HomeMy WebLinkAboutDDW-2024-014456WATER STANDARD PLANS
2021
PREFACE
These standard plans incorporate current Water regulations and City water system operation,
maintenance, and asset management considerations.
The plan numbering structure of this document follows the same basic structure as the APWA Standard
Plans, however, there are some differences. Following is an explanation of the structure of this
document:
1. Part 5 – Water Systems. Standard Plan divisions for Water system related details are:
a. Notes, Abbreviations, and Symbols
b. Fire Hydrants
c. Water Meters
d. Corrosion Protection Systems
e. Piping
f. Thrust Blocks
g. Valves
h. Trenching
i. General
2. Numbering – A plan number having a suffix of “S” identifies that the plan contains index, legend,
detail specific notes, and acceptable manufacturer and parts numbers related to the standard
plan.
This document is intended to be altered periodically to ensure that the most current Park City Standards
are available for public use. This document will be revised and published on the City’s web site annually,
during the first week of January.
THE FOLLOWING IS A SUMMARY OF CHANGES MADE TO DRAWINGS
2019
Clarifications were made to ensure adequate separation requirements between water lines and other
utilities. Clarifications regarding pressure testing and disinfection requirements were also added.
2021
500.2 – updated shut down notification requirements. Clarification on potholing requirements as well as
when valves are to be accessible after paving.
511 - Clarification on clearance requirements around all sides of hydrant
511S- Update to new V-Bio poly wrap from High Density Cross Laminated
520.1 – Clarification on clearance requirements around meter vaults
520.2 – Added tracer wire requirement from water main to meter, no irrigation connections within
vaults, and wax tape on all buried fittings
521 – Clarification on service side to home, update to 18-24” height from lid
521S to 528S – Updated Ford model numbers, added supplied meter for reference, wax tape note on all
buried fittings.
529S – updated PTP model number
531 – Clarification on contractor responsibilities
534.1 – included all buried fittings including corps, saddles, repair clamps
534.2 – clarification that wax tape is always required unless soil testing supplied. Included wax tape
instructions
540A – Add “ductile iron pipe” to detail title
540B – update separation requirements as well as minimum length requirements
541 – remove “type K copper” reference
541S – update ford saddle number, as well as change to IP threads from CC
542 - Change detail to require interior meter instead of exterior.
545 – Clarification of how tracer wire is ran
573A – Added clearance requirements from hatch
573C.1 – Updated to accommodate Mag Meters
573C.2 – Updated to accommodate Mag Meters
573C.3 – removed x144 insertion meters on PRV’s
573C.4 – added mag meters
573D.1 – added smart gateway requirement on vaults without power, clarification of vent material to be
bare steel
573E.3 – updated to Burko heater from Dayton
574S – Updated Ford model numbers
576 – clarification that enclosure is bare steel
577 – update to 4” concrete pad only required on commercial backflows
*All drawings with 2019 and 2021 updates are shown with updated date in title block.
TABLE OF CONTENTS
PART 5 – WATER SYSTEMS
Notes, Abbreviations, and Symbols
500.1 General Water Notes
500.2 General Water Notes
Fire Hydrants
511 Fire Hydrant
511 S Fire Hydrant
Water Meters
520.1 General Requirements -Water Meter, Meter Vault, and Service Line
520.2 General Requirements -Water Meter, Meter Vault, and Service Line
521 3/4” and 1” Single Meter – Outside Setting
521 S 3/4” and 1” Single Meter – Outside Setting
522 3/4” and 1” Dual Meters – Outside Setting
522 S 3/4” and 1” Dual Meters – Outside Setting
523 3/4” and 1” Meter – Inside Setting
523 S.1 3/4” and 1” Meter – Inside Setting
523 S.2 3/4” and 1” Meter – Inside Setting
524 1 ½” and 2” Single Meter – Outside Setting
524 S 1 ½” and 2” Single Meter – Outside Setting
525 1 ½” Dual Meters – Outside Setting
525 S 1 ½” Dual Meters – Outside Setting
526 1 ½” and 2” Meter – Inside Setting
526 S.1 1 ½” and 2” Meter – Inside Setting
526 S.2 1 ½” and 2” Meter – Inside Setting
527 3” and Larger Meter – Outside Setting
527 S 3” and Larger Meter – Outside Setting
528 3” and Larger Meter – Inside Setting
528 S.1 3” and Larger Meter – Inside Setting
528 S.2 3” and Larger Meter – Inside Setting
529 Meter Vault Frame and Cover / MXU Device Location
529 S Meter Vault Frame and Cover / MXU Device Location
530 Remote MXU Device
531 Temporary Hydrant Meter Assembly
Corrosion Protection Systems
534.1 Metallic Pipe Corrosion Protection
534.2 Metallic Pipe Corrosion Protection
535-A Type A Test Station
535-B Type I Test Station
535-C Type F Test Station
535-D Type T Test Station
536-A Horizontal Galvanic Anode Installation w/o Test Station
536-B Horizontal Galvanic Anode Installation
537-A Steel and Ductile Iron Pipe Wire Connection
537-B Ductile Iron Pipe Joint Bond
537-C Flexible Joint Bond
537-D Flanged and Mechanical Joint Bond
537-E Galvanic Anode Wire Splice
537-F Insulating Flange
537-G.1 Metallic Pipe Appurtenance and Fitting Cathodic Protection
537-G.2 Metallic Pipe Appurtenance and Fitting Cathodic Protection
537-G.3 Metallic Pipe Appurtenance and Fitting Cathodic Protection
537-G.4 Metallic Pipe Appurtenance and Fitting Cathodic Protection
538-A Post-Style Test Station- Wood
538-B Post-Style Test Station-Plastic
538-C Flush-Style Test Station-Box
538-D Flush-Style Test Station-Terminal Board
Piping
540-A Water Main and Fire Line – 3” to 12” Diameter
540-B Water Main – PVC Pipe – 8” to 12” Diameter
540 S Water Main and Fire Lines
541 Water Service Line – 3/4” to 2” Meters
541 S Water Service Line – 3/4” to 2” Meters
542 Fire Service Line – 3” Diameter and Larger
543 Water Service Line Loop
544-A Water Main Loop
544-B Water Main Loop
544-C Water Main Loop
545-A Tracer Wire – Valve Box Termination
545-B Tracer Wire – Access Box Termination
546 Pipe Insulation at Storm Drain Crossings
547-A Water-Sanitary Sewer Separation
547-B Water-Sanitary Sewer Separation Notes
Thrust Blocks
561 Direct Bearing Thrust Block
562-A Tie-down Thrust Restraints
562-B Tie-down Thrust Restraints
Valves
570 Buried Valve and Valve Box
570 S Buried Valve and Valve Box
571 Valve Box Collar
573-A Pressure Reducing Valve Vault
573-B.1 Pressure Reducing Valve Vault
573-B.2 Pressure Reducing Valve Vault
573-C.1 Pressure Reducing Valve Vault
573-C.2 Pressure Reducing Valve Vault
573-C.3 Pressure Reducing Valve Vault
573-C.4 Pressure Reducing Valve Vault
573-D.1 Pressure Reducing Valve Vault
573-D.2 Pressure Reducing Valve Vault
573-D.3 Pressure Reducing Valve Vault
573-D.4 Pressure Reducing Valve Vault
573-E.1 Pressure Reducing Valve Vault
573-E.2 Pressure Reducing Valve Vault
573-E.3 Pressure Reducing Valve Vault
573-E.4 Pressure Reducing Valve Vault
573-E.5 Pressure Reducing Valve Vault
574 Air Release / CAV Valve Manhole
574 S Air Release / CAV Valve Manhole
575-A Air Release / CAV Valve Manhole – Heat Trace
575-B Air Release / CAV Valve Manhole – Heat Trace Electrical
576 Air Vent Stand Pipe
577 Irrigation Backflow Preventer – Outside Setting
578 Pipe Support
Trenching
580 Water Trench Bedding and Backfill
581 Water Trench Cut-off Wall
General
592 Meter Vault and Water Manhole Grading – Landscape Areas
593 Meter Vault and Water Manhole Collar – Pavement Areas
594.1 Water Service Line Flow Chart
594.2 Water Service Line Flow Chart
595 NFPA 13D Residential Fire Sprinkler Services
595 S NFPA 13D Residential Fire Sprinkler Services
596 Water Line Reference Marker
597 Water Line Casing
597 S Water Line Casing
Water System Field Observation Guidelines 2014
PARK CITY MUNICIPAL CORPORATION WATER
DATE
GENERAL WATER NOTES
STD. PLAN
10/20
500.1 REV.
GENERAL WATER NOTES
1. THE FOLLOWING DOCUMENTS ARE INCORPORATED INTO THESE CONTRACT DOCUMENTS BY REFERENCE:
a. PARK CITY DESIGN STANDARDS, CONSTRUCTION SPECIFICATIONS, AND STANDARD DETAILS
b. AMERICAN WATER WORKS ASSOCIATION STANDARDS (AWWA)
c. UTAH DEPARTMENT OF ENVIRONMENTAL QUALITY, DIVISION OF DRINKING WATER (DDW), R309-550
FACILITY DESIGN AND OPERATION: TRANSMISSION AND DISTRIBUTION PIPELINES
d. INTERNATIONAL PLUMBING CODE
2. ALL PIPE, JOINTS, FITTINGS, VALVES, AND FIRE HYDRANTS SHALL CONFORM TO ANSI/NSF STANDARD 61
AND APPLICABLE SECTIONS OF AWWA STANDARDS C104-08 THROUGH C550-05 AND C900-07 THROUGH
C950-07. ALL BRASS AND BRONZE PIPE, FITTINGS, AND VALVES SHALL MEET LOW LEAD COMPLIANCE
REQUIREMENTS IN ACCORDANCE WITH ANSI/ASTM 371.
