAME(S) AND INITIALS OF PERSON(S) CONDUCTING MONTHLY INSPECTIONS: Please respond to ALL of the following questions with a Y (Yes), N (No), or NA (Not Applicable) answer. Months of the Current Year J F M A M J J A S O N D Monthly Inspection – Release Detection 1 Release detection equipment is operating with no alarms or other unusual operating conditions. 2 Records of release detection (tanks and piping) are reviewed and current. Monthly Inspection – Spill Prevention Equipment 3 Equipment is undamaged, intact and free from defects. 4 Equipment is free from debris, water, or product. 5 Fill Pipe is unobstructed. 6 Fill cap is un-broken and is securely on the fill pipe. 7 Double walled spill prevention equipment - Interstitial area is free from leaks. Initials of person performing Inspection. Annual Inspection – Containment Sumps Date of annual Inspection 8 Secondary Containment Sumps (STP, Dispenser and Transition) Visual Inspection of sump indicates no damage and it is free from debris, water and fuel. The penetration fittings for conduits and piping entering the STP Sumps are intact. 9 Double Walled Sumps Interstitial area is free from leaks. 10 Hand-held release detection equipment Hand-held release detection equipment (bailer, gauge stick, etc.) is serviceable and operable. I certify under penalty of law that I am the Class B Operator referenced above and that I am familiar with information on this form and that it is true, accurate and was completed in accordance with R311-203-7. Signature of the Primary Class B Operator (Sign this document after the last inspection of the Current Year) Date B Operator # Turn over for record of Interstitial Monitoring visual inspections and Impressed Current rectifier checks. Comments/Follow up: 2024 Fast Stop 1118 1200647 1584 W 2700 N, Pleasant View , UT 84404 y y y y y y y y y y y y y y UST Operator Inspection - Utah – Page 2 of 2 If you perform Interstitial Monitoring on your tanks and/or piping and use a visual check rather than sump or interstitial sensors for your monthly leak detection, complete the table to document the monthly visual checks. Months of the Current Year J F M A M J J A S O N D 1 Visual check of the interstitial space of the double-walled tank indicated no release or unusual operating conditions. 2 Visual check of piping (STP, dispenser and transition) containment sumps indicates normal function and no indication of water or leaked product. Impressed Current 60 Day Rectifier Check Months of the Current Year J F M A M J J A S O N D Show the date the Impressed Current system was inspected to ensure the equipment is running properly Amperage reading from impressed current rectifier Voltage reading from impressed current rectifier INSTRUCTIONS 1. The monthly UST system inspections must be conducted by or under the direction of the Primary Class B UST Operator. 2. The Primary Class B UST Operator must alert the UST Owner or Operator of any condition discovered during the monthly visual inspection that may require follow-up actions. 3. The UST Owner or Operator must maintain a copy of the monthly inspection reports for the most recent 12 months. The records shall be maintained on-site or off-site at a readily available location. Ver. 4/14/2016 y y y y n a Tank # / Tank Facility ID / ProductLeak Detection: UST Monthly Compliance Inspection Facility Information Name:Fast Stop 1118 Certification/Inspection #:56600 Address:1584 W 2700 N State ID:1200647 Phone Number:Form Completed By:Larry Vasquez Date:11/18/2024 T4 DSL T4 DSL Diesel T3 ETH FREE T3 ETH FREE Ethanol Free Unleaded T2 PUL T2 PUL Premium T1 RUL T1 RUL Unleaded Tanks: 1 Is release detection equip. operating w/o alarms