3. ALL PRODUCTS AND MATERIALS SHALL BE “MADE IN THE USA”, UNLESS SPECIFICALLY APPROVED BY THE
PARK CITY WATER DIRECTOR. STEEL AND IRON MATERIAL PRODUCTS SUCH AS PIPE, FITTINGS, VALVES,
MANHOLE, METER VAULT, AND VALVE BOX CASTINGS SHALL BE “MELTED & MANUFACTURED IN THE USA”.
PARK CITY WATER ACKNOWLEDGES THAT CERTAIN SPECIALIZED WATER SYSTEM PRODUCTS INCLUDED IN
THE ACCEPTABLE PRODUCTS LIST, SUCH AS HIGHER PRESSURE-RATED VALVES, MAY NOT MEET THE
MADE IN USA REQUIREMENT AND ARE IN THE “QUALIFIED” MADE IN USA CATEGORY. THESE PRODUCTS
HAVE BEEN PREVIOUSLY REVIEWED AND APPROVED.
4. UTAH DIVISION OF DRINKING WATER (DDW) APPROVALS:
a. FOR PROJECTS WITH TRANSMISSION AND/OR DISTRIBUTION LINES OVER 16 INCHES IN DIAMETER
AND/OR INCLUDING A WATER BOOSTER STATION OR PRESSURE REDUCING STATION, DDW APPROVALS
OUTLINED IN R309-500 MUST BE OBTAINED IN CONJUNCTION WITH SUBMITTAL OF A WATER MASTER
PLAN TO THE CITY. FOLLOWING DESIGN REVIEW BY THE CITY AND INCORPORATION OF CITY
COMMENTS, THE DESIGN ENGINEER SHALL SUBMIT WATER CONSTRUCTION PLANS TO THE DDW TO
OBTAIN APPROVALS. NO WATER CONSTRUCTION SHALL COMMENCE UNTIL ALL REQUIRED DDW
APPROVALS HAVE BEEN OBTAINED.
b. FOR PROJECTS WITH TRANSMISSION AND/OR DISTRIBUTION LINES OVER 16 INCHES IN DIAMETER
AND/OR INCLUDING A WATER BOOSTER STATION OR PRESSURE REDUCING STATION A DDW FINAL
OPERATING PERMIT IS REQUIRED PRIOR TO THE CITY OPERATING AND ACCEPTING THE WATER
IMPROVEMENTS. FOLLOWING THE CITY’S WATER SYSTEM WALK-THROUGH AND THE CONTRACTOR’S
SUBSEQUENT COMPLETION OF PUNCH-LIST ITEMS, THE CITY’S WATER DEPARTMENT WILL SUBMIT AN
OPERATING PERMIT REQUEST TO THE DDW. THE FOLLOWING ITEMS ARE REQUIRED FROM THE
DEVELOPER FOR THE CITY’S SUBMITTAL:
i. FINAL RECORD DRAWINGS AND O&M MANUALS
ii. HYDROSTATIC TESTING AND FLUSHING RECORDS (COMPLETED BY THE CITY’S INSPECTOR)
iii. ACCEPTABLE BACTERIOLOGICAL TESTING RESULTS
iv. CERTIFICATION BY THE (DEVELOPER’S) ENGINEER OF RECORD
5. THE CITY UTILIZES AN ADVANCED METERING INFRASTRUCTURE (AMI) SYSTEM. THE DEVELOPER MAY BE
REQUIRED TO CONDUCT A PROPOGATION STUDY AND INSTALL RESULTING RECOMMENDED
IMPROVEMENTS TO FACILITATE A CLEAR SIGNAL TO THE PROJECT. REFER TO STANDARD PLAN 520 FOR
SPECIFIC METER TRANSMITTER UNIT (MXU) REQUIREMENTS.
6. REFER TO APPLICABLE STANDARD PLANS FOR WATER SYSTEM DETAILS AND REQUIREMENTS
7. EXTERNAL CORROSION PROTECTION SHALL BE INCLUDED ON ALL WATER SYSTEM IMPROVEMENTS,
REFERENCE STANDARD PLAN 534 FOR REQUIREMENTS. A SOILS ANALYSIS MAY BE REQUIRED IN
CONJUNCTION WITH THE DESIGN OF THE WATER SYSTEM TO DETERMINE THE EXTENT OF CORROSION
PROTECTION REQUIRED.
8. REFER TO STANDARD PLAN 520 FOR GENERAL REQUIREMENTS FOR WATER METERS, METER VAULTS, AND
WATER SERVICE LINES
9. CITY INSPECTION OF WATER SYSTEM IMPROVEMENTS WILL FOLLOW THE “PUBLIC WATER SYSTEM FIELD
OBSERVATION GUIDELINES” AND ESTABLISHED CITY POLICIES. CONTRACTOR SHALL PROVIDE NECESSARY
ASSISTANCE TO MEET THE GUIDELINE REQUIREMENTS.
10. NOTIFY CITY ENGINEER’S OFFICE AT LEAST 48 HOURS BEFORE PERFORMING ANY WATER RELATED WORK.
ARRANGE A PRECONSTRUCTION CONFERENCE SPECIFIC TO WATER CONSTRUCTION WITH THE CITY
ENGINEER AND WATER DEPARTMENT AT LEAST 48 HOURS BEFORE START OF WORK. FOR PROJECTS
INVOLVING ONLY SERVICE LINE AND/OR METER VAULT INSTALLATION, AN ON-SITE MEETING WITH THE CITY
ENGINEER 48 HOURS PRIOR TO CONSTRUCTION IS ACCEPTABLE.
11. FOR TEMPORARY USE OF EXISTING WATER SYSTEM AND FIRE HYDRANTS TO OBTAIN CONSTRUCTION
WATER, REFER TO STANDARD PLAN 531.
PARK CITY MUNICIPAL CORPORATION WATER
DATE
GENERAL WATER NOTES
STD. PLAN
10/20
500.2 REV.
12. ALL CONSTRUCTION OF WATER SYSTEM SHALL BE CLEARLY STAKING BY THE DEVELOPER’S OR
CONTRACTOR’S SURVEYOR. STAKING SHALL INCLUDE ALL BENDS, VALVES, HYDRANTS, SERVICES, METER
VAULTS, AND SPECIALS. A MINIMUM OF 50-FOOT STATIONING IS REQUIRED FOR PIPELINE.
13. CHANGES TO THE APPROVED WATER PLANS, INCLUDING PIPE ALIGNMENT, SIZE, AND DEPTH AS WELL AS
FITTINGS, VALVES, SERVICES, AND METER VAULT LOCATIONS SHALL BE AUTHORIZED BY THE CITY
ENGINEER PRIOR TO INSTALLATION.
14. WATER SERVICE INTERRUPTION. THE FOLLOWING SHALL BE MET WITH RESPECT TO THE INTERRUPTION
OF SERVICE TO CUSTOMERS INCLUDING THE SHUTDOWN OF THE EXISTING WATER SYSTEM:
a. CONTRACTOR SHALL NOT OPERATE EXISTING WATER VALVES
b. SCHEDULE SERVICE WORK REQUIRING WATER SERVICE INTERRUPTIONS OR SHUTDOWN OF THE
EXSTING WATER SYSTEM A MINIMUM OF 96 HOURS IN ADVANCE WITH THE WATER DEPARTMENT (48HR
WATER DEPARTMENT REVIEW, AND 48HR NOTIFICATION PERIOD)
c. LIMIT INTERRUPTIONS TO OCCUR AND BE COMPLETED ON MONDAY THRU THURSDAY, 9:00 AM TO 4:00
PM. NO INTERRUPTIONS SHALL OCCUR ON FRIDAYS, WEEKENDS, OR HOLIDAYS.
d. CONTRACTOR SHALL BE RESPONSIBLE FOR NOTIFICATION TO AFFECTED CUSTOMERS. CONTACT THE
WATER DEPARTMENT FOR NOTIFICATION REQUIREMENTS. BE ADVISED THAT ON OCCASION VALVES IN
THE EXISTING WATER SYSTEM MAY BE INOPERABLE AND MAY REQUIRE NOTIFICATION OF A LARGER
AREA. IF VALVE MAINTENANCE IS REQUIRED, A SHUTDOWN DELAY OF SEVERAL DAYS SHOULD BE
EXPECTED.
e. FOR WATER SHUTDOWNS LONGER THAN 8 HOURS, CONTRACTOR SHALL SUBMIT A TEMPORARY
WATER PLAN TO KEEP ALL CUSTOMERS IN SERVICE. ALL COSTS ASSOCIATED WITH MAINTAINING
SERVICE TO AFFECTED CUSTOMERS SHALL BE BORNE BY THE CONTRACTOR
f. CONTRACTOR SHALL HAVE ALL PERTINENT PARTS AND MATERIALS ON SITE PRIOR TO SHUTDOWN OF
THE WATER SYSTEM BY THE WATER DEPARTMENT
g. CONSTRUCTION EXCAVATION MUST BE PREPARED AND THE WATER MAIN EXPOSED PRIOR TO
SHUTDOWN OF THE WATER SYSTEM
15. EXPOSE EXISTING WATER PIPES AND VERIFY HORIZONTAL AND VERTICAL LOCATION PRIOR TO INSTALLING
NEW IMPROVEMENTS, POTHOLE ANY AND ALL UTILITIES TO ELIMINATE POTENTIAL CONFLICTS
16. THE HORIZONTAL DISTANCE BETWEEN WATER LINES AND SANITARY SEWER LINES SHALL BE AT LEAST 10
FEET. WHERE A WATER MAIN AND SEWER MUST CROSS, THE WATER MAIN SHALL BE AT LEAST 18 INCHES
ABOVE THE SEWER LINE. SEPARATION DISTANCES SHALL BE MEASURED EDGE-TO-EDGE (I.E. FROM THE
NEAREST EDGES OF THE FACILITIES)
17. IF THE BASIC SEPARATION STANDARDS CANNOT BE MET, AN EXCEPTION TO THE RULE CAN BE APPLIED
WITH ADDITIONAL MITIGATION MEASURES TO PROTECT PUBLIC HEALTH, IN ACCORDANCE WITH UTAH
ADMINISTRATIVE CODE R309-105-6(2)(B).
18. THE OPEN ENDS OF ALL PIPELINES UNDER CONSTRUCTION SHALL BE COVERED AND EFFECTIVELY SEALED
AT THE END OF THE DAY’S WORK.
19. PROVIDE ACCESS TO EXISTING MAIN LINE VALVES THROUGHOUT CONSTRUCTION. ALL VALVES MUST BE
ACCESSIBLE WITHIN 24 HOURS AFTER PAVING OR COLLAR ADJUSTMENTS.
20. UNDER NO CIRCUMSTANCE SHALL THE PIPE OR ACCESSORIES BE DROPPED INTO THE TRENCH.
21. WHERE JOINING EXISTING ASBESTOS CEMENT PIPE, CUT IN ACCORDANCE WITH OSHA REQUIREMENTS
AND DISPOSE OF IN ACCORDANCE WITH APPLICABLE ENVIRONMENTAL REGULATIONS.
22. PROVIDE EXTENSIONS ON VALVE STEM TOPS HAVING OVER 5 FEET BURY. REFER TO STANDARD PLAN 570.
23. INSTALL AIR AND VACUUM VALVES PER STANDARD PLANS 574 AND 575 AT HIGH POINTS (8” DIAMETER PIPE
OR LARGER) AS DEEMED NECESSARY BY THE DESIGN ENGINEER AND CITY.
24. THRUST BLOCKING IS REQUIRED ON ALL WATER MAIN AND FIRE LINES. REFER TO STANDARD PLANS 561
AND 562
25. REMOVE AND CORRECT DEFECTIVE WORK WITHIN 24 HOURS FOLLOWING WRITTEN NOTIFICATION BY THE
CITY ENGINEER.
26. CONSTRUCT TEMPORARY FLUSHING VALVES/BLOW-OFF PIPING ON THE END OF NEW WATER MAINS AS
REQUIRED TO MEET FLUSHING REQUIREMENTS. CONSULT WITH CITY INSPECTOR TO DETERMINE
ACCEPTABLE LOCATIONS AND SIZING REQUIREMENTS. MINIMUM ACCEPTABLE FLUSHING VELOCITY FOR
INITIAL FLUSH IS 6 FEET PER SECOND. DO NOT PERFORM INITIAL FLUSH THROUGH FIRE HYDRANTS.
27. ALL TYPES OF INSTALLED PIPE SHALL BE PRESSURE TESTED AND LEAKAGE TESTED IN ACCORDANCE WITH
AWWA STANDARD C600-10
28. ALL NEW WATER MAINS OR APPURTENANCES SHALL BE DISINFECTED IN ACCORDANCE WITH AWWA
STANDARD C651-05 OR A METHOD APPROVED BY THE DIRECTOR. THE SPECIFICATIONS SHALL INCLUDE
DETAILED PROCEDURES FOR THE ADEQUATE FLUSHING, DISINFECTION AND MICROBIOLOGICAL TESTING
PARK CITY MUNICIPAL CORPORATION WATER
DATE
GENERAL WATER NOTES
STD. PLAN
10/20
500.3 REV.
OF ALL WATER MAINS. ON ALL NEW AND EXTENSIVE DISTRIBUTION SYSTEM CONSTRUCTION, EVIDENCE OF
SATISFACTORY DISINFECTION SHALL BE PROVIDED TO THE CITY INSPECTOR. SAMPLES FOR COLIFORM
ANALYSES SHALL BE COLLECTED AFTER DISINFECTION IS COMPLETE AND THE SYSTEM IS REFILLED WITH
DRINKING WATER. A STANDARD HETEROTROPHIC PLATE COUNT IS ADVISABLE. THE USE OF WATER FOR
PUBLIC DRINKING WATER PURPOSES SHALL NOT COMMENCE UNTIL THE BACTERIOLOGICAL TESTS
INDICATE THE WATER IS FREE FROM CONTAMINATION.
29. DISINFECTING, FLUSHING, AND HYDROSTATIC PLANS SHALL BE SUBMITTED TO THE CITY INSPECTOR A
MINIMUM OF 5 WORKING DAYS PRIOR TO COMMENCEMENT OF ACTIVITY. CONTRACTOR SHALL NOT
OPERATE EXISTING WATER VALVES.
30. BACKFLOW PREVENTION DEVICES MAY BE REQUIRED. IF REQUIRED, THE CITY MAY NOT SET A WATER
METER UNTIL AN APPROVED AND TESTED BACKFLOW DEVICE IS INSTALLED AND INSPECTED
31. ALL BACKFLOW PREVENTERS HAVE TO BE TESTED PERIODICALLY TO ENSURE THAT THEY ARE
FUNCTIONING PROPERLY. A VISUAL CHECK OF AIR GAPS IS SUFFICIENT, BUT MECHANICAL BACKFLOW
PREVENTERS HAVE TO BE TESTED BY A STATE CERTIFIED BACKFLOW SPECIALIST, WITH PROPERLY
CALIBRATED GAUGE EQUIPMENT. TO OBTAIN A LIST OF STATE CERTIFIED TESTERS EITHER CALL US OR
REFER TO THE STATE OF UTAH WEBSITE PAGE OF BACKFLOW TESTERS.
HTTP://WWW.DRINKINGWATER.UTAH.GOV/DOCUMENTS/COMPLIANCE/BACKFLOW_TECHNICIANS_COMMER_
AVAIL.PDF
32. FIRE SPRINKLER SYSTEM BOOSTER PUMPS: FIRE SPRINKLER SYSTEM PUMPS, INTEGRAL TO THE FIRE
SPRINKLER PIPING, REQUIRED TO MEET FIRE SPRINKLER PRESSURE DESIGN REQUIREMENTS, ARE
CONSIDERED OUTSIDE THE INTENT OF UTAH DDW REGULATION R309-550-11(3) AND DO NOT REQUIRE
APPROVAL OF THE DDW IF THEIR INSTALLATION CONFORMS TO UTAH ADOPTED PLUMBING CODE AND
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 13 D. FIRE BOOSTER PUMPS SHALL BE INSTALLED ON
THE BUILDING SIDE OF THE WATER METER VAULT, OUTSIDE THE VAULT, AND SHALL BE APPROVED BY THE
CITY ENGINEER, FIRE MARSHAL, AND BUILDING DEPARTMENT.
PARK CITY MUNICIPAL CORPORATION
WATER
DATE
FIRE HYDRANT
STD. PLAN
10/2020
511 S REV.
LEGEND AND APPROVED PARTS LIST
ITEM DESCRIPTION ACCEPTABLE
MANUFACTURER MODELS
① FIRE HYDRANT, DRY BARREL, AWWA C502
MUELLER
SUPER CENTURION 250 3-WAY
A-423, 5-1/4 PUMPER NOZZLE,
NATIONAL STD. OPERATING NUT
(OPENS LEFT)
CLOW
MEDALLION, 5-1/4 PUMPER NOZZLE,
NATIONAL STD. OPERATING NUT
(OPENS LEFT)
②BURIED VALVE AND VALVE BOX
(STD. PLAN 570), 6” GATE VALVE, NRS, FLG X MJ,
2” SQ. OPERATING NUT, AWWA C509
MUELLER SERIES 2360, SST BONNET BOLTS
CLOW MODEL 2639, SST BONNET BOLTS
③ 6” DUCTILE IRON FLANGE TEE, AWWA C110
④ HYDRANT SERVICE LINE, 6” DIAMETER DUCTILE
IRON PIPE, RESTRAINED JOINTS (STD PLAN 540)
⑤ MECHANICAL JOINT RESTRAINT OR SST TIE ROD
/ NUT RESTRAINTS EBBA IRON MEGALUG SERIES 1100, STD T-BOLTS
AND NUTS
⑥
HYDRANT MARKER, HEAVY DUTY FIBERGLASS
WITH RED FLAG, TOP MOUNT, 5’ LENGTH (STD.),
6’ LENGTH (ABOVE 7300’ ELEVATION)
POLLARD
REFLECTIVE HYDRANT MARKER MODEL
P69161 (STD.) AND P69170 (ABOVE
7300’) WITH FLAG MODEL P691801, OR
APPROVED EQUAL
⑦
POLYETHYLENE ENCASEMENT,
V-BIO ENHANCED POLYETHYLENE ENCASEMENT
FILM, AWWA C105 & AWWA C703E METHOD A & C
US PIPE
AWWA C703E METHOD A (4 MIL) AT PIPE
AND AWWA C703E METHOD C (10 MIL)
AT BOLT-TYPE JOINTS, FITTINGS AND
VALVES
DETAIL NOTES
1. LOCATE HYDRANT AS SHOWN ON THE APPROVED PLANS
2. SET HYDRANT PLUMB WITH PUMPER NOZZLE FACING STREET
3. ADJUST TO GRADE WITH MAXIMUM OF ONE (1) HYDRANT BARREL EXTENSION (AWWA C502)
4. PROVIDE 316 STAINLESS STEEL BOLTS AND NUTS WITH ANTI-SIEZE LUBRICATION ON ALL FLANGED
CONNECTIONS
5. RECOAT DAMAGED OR MARRED HYDRANT COATING AFTER INSTALLATION (UV RESISTANT, HIGH
GLOSS, POLYURETHANE ENAMEL COATING, FIRE HYDRANT RED)
6. REFER TO SPECIFICATIONS FOR FLUSHING, HYDROSTATIC TESTING, AND DISINFECTING
REQUIREMENTS
7. APPLY WAX TAPE COATING SYSTEM TO VALVE BONNET BOLTS AND ALL OTHER BURIED BOLTS, NUTS,
CONNECTORS, AND COUPLINGS, AWWA C 217. (STD PLAN 534)
8. CATHODICALLY PROTECT PIPE AND OR FITTINGS, WHEN EXISTING SOIL CONDITIONS REQUIRE PER
SOILS ANALYSIS (STD. PLAN 534)
9. HYDRANT DRAINS SHALL NOT BE CONNECTED TO, OR LOCATED WITHIN, 10 FEET OF SANITARY
SEWERS. WHERE POSSIBLE, HYDRANT DRAINS SHALL NOT BE LOCATED WITHIN 10 FEET OF STORM
DRAINS.