or unusual conditions? Y N NA Y N NA Y N NA Y N NA 2 Is tank free of water? Y N NA Y N NA Y N NA Y N NA 3 Primary Tank Release Detection Method Inspected:Interstitial Monitoring Interstitial Monitoring Interstitial Monitoring Interstitial Monitoring 4 Date of last passing result:11/18/2024 11/18/2024 11/18/2024 11/18/2024 5 Are Inventories reconciled daily and are the variances within the guideline set by the facility owner? Y N NA Y N NA Y N NA Y N NA Lines: 6 Are line leak detectors present? Y N NA Y N NA Y N NA Y N NA 7 LD s operating properly (no slow flow)? Y N NA Y N NA Y N NA Y N NA 8 Primary Line Release Detection Method Inspected Sump Sensor Monitoring Sump Sensor Monitoring Sump Sensor Monitoring Sump Sensor Monitoring 9 Date of last passing result:11/18/2024 11/18/2024 11/18/2024 11/18/2024 Fill/Overfill: 10 Fill caps, adapters, gaskets in good condition? Y N NA Y N NA Y N NA Y N NA 11 Fills properly marked? Y N NA Y N NA Y N NA Y N NA 12 Spill bucket free of liquid/debris? Y N NA Y N NA Y N NA Y N NA 13 Spill bucket free of damage/drain work correctly? Y N NA Y N NA Y N NA Y N NA 14 Does the spill bucket drain assembly work correctly? Y N NA Y N NA Y N NA Y N NA 15 For double wall spill bucket, is the interstitial monitoring equipment functioning, in good condition and not in alarm? Y N NA Y N NA Y N NA Y N NA 16 Fill cap in place and sealed tightily? Y N NA Y N NA Y N NA Y N NA 17 Overfill drop tube free of obstructions? Y N NA Y N NA Y N NA Y N NA Vapor: 18 Vapor cap in place and sealed tightly? Y N NA Y N NA Y N NA Y N NA 19 Vapor recovery adapter intact? Y N NA Y N NA Y N NA Y N NA 20 Vapor recovery lids painted orange? Y N NA Y N NA Y N NA Y N NA 21 Is Vapor Bucket free of damage and free of liquid/debris? Y N NA Y N NA Y N NA Y N NA STP Secondary Containment: 22 Sump containment free of water/fuel/debris? Y N NA Y N NA Y N NA Y N NA 23 STP and piping free of leaks and seeps? Y N NA Y N NA Y N NA Y N NA 24 Sump containment free of damage? Y N NA Y N NA Y N NA Y N NA 25 For DW containment with Brine, are levels correct? Y N NA Y N NA Y N NA Y N NA 12/4/24, 10:43 AM Monthly Inspection UST CO about:blank 1/2 6 26 Sensors located @ lowest point in containment? Y N NA Y N NA Y N NA Y N NA Dispensing Equipment:Qty:Facility Notes: 27 UDC free of water/fuel/debris? Y N NA 28 All meters/ piping free from leaks and seeps? Y N NA 29 UDC in good condition & free from damage? Y N NA 30 For DW containment with Brine, are levels correct? Y N NA 31 Sensors located lowest point in UDC? Y N NA 32 Shear valves properly set and secured? Y N NA 33 Nozzles, swivels, hoses and connectors free of leaks? Y N NA 34 All product and whip hoses in good condition? Y N NA Cathodic Protection: 35 Rectifier is on? Y N NA Contractor Signature:Date:11/18/2024 Printed Name:Larry Vasquez Certification Number: 12/4/24, 10:43 AM Monthly Inspection UST CO about:blank 2/2 Automatic Tank Gauge Inspection ATG 1 ATG 1743 Facility Information Name:Fast Stop 1118 Certification/Inspection #:56602 Address:1584 W 2700 N, Pleasant View , UT, 84404 State ID:1200647 Phone Number:Form Completed By:Larry Vasquez Date:11/18/2024 ATG Console Inspection Tank Level Monitor Brand :Veeder Root 1.Status upon Arrival:All Functions Normal 2.Status upon Departure:All Functions Normal 3.Is the display in good condition and functioning?: Yes 4.Is the keypad in good condition?: Yes Tank Level Monitor Model :TLS-450 Plus 5.Are all indicator lights functional?: Yes 6.Is printer functional?:Yes 7.Back-up battery tested? (if applicable)?: Yes 8.Back-up battery voltage (if applicable): Tank Information Probe and Programing Inspection: 9.Tank # T1 RUL T2 PUL T4 DSL T3 ETH FREE 10.Tank Facility ID T1 RUL T2 PUL T4 DSL T3 ETH FREE 11.Tank # per ATG T1 RUL T2 PUL T4 DSL T3 ETH FREE 12.Product:Unleaded Premium Diesel Ethanol Free Unleaded 13.Tank Volume, gallons 14881 4706 4706 4190 14.Tank Dia/depth, inches 90.5 90.5 90.5 90.5 In-Tank Setup Parameters: 15.Thermal coefficient .000700 .000700 .00450 .000700 16.ATG Programmed Diameter 90.5 90.5 90.5 90.5 17.Number of points on profile 4 4 4 4 18.Full volume on profile 14881 4706 4706 4190 12/4/24, 10:44 AM ATG about:blank 1/2 Pass/Fail Criteria: if any of questions 19, 20 ,21 & 22 are No, then the system has failed the test. Comment Operator Certification Contractor Signature:Printed Name:Larry Vasquez 19.After removing the probe from the tank, it has been inspected and any damaged or missing parts replaced? Yes Yes Yes Yes 20.Do floats move freely along the stem without binding?Yes Yes Yes Yes 21.Does product level match console value?Yes Yes Yes Yes 22.Does water level match console value?Yes Yes Yes Yes 23.Water warning (inches)(1")1.5 1.5 1.5 1.5 24.High water limit (inches)(1.5")2.5 2.5 2.5 2.5 25.Does console water alarm trigger at programmed level?Yes Yes Yes Yes 26.Programmed Overfill Limit (90%)90 90 90 90 27.Does console overfill alarm trigger at programmed level?Yes Yes Yes Yes 28.Programmed High Product Limit (95%)95 95 95 95 29.Does console high product alarm trigger at programmed level?Yes Yes Yes Yes 30.Low Product (15% of tank volume or 15" whichever is greater)15 15 15 15 31.Tank test program enabled?Yes Yes Yes Yes 32.Tank Test Method?Interstitial Interstitial Interstitial Interstitial 33.Tank Test Rate 0.2 0.2 0.2 0.2 34.Test duration (hrs)CONT CONT CONT CONT 35.12 months of tank test history present?Yes Yes Yes Yes Lines: 36.Electronic Line Leak Type PLLD PLLD PLLD PLLD 37.Line # and label in ATG (Q1, Unleaded)Q1 Q2 Q4 Q3 38.Line Test Rate 0.2 GPH 0.2 GPH 0.2 GPH 0.2 GPH 39.12 months of line test history present?Yes Yes Yes Yes 40.Test Result Pass Pass Pass Pass 12/4/24, 10:44 AM ATG about:blank 2/2 Automatic Tank Gauge Sensor ATG 1 Facility Information Name:Fast Stop 1118 Certification/Inspection #:56604 Address:1584 W 2700 N, Pleasant View , UT, 84404 State ID:1200647 Phone Number:Form Completed By:Larry Vasquez Date:11/18/2024 Sensor: # Brand:Veeder Root Veeder Root Veeder Root Veeder Root Veeder Root Model:Piping Sump Sensor Non- Discriminating Interstitial Sensor Piping Sump Sensor Piping Sump Sensor Piping Sump Sensor Type:Non- discriminating Non- discriminating Non- discriminating Non- discriminating Non- discriminating Location:STP INT STP STP STP Test Liquid, Fuel(F) and/or Water(W):Both Both Both Both Both Is the ATG console clear of any active or recurring warnings or alarms regarding sensor? If sensor is in alarm and functioning indicate why below: Y Y Y Y Y Is the sensor alarm circuit operational?Y Y Y Y Y Has the sensor been inspected and in good operating condition? Y Y Y Y Y When placed in the test liquid does the sensor trigger an alarm? Y Y Y Y Y Sensor removed for testing?Y Y Y Y Y When an alarm is triggered, is the sensor properly identified on the ATG console? Y Y Y Y Y Sensor returned to proper placement and verified to be functional after testing? Y Y Y Y Y Any "No" answers above indicates the sensor fails the test. Test Result Pass Pass Pass Pass Pass 12/4/24, 10:44 AM ATG Sensor about:blank 1/3 Sensor: # Brand:Veeder Root Veeder Root Veeder Root Veeder Root Veeder Root Model:Non- Discriminating Interstitial Sensor Piping Sump Sensor Piping Sump Sensor Piping Sump Sensor Piping Sump Sensor Type:Non- discriminating Non- discriminating Non- discriminating Non- discriminating Non- discriminating Location:INT UDC UDC UDC UDC