PARK CITY MUNICIPAL CORPORATION
WATER
DATE
GENERAL REQUIREMENTS
METER, METER VAULT, AND
SERVICE LINE
STD. PLAN
10/2020
520.1 REV.
0
GENERAL REQUIREMENTS –
WATER METER, METER VAULT, AND SERVICE LINE
REFER TO SPECIFICATIONS AND STANDARD PLANS FOR DETAILED WATER METER, METER
VAULT, AND SERVICE LINE REQUIREMENTS
WATER METER & METER VAULT:
1. WATER METER AND RADIOREAD METER TRANSCEIVER UNIT (MXU) WILL BE PROVIDED BY THE CITY.
ALL OTHER COMPONENTS SHALL BE PROVIDED AND INSTALLED BY THE DEVELOPER/BUILDER.
PROVIDE 2 WEEKS ADVANCE NOTICE TO THE WATER DEPARTMENT FOR METER SET REQUESTS
EXCEEDING FIVE METERS OR METER SIZES GREATER THAN 2 INCHES. APPROPRIATE METER
APPLICATION AND PAYMENT OF FEES APPLY BEFORE THE CITY WILL SET A METER.
2. WATER METER SIZE SHALL BE APPROVED BY THE CITY ENGINEER PRIOR TO INSTALLATION OF ANY
SERVICE LINE, METER VAULT, OR WATER MAIN TAP. SEE STANDARD DETAIL 594 FOR SIZING
REQUIREMENTS. A 1.5” MINIMUM WATER SERVICE SIZE IS REQUIRED FROM THE MAIN LINE.
3. INSTALLATION OF A WATER METER EXCEEDING 2-INCH WILL REQUIRE CITY ENGINEER APPROVAL.
THE METER AND VAULT WILL REQUIRE A FLOWRATE AND DEMAND ANALYSIS BY THE DEVELOPER /
BUILDER AND A SITE SPECIFIC DESIGN.
4. INSTALLATION OF A WATER SERVICE LINE SIZE GREATER THAN 1-1/2” WILL REQUIRE CITY ENGINEER
APPROVAL. THE SERVICE LINE UPGRADE REQUEST WILL REQUIRE SUBMITTAL OF A FLOWRATE AND
DEMAND ANALYSIS BY THE DEVELOPER/BUILDER.
5. USE OF AN INSIDE WATER METER WILL REQUIRE CITY ENGINEER APPROVAL. INSIDE METERS SHALL
BE USED ONLY FOR COMMERCIAL OR MULTI-UNIT BUILDINGS SUBJECT TO THE FOLLOWING
CONDITIONS:
A. UNRESTRICTED ACCESS IS AVAILABLE TO WATER DEPARTMENT PERSONNEL
B. THE METER SHALL BE LOCATED IN A SEPARATE MECHANICAL ROOM
C. THE METER SHALL BE ASSOCIATED WITH FIRE PROTECTION SPRINKLER SYSTEM (FIRE STACK)
PLUMBING
D. THE METER REQUIRES A SITE SPECIFIC DESIGN APPROVED BY THE FIRE MARSHAL, THE PARK
CITY BUILDING DEPARTMENT, AND THE WATER DEPARTMENT. LAYOUT SHALL BE CONSISTENT
WITH WATER STANDARD PLANS 523, 526, AND 528
E. A REMOTE RADIOREAD METER TRANSCEIVER UNIT (MXU) DEVICE SHALL BE INSTALLED AT A
LOCATION ACCEPTABLE TO THE WATER DEPARTMENT. REFER TO NOTE 11.
6. METER VAULT LOCATION SHALL BE APPROVED BY THE CITY ENGINEER AND WATER DEPARTMENT
PRIOR TO INSTALLATION OF ANY SERVICE LINE OR WATER MAIN TAP. MINIMUM REQUIREMENTS
AROUND METER VAULT MUST BE MET. NO POWER, IRRIGATION, COMMUNICATION, CABLING, ECT.
WITHIN METER VAULT CLEARANCE AREA.
7. LOCATE METER VAULT, WHENEVER POSSIBLE, IN LANDSCAPE AREAS. PLACEMENT WITHIN A PAVED
SURFACE, DRIVEWAY OR WALKWAY, REQUIRES WRITTEN APPROVAL PRIOR TO INSTALLATION OF THE
SERVICE LINE OR WATER MAIN TAP. THE METER VAULT SHALL BE PLACED AT THE PUBLIC RIGHT OF
WAY LINE. IN THE ABSENCE OF A PUBLIC R-O-W LINE, THE METER VAULT SHALL BE LOCATED WITHIN
A DEDICATED EASEMENT AND A MAXIMUM OF FIVE FEET BEHIND THE CURB AND GUTTER OR
SIDEWALK AS APPLICABLE.
8. EXTEND THE SERVICE LINE STUB ON THE CUSTOMER SIDE TO 5 FEET BEYOND THE METER VAULT
WITH METER VAULT CONSTRUCTION. INSTALL END CAP AND MARKER ON SERVICE LINE
TERMINATION.
9. LOCATE METER VAULT TO PROVIDE CONVENIENT, SAFE, AND UNINHIBITED ACCESS FROM A PUBLIC
ROW OR WATER EASEMENT. NO FENCES SHALL BE LOCATED BETWEEN THE ROW/EASEMENT LINE
AND THE METER VAULT. NO OBSTRUCTIONS OR UTILITIES SHALL BE LOCATED WITHIN 3 FEET OF THE
OUTSIDE WALL OF THE METER VAULT. NO BUSHES, SHRUBS, OR PLANTS SHALL BE WITHIN 2 FEET OF
THE METER LID AND NO TREES SHALL BE PLANTED SUCH THAT THE DRIP LINE AT MATURITY WILL BE
WITHIN 3 FEET OF THE METER LID.
10. SET METER VAULT SET FLUSH WITH THE FINAL LANDSCAPE OR PAVEMENT GRADE. IF THE GROUND IS
NOT TO FINAL GRADE AT THE TIME OF THE METER INSTALLATION OR INSPECTION, ADJUST METER
VAULT WHEN FINAL GRADE IS ESTABLISHED AND ADJUST THE METER SETTER TO MEET REQUIRED
PARK CITY MUNICIPAL CORPORATION
WATER
DATE
GENERAL REQUIREMENTS
METER, METER VAULT, AND
SERVICE LINE
STD. PLAN
10/2020
520.2 REV.
0
VAULT DIMENSIONS. REFERENCE STANDARD PLANS 592 AND 593 FOR METER VAULT GRADING
REQUIREMENTS.
11. IN MOST CASES THE METER TRANSCEIVER UNIT (MXU) DEVICE WILL MOUNT THROUGH THE METER
VAULT LID. IF METER LOCATION DOES NOT PERMIT A CLEAR RELIABLE MXU DEVICE RADIO SIGNAL TO
CITY FACILITIES, A REMOTE MXU DEVICE WILL BE REQUIRED. THE REMOTE MXU DEVICE WILL BE
INSTALLED BY THE CITY, AT A LOCATION DETERMINED BY THE CITY, AT THE TIME OF THE METER
INSPECTION. IN MOST CASES THE REMOTE MXU DEVICE WILL BE INSTALLED ON THE OUTSIDE OF THE
BUILDING FACING A PUBLIC STREET. PROVIDE CONDUIT AND SIGNAL WIRE FROM METER VAULT TO
REMOTE MXU DEVICE LOCATION, REFERENCE STANDARD PLAN 530. FOR DEVELOPMENT PROJECTS,
A SIGNAL PROPAGATION STUDY AND INSTALLATION OF A NEW REPEATER STATION AT THE
DEVELOPER’S EXPENSE MAY BE REQUIRED.
12. IF REPLACING METER VAULT, PROTECT EXISTING METER AND MXU DEVICE, TAG OR LEAVE IN VAULT.
CONTACT PARK CITY WATER DEPARTMENT PRIOR TO REMOVING OR REPLACING METER.