Test Liquid, Fuel(F) and/or Water(W):Both Both Both Both Both Is the ATG console clear of any active or recurring warnings or alarms regarding sensor? If sensor is in alarm and functioning indicate why below: Y Y Y Y Y Is the sensor alarm circuit operational?Y Y Y Y Y Has the sensor been inspected and in good operating condition? Y Y Y Y Y When placed in the test liquid does the sensor trigger an alarm? Y Y Y Y Y Sensor removed for testing?Y Y Y Y Y When an alarm is triggered, is the sensor properly identified on the ATG console? Y Y Y Y Y Sensor returned to proper placement and verified to be functional after testing? Y Y Y Y Y Any "No" answers above indicates the sensor fails the test. Test Result Pass Pass Pass Pass Pass Sensor: # Brand:Veeder Root Veeder Root Model:Piping Sump Sensor Piping Sump Sensor Type:Non- discriminating Non- discriminating Location:UDC UDC Test Liquid, Fuel(F) and/or Water(W):Both Both Is the ATG console clear of any active or recurring warnings or alarms regarding sensor? If sensor is in alarm and functioning indicate why below: Y Y Is the sensor alarm circuit operational?Y Y Has the sensor been inspected and in good operating condition?Y Y 12/4/24, 10:44 AM ATG Sensor about:blank 2/3 When placed in the test liquid does the sensor trigger an alarm?Y Y Sensor removed for testing?Y Y When an alarm is triggered, is the sensor properly identified on the ATG console?Y Y Sensor returned to proper placement and verified to be functional after testing?Y Y Any "No" answers above indicates the sensor fails the test. Test Result Pass Pass Comment Operator Certification Contractor Signature:Printed Name:Larry Vasquez 12/4/24, 10:44 AM ATG Sensor about:blank 3/3 Leak Detector Facility Information Name:Fast Stop 1118 Certification/Inspection #:56599 Address:1584 W 2700 N, Pleasant View, UT, 84404 State ID:1200647 Phone Number:Form Completed By:Larry Vasquez Date:11/18/2024 Tank Information Tank #:T1 RUL T2 PUL T3 ETH FREE T4 DSL Capacity:14881 4706 4190 4706 Product:Unleaded Premium Ethanol Free Unleaded Diesel Line #:Q1 RUL T2 PUL Q3 ETH FREE Q4 DSL Line Type:Pressure Pressure Pressure Pressure LD Brand:Veeder Root Veeder Root Veeder Root Veeder Root LD Model:PLLD PLLD PLLD PLLD Serial #:0 0 0 0 Associated Tank:T1 RUL T2 PUL T3 ETH FREE T4 DSL Resiliency (ml):0 0 0 0 Check Valve Holding PSI:0 0 0 0 Opening Time:2 0 0 2 Result:Pass Fail Fail Pass Test Equip. Mfg.:Vaporless, LDT-890 Vaporless, LDT-890 Vaporless, LDT-890 Vaporless, LDT-890 Notes: PUL and ETH Free Failed to Detect that test was going on ran a manual test from ATG and Still No Reaction From Leak Detector and ATG. Tested per manufacturer specifications. Contractor Signature:Printed Name:Larry Vasquez Line Test Facility Information Name:Fast Stop 1118 Certification/Inspection #:56598 Address:1584 W 2700 N State ID:1200647 Phone Number:Form Completed By:Larry Vasquez Date:11/18/2024 Tank Test Information Tank #:T1 RUL T2 PUL T3 ETH FREE T4 DSL Capacity:14881 4706 4190 4706 Product:Unleaded Premium Ethanol Free Unleaded Diesel Line Test Information Line #:Q1 RUL T2 PUL Q3 ETH FREE Q4 DSL LineType:Pressure Pressure Pressure Pressure Line Material:DW FRP DW Flex DW Flex DW Flex Line ID Size (in):2 2 2 2 Line Length (ft):205 205 205 205 Pump Type:FE Petro FE Petro FE Petro FE Petro Associated Tank:T1 RUL T2 PUL T3 ETH FREE T4 DSL Test Equip. Mfg.:Triangle Triangle Triangle Triangle Test Pressure (PSI):50 50 50 50 Initial Cyl. Level:300 250 400 210 Final Cyl. Level:270 230 400 180 Change in Time (mins):15 15 15 15 Change in Vol:-30.0000 -20.0000 0.0000 -30.0000 Change in Temp (F):0 0 0 0 Coeff. Of Thermal Expansion (g/F):0.00070 0.00070 0.00070 0.00045 Line Vol (gal):33.44 33.44 33.44 33.44 Leak Rate (GPH):-0.0317 -0.0211 0.0000 -0.0317 Result:Pass Pass Pass Pass Notes TIGHTNESS TESTING CERTIFICATION CGRS certifies that the systems in the above table have been tested utilizing leak detection methods which meet the prescribed leak rate testing standard of 0.10 gph with a minimum probability of detection of 95% and a 5% probability of a false alarm. CGRS further certifies that the protocol for each test method was strictly adhered to, and that all precision tightness testing performed by CGRS was conducted in accordance with EPA 40 CFR parts 280.43(c) and 280.44(b) and the National Fire Protection Association, Bulletin NFPA 329 criteria. Contractor Printed Name:Larry Vasquez Contractor Signature: Certification Number:TMI-301 12/4/24, 10:45 AM Line Test about:blank 1/1 Spill Bucket Test Facility Information Name:Fast Stop 1118 Certification/Inspection #:56601 Address:1584 W 2700 N, Pleasant View , UT, 84404 State ID:1200647 Phone Number:Form Completed By:Larry Vasquez Date:11/18/2024 Spill Bucket Information Tank #Spill Bucket T1 RUL Spill Bucket T2 PUL Spill Bucket T3 ETH FREE Spill Bucket T4 DSL Vapor Bucket T1 RUL vapor Tank Facility ID:T1 RUL T2 PUL T3 ETH FREE T4 DSL T1 RUL Product:Unleaded Premium Ethanol Free Unleaded Diesel Unleaded Spill Bucket Capacity:5 gal 5 gal 5 gal 5 gal 5 gal Manufacture:OPW OPW OPW OPW OPW Construction:DW DW DW DW DW Spill Bucket Type?Product Product Product Product Vapor Liquid and debris removed from spill bucket?Yes Yes Yes Yes Yes Visual Inspection (No cracks, loose parts or separation of the bucket from fill pipe) Pass Pass Pass Pass Pass Tank riser cap included in test?Yes Yes Yes Yes Yes Is drain valve included in test?Yes Yes Yes Start Level 15 15 15 15 15 End Level 14.90 14.89 14.90 14.98 14.94 Test Duration (hh:mm)01:00 01:00 01:00 01:00 01:00 Level Change -0.1000 -0.1100 -0.1000 -0.0200 -0.0600 Pass/Fail Criteria (Test Method):Vacuum: maintain at least 12in WC Vacuum: maintain at least 12in WC Vacuum: maintain at least 26in WC Vacuum: maintain at least 12in WC Vacuum: maintain at least 12in WC Test Result:Pass Pass Pass Pass Pass Tank #Vapor Bucket T2 PUL Vapor Bucket T3 ETH FREE Tank Facility ID:T2 PUL T3 ETH FREE Product:Premium Ethanol Free Unleaded Spill Bucket Capacity:5 gal 5 gal Manufacture:OPW OPW Construction:DW DW Spill Bucket Type?Vapor Vapor Liquid and debris removed from spill bucket?Yes Yes Visual Inspection (No cracks, loose parts or separation of the bucket from fill pipe) Pass Pass 12/4/24, 10:46 AM Spill Bucket Test about:blank 1/2 Tank riser cap included in test?Yes Yes Is drain valve included in test?Yes Yes Start Level 15 15 End Level 14.88 14.9 Test Duration (hh:mm)01:00 01:00 Level Change -0.1200 -0.1000 Pass/Fail Criteria (Test Method):Vacuum: maintain at least 26in WC Vacuum: maintain at least 12in WC Test Result:Pass Pass Comments Operator Certification Contractor Printed Name:Larry Vasquez Contractor Signature: Certification Number: 12/4/24, 10:46 AM Spill Bucket Test about:blank 2/2 If any answers in Questions 3,4,5,6,7,11,13 or 14 are No, the system has failed the test. Overfill Alarm Inspection Facility Information Name:Fast Stop 1118 Certification/Inspection #:56605 Address:1584 W 2700 N, Pleasant View, UT, 84404 State ID:1200647 Phone Number:Form Completed By:Larry Vasquez Date:11/19/2024 Overfill Alarm Information This procedure is to determine wheather the high level alarm is operational and will trigger when the tank is no more than 90% full. See PEI/RP1200 Section 7.3 for inspection procedure. This procedure is applicable to tank level monitor stems that touch the bottom of the tank when in place. Tank #T1 