13. PROTECT METER VAULT AND MXU DEVICE THROUGHOUT CONSTRUCTION.
14. A WATER METER WILL NOT BE SET BY THE CITY UNTIL THE METER VAULT AND SERVICE LINE ARE IN
COMPLIANCE WITH THE MOST CURRENT VERSION OF THE ENGINEERING STANDARDS, STANDARD
DRAWINGS, AND APPROVED PROJECT DRAWINGS, A METER INSPECTION HAS BEEN PERFORMED AND
DEFICIENCIES CORRECTED, AND ALL APPLICABLE FEES PAID.
15. ALL BRASS AND BRONZE PIPE, FITTINGS, AND VALVES SHALL MEET LOW LEAD COMPLIANCE
REQUIREMENTS IN ACCORDANCE WITH ANSI/ASTM 371.
16. PROVIDE COMPRESSION STYLE FITTINGS AND VALVES. FLARED STYLE CONNECTIONS ARE NOT
ALLOWED.
SERVICE LINE:
1. ROUTE SERVICE LINES AT A 90 DEGREE ANGLE TO THE FRONT PROPERTY/R-O-W/EASEMENT LINE
FROM THE WATER MAIN. AVOID ROUTING SERVICE LINES UNDER DRIVEWAYS.
2. MAINTAIN 5 FEET OF HORIZONTAL SEPARATION BETWEEN TAP LOCATION AND UTILITY CROSSINGS.
3. DUCTILE IRON WATER MAIN: MAINTAIN 2 FEET SEPARATION BETWEEN SERVICE LINE TAP AND ALL
MAIN LINE FITTINGS, VALVES, PIPE JOINTS, AND OTHER SERVICE TAPS.
4. PVC WATER MAIN: MAINTAIN 3 FEET SEPARATION BETWEEN SERVICE LINE TAP AND ALL MAIN LINE
FITTINGS, VALVES, PIPE JOINTS, AND OTHER SERVICE TAPS.
5. WATER SERVICE LINE SHALL BE CONTINUOUS. NO BENDS, FITTINGS, COUPLERS, OR CONNECTIONS,
ARE PERMITTED BETWEEN WATER MAIN CORPORATION STOP AND THE METER VAULT CURB VALVE.
6. PROVIDE COMPRESSION STYLE VALVES FITTINGS. FLARED STYLE CONNECTIONS ARE NOT ALLOWED.
7. METER VAULTS AND SERVICE LINES MUST BE INSPECTED BY THE CITY PRIOR TO BACKFILLING,
UNLESS SPECIFIC PRIOR APPROVAL IS PROVIDED BY THE CITY.
8. TAPPING NEW CONSTRUCTION WATER MAIN: NOTIFY AND SECURE INSPECTION OF INSTALLATION BY
CITY ENGINEER PRIOR TO TAPPING WATER MAIN. PROVIDE TAPPING “COUPON” TO CITY INSPECTOR
9. TAPPING EXISTING WATER MAIN: NOTIFY AND SECURE INSPECTION OF INSTALLATION BY WATER
DEPARTMENT 48 HOURS PRIOR TO TAPPING WATER MAIN. PROVIDE TAPPING “COUPON” TO CITY
INSPECTOR
10. SERVICES LINES LARGER THAN 2-INCH DIAMETER SHALL MEET WATER MAIN REQUIREMENTS.
11. ALL BRASS AND BRONZE PIPE, FITTINGS, AND VALVES SHALL MEET LOW LEAD COMPLIANCE
REQUIREMENTS IN ACCORDANCE WITH ANSI/ASTM 371
12. DISINFECT ALL NEW WATER SERVICES AND APPURTENANCES IN ACCORDANCE WITH AWWA
STANDARD C651-05, THE SPECIAL REQUIREMENTS OF THE PARK CITY DESIGN STANDARDS,
CONSTRUCTION SPECIFICATIONS, AND STANDARD DETAILS, AND THE PARK CITY WATER SYSTEM
FIELD OBSERVATION GUIDELINES. DISINFECTING, FLUSHING, AND HYDROSTATIC PLANS SHALL BE
SUBMITTED TO THE CITY INSPECTOR A MINIMUM OF 5 WORKING DAYS PRIOR TO COMMENCEMENT OF
ACTIVITY. CONTRACTOR SHALL NOT OPERATE EXISTING WATER VALVES.
13. TRACER WIRE IS REQUIRED FROM WATER MAIN TO METER VAULT.
14. ALL BURIED FITTINGS SHALL BE WAXED TAPED (CORPORATION STOPS, SADDLES, ECT.)
15. NO IRRIGATION CONNECTIONS ARE ALLOWED WITHIN METER VAULT
PARK CITY MUNICIPAL CORPORATION
WATER
DATE
3/4” and 1” SINGLE METER
OUTSIDE SETTING
STD. PLAN
10/2020
521 S REV.
0
LEGEND AND APPROVED PARTS LIST
ITEM DESCRIPTION ACCEPTABLE
MANUFACTURER MODELS
① METER VAULT FRAME AND COVER
(STD. PLAN 529)
②MXU REMOTE LOCATION CONDUIT WITH END CAPS,
SCH 40 PVC (STD. PLAN 530)
③
24” DIAMETER METER VAULT
PAVED AREAS: REINF. CONCRETE PIPE
LANDSCAPE AREAS: CORRUGATED DUAL-WALL HDPE
PIPE
HDPE PIPE: ADS HDPE: MEGA GREEN N-12, OR
APPROVED EQUAL
④ METER, SUPPLIED AND INSTALLED BY PCMC SENSUS iPERL
⑤
3/4” METER YOKE
MUELLER 5/8”x3/4”x9” B2410N-6AN
FORD 5/8”x3/4” VBHC72-9W-11-33-NL
1” METER YOKE MUELLER 1”x12” B2410N-6AN
FORD 1” VBHC74-12W-11-33-NL
⑥ 3/4” OR 1” METER YOKE END CONNECTION
MUELLER MULTI X M.I.P, H-14223N
FORD 3/4” OR 1” CLOSE BRASS NIPPLE
⑦ 1-1/2” X 3/4” OR 1” BRONZE BUSHING
⑧ 1-1/2” CURB VALVE, F.I.P. X CTS (INLET)
MUELLER B-25172N
FORD B41-66Q
⑨ 1-1/2” CONNECTION, F.I.P. X CTS (OUTLET)
MUELLER H-15451N
FORD C-14-66-G-NL
⑩ END CAP AND MARKER, CTS X F.I.P. (OUTLET) MUELLER H-15451N AND H-10035N
⑪ MXU AND WIRING, SUPPLIED AND INSTALLED BY PCMC
DETAIL NOTES
1. LOCATE METER VAULT PER APPROVED PLANS AND SET METER BOX PLUMB
2. SST INSERT STIFFENERS REQUIRED ON ALL CTS TUBING CONNECTIONS
3. WAX TAPE ALL BURIED FITTINGS (CORP STOP, SADDLE, ECT.)
4. TRACER WIRE FROM WATER MAIN TO METER VAULT
PARK CITY MUNICIPAL CORPORATION
WATER
DATE
3/4” and 1” DUAL METER
OUTSIDE SETTING
STD. PLAN
10/2020
522 S REV.
LEGEND AND APPROVED PARTS LIST
ITEM DESCRIPTION ACCEPTABLE
MANUFACTURER MODELS
① 4’ DIA. MANHOLE, PRECAST CONCRETE ECCENTRIC
CONE AND WALL SECTIONS ASTM C 478
② METER VAULT FRAME AND COVER (STD PLAN 529)
③ POLYPROPYLENE ENCASED GRADE 60 STEEL STEPS AT
13” C-C, 13-1/2” TREAD WIDTH
M.A. INDUSTRIES
OR APP’D EQUAL PS2-PFDF
④ 1-1/2” CURB VALVE
MUELLER B-25172N
FORD B41-666Q
⑤ 1-1/2” DIA. BRASS NIPPLE X 6” LENGTH, M.I.P.
⑥1-1/2” DIA. BRONZE TEE, F.I.P., THREADED
⑦ 1-1/2” BRONZE 900 ELBOW, F.I.P., THREADED (2 EA)
⑧ 1-1/2” BRASS NIPPLE X 4” LENGTH, M.I.P. (2 EA)
⑨ BRONZE BELL REDUCER REQ’D (2 EA)
3/4” YOKE: 1-1/2” X 3/4”
1” YOKE: 1-1/2” X 1” DIA.
⑩
3/4” METER YOKE (2 EA) MUELLER 5/8”x3/4”x9” B2404N-6AN
FORD 5/8”x3/4” VBHC72-9W-11-33-NL
1” METER YOKE (2 EA)
MUELLER 1”x12” B2404N-6AN
FORD 1” VBHC74-12W-11-33-NL
⑪ 3/4” OR 1” METER YOKE END CONNECTIONS (2 EA)
MUELLER MULTI X M.I.P., H-14223N
FORD 3/4” OR 1” CLOSE BRASS NIPPLE
⑫ 1-1/2” x 3/4” OR 1” BRONZE BUSHING (OUTLET) (2 EA)
⑬ 1-1/2” CONNECTION, F.I.P. X CTS (OUTLET) (2 EA)
MUELLER H-15451N
FORD C-14-66-G-NL
⑭ METER, SUPPLIED AND INSTALLED BY PCMC (2 EA) SENSUS iPERL
⑮ PIPE SUPPORTS, GALVANIZED PIPE SUPPORT ROD AND
(2) 16”x8”x8” CMU BLOCK
⑯ MXU AND WIRING, SUPPLIED AND INSTALLED BY PCMC
⑰ MXU REMOTE LOCATION CONDUIT WITH END CAPS,
SCH 40 PVC (STD. PLAN 531)
⑱ END CAP AND MARKER, CTS X F.I.P. (OUTLET) (2 EA) MUELLER H-15451N AND H-10035N
⑲ 3/4” OR 1” UNIONS (2 EA)
DETAIL NOTES
1. LOCATE METER VAULT PER APPROVED PLANS AND SET METER BOX PLUMB
2. SST INSERT STIFFENERS REQUIRED ON ALL CTS TUBING CONNECTION
3. USE PIPE DOPE OR TEFLON TAPE ON THREADED FITTINGS
4. WAX TAPE ALL BURIED FITTINGS. TRACER WIRE REQUIRED FROM WATER MAIN TO METER
PARK CITY MUNICIPAL CORPORATION
WATER
DATE
3/4” and 1” METER
INSIDE SETTING
STD. PLAN
10/2020
523 S.1 REV.
0
LEGEND AND APPROVED PARTS LIST
ITEM DESCRIPTION ACCEPTABLE
MANUFACTURER MODELS
① 1” BRONZE SERVICE SADDLE, DOUBLE STRAP MUELLER BR2B SERIES, CC THREADS
FORD STYLE 202B, CC THREADS
② 1” DIA. BRASS NIPPLE x 2” LENGTH, M.I.P.
③ 1” CURB VALVE, F.I.P. X F.I.P. MUELLER B-20283N
④ 1” DIA. BRASS NIPPLE x 2” LENGTH, M.I.P. AND BRONZE
BELL REDUCER, 1” X 3/4” DIA. (REQ’D FOR 3/4” METER
YOKE ONLY)
⑤ 3/4” OR 1” DIA. COPPER PIPING AND FITTINGS, AS REQ’D
PER SITE SPECIFIC LAYOUT
⑥3/4” OR 1” METER YOKE END CONNECTIONS MUELLER MULTI X F.I.P, H-14222N
⑦
3/4” METER YOKE (STRAIGHT LINE INLET AND OUTLET) MUELLER 5/8”x3/4”x7” B-2418-6AN
FORD 5/8”x3/4” LSVH11-233W-NL
3/4” METER YOKE (VERTICAL INLET AND OUTLET)
MUELLER 5/8”x3/4”x10” B-2448-6AN
FORD 5/8”x3/4” LSVH11-233W-NL
1” METER YOKE (STRAIGHT LINE INLET AND OUTLET)
MUELLER 1” VBHC84-12W-11-44-NL
FORD 1” LSVH11-444W-NL
1” METER YOKE (VERTICAL INLET AND OUTLET)
MUELLER 1”x12” B-2448-6AN
FORD 1” KHVBHC-4-FP-NL
⑧ METER, SUPPLIED AND INSTALLED BY PCMC SENSUS iPEARL
⑨ PIPE SIZE BRASS NIPPLE AND CURB VALVE, F.I.P. X
F.I.P. MUELLER B-20283N
⑩ MXU AND WIRING, SUPPLIED AND INSTALLED BY PCMC
⑪ EMT CONDUIT FOR MXU WIRING, AS REQUIRED
PARK CITY MUNICIPAL CORPORATION
WATER
DATE
3/4” and 1” METER
INSIDE SETTING
STD. PLAN
10/2020
523 S.2 REV.
0
DETAIL NOTES
1. USE OF AN INSIDE WATER METER REQUIRES CITY ENGINEER APPROVAL. REFERENCE WATER
STANDARD PLAN 520 FOR APPLICABLE CONDITIONS.
2. FIRE SPRINKLER RISER WITH POTABLE WATER SERVICE: A SITE SPECIFIC DESIGN IS REQUIRED.
THE FIRE PROTECTION SPRINKLER SYSTEM AND POTABLE WATER SYSTEM DESIGN SHALL BE
APPROVED BY THE FIRE MARSHAL AND THE PARK CITY BUILDING DEPARTMENT. THE POTABLE
WATER SERVICE CONNECTION AND METER ASSEMBLY DESIGN SHALL BE APPROVED BY THE PARK
CITY BUILDING DEPARTMENT AND THE CITY ENGINEER. DESIGN AND CONSTRUCTION SHALL COMPLY
WITH APPLICABLE BUILDING AND PLUMBING CODES.
3. BACKFLOW PREVENTION: PROVIDE A DOUBLE CHECK BACKFLOW ASSEMBLY (DCBA) OR REDUCED
PRESSURE PRINCIPLE BACKFLOW ASSEMBLY (RPBA) ON THE FIRE SPRINKLER RISER ASSEMBLY.
STYLE TO BE DETERMINED BY THE BUILDING AND WATER DEPARTMENT BASED ON DEGREE OF
HAZARD POSED BY FIRE SPRINKLER PROTECTION SYSTEM. BEFORE A CERTIFICATE OF OCCUPANCY
CAN BE ISSUED BY THE BUILDING DEPARTMENT, BACKFLOW ASSEMBLY TESTING FOR PROPER
OPERATION (PER CITY REQUIREMENTS BY A CERTIFIED TESTER RECOGNIZED BY THE CITY) IS
REQUIRED AND A REPORT SUBMITTED.
4. CONNECTIONS TO THE WATER SYSTEM ARE NOT PERMITTED PRIOR TO THE POTABLE WATER METER
ASSEMBLY OR THE FIRE SPRINKLER RISER BACKFLOW ASSEMBLY. THIS INCLUDES OUTSIDE
IRRIGATION SUPPLY.
5. CLEARANCES: PROVIDE ADEQUATE CLEARANCES FROM FIRE RISER AND AROUND WATER METER
ASSEMBLY. MAINTAIN: 9” MINIMUM FROM WALL TO FACE OF POTABLE WATER PIPING
18” CLEAR ON EACH SIDE OF METER ASSEBLY
36” CLEAR IN FRONT OF METER ASSEMBLY
6. LOCATE METER ASSEMBLY TWO (2) TO FOUR (4) FEET ABOVE THE FLOOR. POSITION METER
HORIZONTAL WITH DIAL POINTING UP.
7. PROVIDE ISOLATION (CURB) VALVES AT METER INLET AND OUTLET
8. FOR MULTIPLE METERS PROVIDE A MANIFOLD WITH A MAIN CURB VALVE PRIOR TO THE MANIFOLD
AND INDIVIDUAL CURB VALVES LOCATED PRIOR TO AND AFTER METERS.
9. PROVIDE A FLOOR DRAIN IN THE FIRE RISER ROOM WITHIN 10 FEET OF THE WATER METER LOCATION.
10. PROVIDE PIPE LABELS ON THE POTABLE WATER LINE BETWEEN THE FIRE RISER AND THE WATER
METER DESIGNATING PIPE AS “POTABLE WATER”.
11. PROVIDE PIPE ANCHORAGE TO SUPPORT METER YOKE AND ASSEMBLY INDEPENDENT OF THE
POTABLE WATER SUPPLY PIPING AND BUILDING PLUMBING. PROVIDE PIPE STANDS OR UNISTRUT
WALL STANDOFFS. DO NOT SUPPORT METER ASSEMBLY FROM OTHER PIPING.
12. PROVIDE A WALL PENETRATION AND CONDUIT FOR REMOTE RADIOREAD METER TRANSEIVER UNIT
(MXU) DEVICE(S). COORDINATE ROUTING AND WALL PENETRATION LOCATION WITH THE WATER
DEPARTMENT. REFERENCE WATER STANDARD PLANS 520 AND 530.
13. PROVIDE 1/2” EMT CONDUIT AND SUPPORTS FOR MXU SIGNAL WIRE IF DISTANCE TO WALL
PENETRATION EXCEEDS 10 FEET
14. INSPECTION: CONTACT THE CITY ENGINEER FOR INSPECTION OF THE POTABLE WATER SYSTEM
METER ASSEMBLY INSTALLATION
15. REFER TO STD. PLAN 500 AND THE SPECIFICATIONS FOR FLUSHING, HYDROSTATIC TESTING, AND
DISINFECTING REQUIREMENTS
PARK CITY MUNICIPAL CORPORATION
WATER
DATE
1-1/2” and 2” SINGLE METER
OUTSIDE SETTING
STD. PLAN
10/2020
524 S REV.
LEGEND AND APPROVED PARTS LIST
ITEM DESCRIPTION ACCEPTABLE
MANUFACTURER MODELS
① 5’ DIA. MANHOLE, PRECAST CONCRETE ECCENTRIC
CONE AND WALL SECTIONS ASTM C 478
② METER VAULT FRAME AND COVER (STD. PLAN 529)
③ POLYPROPYLENE ENCASED GRADE 60 STEEL STEPS
AT 13” C-C, 13-1/2” TREAD WIDTH
M.A. INDUSTRIES
OR APPV’D EQ. PS2-PFDF
④ 2” CURB VALVE, F.I.P. x CTS
MUELLER B-25172N
FORD B11-777Q
⑤ 2” DIA. BRASS NIPPLE x 4” LENGTH, M.I.P.