RUL T2 PUL T3 ETH FREE T4 DSL Tank Facility ID T1 RUL T2 PUL T3 ETH FREE T4 DSL Product Stored Unleaded Premium Ethanol Free Unleaded Diesel Tank Level Brand Veeder Root Veeder Root Veeder Root Veeder Root Tank Level Model TLS-450 Plus TLS-450 Plus TLS-450 Plus TLS-450 Plus 1. Tank Diameter, in 90.500 90.500 90.500 90.500 2. Actual Tank Capacity, gal 14881 4706 4190 4706 3.Overfill alarm activates in the test mode at the console? Y Y Y Y 4.When activated, overfill alarm can be heard or seen while delivering to the tank? Y Y Y Y 5.After removing the probe, it has been inspected and any damage or missing parts replaced? Y Y Y Y 6. Float moves freely on stem without binding?Y Y Y Y 7. Moving product level float up stem triggers alarm?Y Y Y Y 8.Inch level from bottom of stem when 90% alarm is triggered 81.45 81.45 81.45 81.45 9. Calculated tank volume from Question 8 13392 4003 3691 4006 10. Tank % full 89.99 85.06 88.09 85.13 11. Is Question 10 less than 90%Y Y Y Y 12.Fuel float level on the console agrees with the gauge stick reading? Y Y Y Y 13. Overfill activates at 90% or less of tank capacity?Y Y Y Y 14.Fuel float level on the console agrees with the gauge stick reading Y Y Y Y Test Results Pass Pass Pass Pass Comments 12/4/24, 10:47 AM Overfill Alarm Inspection about:blank 1/2 Operator Certification Contractor Printed Name:Larry Vasquez Contractor Signature: 12/4/24, 10:47 AM Overfill Alarm Inspection about:blank 2/2 UST Overfill Equipment Inspection Facility Information Name:Fast Stop 1118 Certification/Inspection #:56603 Address:1584 W 2700 N, Pleasant View , UT, 84404, Pleasant View, UT, 84404 State ID:1200647 Phone Number:Form Completed By:Larry Vasquez Date:11/18/2024 Tank Information 1.Tank #T1 RUL T2 PUL T3 ETH FREE T4 DSL 2.Tank Facility ID T1 RUL T2 PUL T3 ETH FREE T4 DSL 3.Product Unleaded Premium Ethanol Free Unleaded Diesel 4.Nominal Capacity, gallons 14881 4706 4190 4706 5.Actual Capacity, gallons 14881 4706 4190 4706 6.Req. Shutoff %95 95 95 95 7.Calculated Shutoff Vol., gallons 14136.95 4470.70 3980.50 4470.70 8.Calculated Shut-off Level, inches 81.5 87.87 80.62 87.87 9.Drop Tube Length, inches 131.5 128.5 131.5 134 10.Top of Droptube to Shutoff Level, inches 51.5 49.5 50.5 53 11.Tank Dia/depth, inches 90.5 90.5 90.5 90.5 12.Riser Length, inches 38 36 39.75 36.75 13.Measured Shut-off Level, inches 77 77 79.75 74.25 14.Overfill Prevention Device Brand Franklin fueling systems Franklin fueling systems Franklin fueling systems Franklin fueling systems 15.Overfill Type Drop Tube Flapper valve Drop Tube Flapper valve Drop Tube Flapper valve Drop Tube Flapper valve Automatic Shutoff Device Inspection 16.Drop tube removed from tank?Yes Yes Yes Yes 17.Drop tube and float mechanisms are free of debris?Yes Yes Yes Yes 18.Float moves freely without binding and poppet moves into flow path? Yes Yes Yes Yes 19.Bypass valve in the drop tube is open and free of blockage (if present)? Yes Yes Yes Yes 20.Flapper is adjusted to shut off flow at required shutoff capacity? Yes Yes Yes Yes Ball Float Valve Inspection 21.Tank top fittings are vapor-tight and leak-free?NA NA NA NA 22.Ball float cage free of debris?NA NA NA NA 23.Ball is free of holes and cracks and moves freely in cage?NA NA NA NA 24.Vent hole in pipe is open and near top of tank?NA NA NA NA 25.Ball float pipe is proper length to restrict flow at required shutoff capacity? NA NA NA NA 12/4/24, 10:46 AM UST OverFill about:blank 1/2 26.Test Result Pass Pass Pass Pass Manufacture's suggested procedures were used. Comments Operator Certification Contractor Printed Name:Larry Vasquez Contractor Signature: Certification Number: 12/4/24, 10:46 AM UST OverFill about:blank 2/2