⑥ 2” BRONZE UNION, F.I.P., THREADED
⑦ 1-1/2” BRASS NIPPLE x 4” LENGTH, 2” x 1-1/2” BRONZE
BELL REDUCER, AND 1-1/2” CLOSE BRASS NIPPLE
(1-1/2” YOKE ONLY)
⑧
1-1/2” METER YOKE
COMMERCIAL SERVICE: WITH BYPASS
RESIDENTIAL SERVICE: WITHOUT BYPASS
IRRIGATION SERVICE: WITHOUT BYPASS
MUELLER
1-1/2”x15” B2423-2-01N (WITH
BYPASS)
1-1/2”x15” B2422-2N (WITHOUT
BYPASS)
FORD
1-1/2” VBHH76-15B-11-66-NL
(WITH BYPASS)
1-1/2” VBHH76-15-11-66-NL
(WITHOUT BYPASS)
2” METER YOKE
COMMERCIAL SERVICE: WITH BYPASS
RESIDENTIAL SERVICE: WITHOUT BYPASS
IRRIGATION SERVICE: WITHOUT BYPASS
MUELLER
2”x15” B2423-2-01N (WITH BYPASS)
2”x15” B2422-2N
(WITHOUT BYPASS)
FORD
2” VBHH77-15B-11-77-NL
(WITH BYPASS)
2” VBHH77-15-11-77-NL
(WITHOUT BYPASS)
⑨
2” CONNECTION, F.I.P. x CTS AND 2” BRASS NIPPLE x 4”
LENGTH (OUTLET);
1-1/2” YOKE ONLY: ADD 2”x1-1/2” BRONZE BELL
REDUCER AND 1-1/2” CLOSE BRASS NIPPLE
MUELLER H-15451N
FORD C-14-66-G-NL
⑩ METER, SUPPLIED AND INSTALLED BY PCMC SENSUS OMNI
⑪ PIPE SUPPORTS (4) 16”x8”x8” CMU BLOCK, (2) METER
SUPPORT RODS, GALVANIZED
⑫ MXU AND WIRING, SUPPLIED AND INSTALLED BY PCMC
⑬ MXU REMOTE LOCATION CONDUIT WITH END CAPS,
SCH 40 PVC (STD. PLAN 531)
⑭ END CAP AND MARKER, CTS x F.I.P. (OUTLET) H-15451N AND H-10035N
DETAIL NOTES
1. LOCATE METER VAULT PER APPROVED PLANS AND SET METER BOX PLUMB
2. SST INSERT STIFFENERS REQUIRED ON ALL CTS TUBING CONNECTIONS
PARK CITY MUNICIPAL CORPORATION
WATER
DATE
1-1/2” DUAL METERS
OUTSIDE SETTING
STD. PLAN
10/2020
525 S REV.
LEGEND AND APPROVED PARTS LIST
ITEM DESCRIPTION ACCEPTABLE
MANUFACTURER MODELS
① 5’ DIA. MANHOLE, PRECAST CONCRETE ECCENTRIC
CONE AND WALL SECTIONS ASTM C 478
② METER VAULT FRAME AND COVER (STD. PLAN 529)
③ POLYPROPYLENE ENCASED GRADE 60 STEEL STEPS
AT 13” C-C, 13-1/2” TREAD WIDTH
M.A. INDUSTRIES
OR APPV’D EQ. PS2-PFDF
④ 2” CURB VALVE, F.I.P. x CTS
MUELLER B-25172N
FORD B11-777Q
⑤ 2” DIA. BRASS NIPPLE x 3” LENGTH, M.I.P. (5 EA)
⑥ 2” DIA. BRONZE TEE, F.I.P., THREADED
⑦ 2” BRONZE 900 ELBOW, F.I.P., THREADED (2 EA)
⑧ 2” BRONZE UNION, F.I.P., THREADED (2 EA)
⑨ 1-1/2” BRASS NIPPLE x 4” LENGTH, 2” x 1-1/2” BRONZE
BELL REDUCER, AND 1-1/2” CLOSE BRASS NIPPLE
(2 EA)
⑩
1-1/2” METER YOKE (2 EA)
COMMERCIAL SERVICE: WITH BYPASS
RESIDENTIAL SERVICE: WITHOUT BYPASS
IRRIGATION SERVICE: WITHOUT BYPASS
MUELLER
1-1/2”x15” B2423-2-01N
(WITH BYPASS)
1-1/2”x15” B2422N
(WITHOUT BYPASS)
FORD
1-1/2” VBHH76-15B-11-66-NL
(WITH BYPASS)
1-1/2” VBHH76-15-11-66-NL
(WITHOUT BYPASS)
⑪ 2” CONNECTION, F.I.P. x CTS; 2” BRASS NIPPLE x 4”
LENGTH; 2”x1-1/2” BRONZE BELL REDUCER; AND 1-1/2”
CLOSE BRASS NIPPLE (OUTLET) (2 EA)
MUELLER H-15451N
FORD C-14-66-G-NL
⑫ METER, SUPPLIED AND INSTALLED BY PCMC (2 EA) SENSUS OMNI
⑬ PIPE SUPPORTS (4) 16”X8”X8” CMU BLOCK, (2) METER
SUPPORT RODS, GALVANIZED
⑭ MXU AND WIRING, SUPPLIED AND INSTALLED BY PCMC
⑮ MXU REMOTE LOCATION CONDUIT WITH END CAPS,
SCH 40 PVC (STD. PLAN 531)
⑯ END CAP AND MARKER, CTS X F.I.P. (OUTLET) (2 EA) H-15451N AND H-10035N
DETAIL NOTES
1. LOCATE METER VAULT PER APPROVED PLANS AND SET METER BOX PLUMB
2. SST INSERT STIFFENERS REQUIRED ON ALL CTS TUBING CONNECTIONS
PARK CITY MUNICIPAL CORPORATION
WATER
DATE
1-1/2” and 2” METER
INSIDE SETTING
STD. PLAN
10/2020
526 S.1 REV.
0
LEGEND AND APPROVED PARTS LIST
ITEM DESCRIPTION ACCEPTABLE
MANUFACTURER MODELS
① DUCTILE IRON TEE OR
2” BRONZE SERVICE SADDLE, DOUBLE STRAP
MUELLER BR2B SERIES, FIP THDS
FORD STYLE 202B, FIP THDS
② 2” DIA. BRASS NIPPLE x 2” LENGTH, M.I.P.
③ 2” CURB VALVE, F.I.P. X F.I.P.
MUELLER B-20283N
FORD B11-777Q
④ 2” DIA. BRASS NIPPLE x 2” LENGTH, M.I.P. AND BRONZE
BELL REDUCER, 2” X 1-1/2” DIA. (REQ’D FOR 1-1/2” YOKE
ONLY)
⑤ 1-1/2” OR 2” DIA. BRASS NIPPLES AND BRASS FITTINGS
OR COPPER PIPING AND FITTINGS, AS REQ’D PER SITE
SPECIFIC LAYOUT
⑥1-1/2” OR 2” METER YOKE END CONNECTIONS MUELLER MULTI X F.I.P, H-14222N
⑦
1-1/2” METER YOKE
COMMERCIAL SERVICE: WITH BYPASS
RESIDENTIAL SERVICE: WITHOUT BYPASS
MUELLER
1-1/2”x12” B2423-2-01N (WITH
BYPASS)
1-1/2”x12” B2422-2N (WITHOUT
BYPASS)
FORD
1-1/2” VBHH76-12B-11-66-NL
(WITH BYPASS)
1-1/2” VBHH76-12-11-66-NL
(WITHOUT BYPASS)
2” METER YOKE
COMMERCIAL SERVICE: WITH BYPASS
RESIDENTIAL SERVICE: WITHOUT BYPASS
MUELLER
2”x12” B2423-2-01N (WITH
BYPASS)
2”x12” B2422-2N
(WITHOUT BYPASS)
FORD
2” VBHH77-12B-11-77-NL
(WITH BYPASS)
2” VBHH77-12-11-77-NL
(WITHOUT BYPASS)
⑧ PIPE SIZE BRASS NIPPLE AND BRONZE UNION, F.I.P.,
THREADED
⑨ METER, SUPPLIED AND INSTALLED BY PCMC SENSUS OMNI
⑩ MXU AND WIRING, SUPPLIED AND INSTALLED BY PCMC
⑪ EMT CONDUIT FOR MXU WIRING, AS REQUIRED
PARK CITY MUNICIPAL CORPORATION
WATER
DATE
1-1/2” and 2” METER
INSIDE SETTING
STD. PLAN
10/2020
526 S.2 REV.
0
DETAIL NOTES
1. USE OF AN INSIDE WATER METER REQUIRES CITY ENGINEER APPROVAL. REFERENCE WATER
STANDARD PLAN 520 FOR APPLICABLE CONDITIONS.
2. FIRE SPRINKLER RISER WITH POTABLE WATER SERVICE: A SITE SPECIFIC DESIGN IS REQUIRED.
THE FIRE PROTECTION SPRINKLER SYSTEM AND POTABLE WATER SYSTEM DESIGN SHALL BE
APPROVED BY THE FIRE MARSHAL AND THE PARK CITY BUILDING DEPARTMENT. THE POTABLE
WATER SERVICE CONNECTION AND METER ASSEMBLY DESIGN SHALL BE APPROVED BY THE PARK
CITY BUILDING DEPARTMENT AND THE CITY ENGINEER. DESIGN AND CONSTRUCTION SHALL COMPLY
WITH APPLICABLE BUILDING AND PLUMBING CODES.
3. BACKFLOW PREVENTION: PROVIDE A DOUBLE CHECK BACKFLOW ASSEMBLY (DCBA) OR REDUCED
PRESSURE PRINCIPLE BACKFLOW ASSEMBLY (RPBA) ON THE FIRE SPRINKLER RISER ASSEMBLY.
STYLE TO BE DETERMINED BY THE BUILDING AND WATER DEPARTMENT BASED ON DEGREE OF
HAZARD POSED BY FIRE SPRINKLER PROTECTION SYSTEM. BEFORE A CERTIFICATE OF OCCUPANCY
CAN BE ISSUED BY THE BUILDING DEPARTMENT, BACKFLOW ASSEMBLY TESTING FOR PROPER
OPERATION (PER CITY REQUIREMENTS BY A CERTIFIED TESTER RECOGNIZED BY THE CITY) IS
REQUIRED AND A REPORT SUBMITTED.
4. CONNECTIONS TO THE WATER SYSTEM ARE NOT PERMITTED PRIOR TO THE POTABLE WATER METER
ASSEMBLY OR THE FIRE SPRINKLER RISER BACKFLOW ASSEMBLY. THIS INCLUDES OUTSIDE
IRRIGATION SUPPLY.
5. CLEARANCES: PROVIDE ADEQUATE CLEARANCES FROM FIRE RISER AND AROUND WATER METER
ASSEMBLY. MAINTAIN: 9” MINIMUM FROM WALL TO FACE OF POTABLE WATER PIPING
18” CLEAR ON EACH SIDE OF METER ASSEBLY
36” CLEAR IN FRONT OF METER ASSEMBLY
6. LOCATE METER ASSEMBLY TWO (2) TO FOUR (4) FEET ABOVE THE FLOOR. POSITION METER
HORIZONTAL WITH DIAL POINTING UP.
7. PROVIDE ISOLATION (CURB) VALVES AT METER INLET AND OUTLET
8. FOR MULTIPLE METERS PROVIDE A MANIFOLD WITH A MAIN CURB VALVE PRIOR TO THE MANIFOLD
AND INDIVIDUAL CURB VALVES LOCATED PRIOR TO AND AFTER METERS.
9. PROVIDE A FLOOR DRAIN IN THE FIRE RISER ROOM WITHIN 10 FEET OF THE WATER METER LOCATION.
10. PROVIDE PIPE LABELS ON THE POTABLE WATER LINE BETWEEN THE FIRE RISER AND THE WATER
METER DESIGNATING PIPE AS “POTABLE WATER”.
11. PROVIDE PIPE ANCHORAGE TO SUPPORT METER YOKE AND ASSEMBLY INDEPENDENT OF THE
POTABLE WATER SUPPLY PIPING AND BUILDING PLUMBING. PROVIDE PIPE STANDS OR UNISTRUT
WALL STANDOFFS. DO NOT SUPPORT METER ASSEMBLY FROM OTHER PIPING.
12. PROVIDE A WALL PENETRATION AND CONDUIT FOR REMOTE RADIOREAD METER TRANSEIVER UNIT
(MXU) DEVICE(S). COORDINATE ROUTING AND WALL PENETRATION LOCATION WITH THE WATER
DEPARTMENT. REFER TO WATER STANDARD PLANS 520 AND 530.
13. PROVIDE 1/2” EMT CONDUIT AND SUPPORTS FOR MXU SIGNAL WIRE IF DISTANCE TO WALL
PENETRATION EXCEEDS 10 FEET.
14. INSPECTION: CONTACT THE CITY ENGINEER FOR INSPECTION OF THE POTABLE WATER SYSTEM
METER ASSEMBLY INSTALLATION
15. REFER TO STD. PLAN 500 AND THE SPECIFICATIONS FOR FLUSHING, HYDROSTATIC TESTING, AND
DISINFECTING REQUIREMENTS
PARK CITY MUNICIPAL CORPORATION
WATER
DATE
3” AND LARGER METER
OUTSIDE SETTING
STD. PLAN
10/2020
527 S REV.
LEGEND AND APPROVED PARTS LIST
ITEM DESCRIPTION ACCEPTABLE
MANUFACTURER MODELS
① 2” BRONZE SERVICE SADDLE, DOUBLE STRAP
MUELLER BR2B SERIES, F.I.P. THREADS
FORD 202B SERIES, F.I.P. THREADS
② GATE VALVE, PIPE SIZE, NRS, FLANGED,
2” SQ. OPERATING NUT, AWWA C509
MUELLER SERIES A-2360
CLOW MODEL 2639
③ DUCTILE IRON PIPE SPOOL (2), FLG X PE
④ METER, SUPPLIED AND INSTALLED BY PCMC SENSUS OMNI
⑤PRECAST CONCRETE VAULT, HS20 RATED
⑥ 2” BRONZE BALL VALVE WITH LOCKING HANDLE, F.I.P.,
THREADED, 300 PSI RATED FORD B11-777Q
⑦ DISMANTLING JOINT ROMAC DJ400 OR APPV’D EQUAL
⑧ 2” DIA. COPPER 900 ELBOW, SOLDERED, OR BRONZE,
F.I.P., THREADED
⑨ 2” DIA. BRONZE UNION, F.I.P., THREADED
⑩ 2” COPPER PIPE, TYPE K, OR BRASS NIPPLE
⑪ DUCTILE IRON PIPE SPOOL, 9” LENGTH, FLG X FLG
⑫ DUCTILE IRON PIPE SPOOL, FLG X PE
⑬ AFTER PIPING INSTALLATION CORE DRILL 6” DIA. HOLE IN
VAULT LID DIRECTLY ABOVE GATE VALVES
⑭ VALVE BOX, FASTEN VALVE BOX TO VAULT WITH TWO
EPOXIED ALL-THREAD ROD/NUT OR SST EXP ANCHOR
D & L SUPPLY
HILTI
M-8065 AND M-8048 TO M-8053
3/8” DIA. ROD SST 316, OR
KWIK BOLT 3 3/8”x3” SS316
⑮ THRUST RESTRAINTS EBBA IRON MEGALUG SERIES 1100
⑯ POLYPROPYLENE ENCASED GRADE 60 STL STEPS AT
13” C-C, 13-1/2” TREAD WIDTH
M.A. INDUSTRIES
OR APPV’D EQUAL PS2-PFDF
⑰ METER VAULT FRAME AND COVER (STD. PLAN 529)
⑱ PIPE SUPPORTS, 5 REQ’D (STD. PLAN 533)
⑲ MXU AND WIRING, SUPPLIED AND INSTALLED BY PCMC
DETAIL NOTES
1. REFER TO STD. PLAN 520 FOR GENERAL REQUIREMENTS – METER, METER VAULT, AND SERVICE LINE
2. LOCATE METER VAULT PER APPROVED PLANS AND SET METER BOX PLUMB
3. SST FASTENERS REQUIRED ON ALL FITTINGS
4. NO BYPASS ALLOWED FOR IRRIGATION METERS
5. NO SERVICE LINE REDUCERS OR BENDS WITHIN 5’ OF VAULT
6. COORDINATE METER SIZE AND LENGTH WITH CITY PRIOR TO ORDERING MATERIALS
7. REFER TO STD. PLANS 592 AND 593 FOR MANHOLE ADJUSTMENT AND GRADING REQUIREMENTS
PARK CITY MUNICIPAL CORPORATION
WATER
DATE
3” AND LARGER METER
INSIDE SETTING
STD. PLAN
10/2020
528 S.1 REV.
0
LEGEND AND APPROVED PARTS LIST
ITEM DESCRIPTION ACCEPTABLE
MANUFACTURER MODELS
① DUCTILE IRON TEE, FLG., PRESSURE CLASS 350,
CEMENT-MORTAR LINED, ASPHALTIC INTERIOR
COATING, AWWA C150 / C151 / C104
U.S. PIPE
PACIFIC STATES
U.S. PIPE
PACIFIC STATES
②
DUCTILE IRON PIPE SPOOL, FLG. X FLG., 3” TO 12”
DIAMETER, FULL BODY, PRESSURE CLASS 350,
CEMENT-MORTAR LINED, ASPHALTIC INTERIOR
COATING, AWWA C150 / C151 / C104
U.S. PIPE
PACIFIC STATES
③ 2” BRONZE SERVICE SADDLE, DOUBLE STRAP
MUELLER BR2B SERIES, FIP THDS
FORD STYLE 202B, FIP THDS
④ 2” BRONZE BALL VALVE WITH LOCKING HANDLE, F.I.P.,
THREADED, 300 PSI RATED, LEAD FREE FORD B11-777Q
⑤ GATE VALVE, PIPE SIZE, NRS WITH HANDWHEEL,
FLANGED, 2” SQ. OPERATING NUT, AWWA C509
MUELLER SERIES A-2360
CLOW MODEL 2639
⑥METER, SUPPLIED AND INSTALLED BY PCMC SENSUS OMNI
⑦DUCTILE IRON PIPE SPOOL (2), FLG X PE
⑧DISMANTLING JOINT, WITH RESTRAINING BOLTS ROMAC DJ400 OR APPV’D EQUAL
⑨ 2” BRONZE UNION, F.I.P., THREADED, LEAD FREE
⑩ 2” COPPER PIPE, TYPE K, WITH COPPER 900 ELBOW,
SOLDERED, OR BRASS NIPPLE BRONZE, F.I.P., WITH
THREADED 900 ELBOW (NO GALVANIZED MATERIALS)
⑪ PIPE SUPPORTS, 2 REQ’D ON MAIN SERVICE LINE AND 2
REQ’D ON BYPASS SERVICE
⑫ MXU AND WIRING, SUPPLIED AND INSTALLED BY PCMC
⑬ 1/2” EMT CONDUIT FOR MXU WIRING, AS REQUIRED
PARK CITY MUNICIPAL CORPORATION
WATER
DATE
3” AND LARGER METER
INSIDE SETTING
STD. PLAN
10/2020
528 S.2 REV.
0
DETAIL NOTES
1. USE OF AN INSIDE WATER METER REQUIRES CITY ENGINEER APPROVAL. REFERENCE WATER
STANDARD PLAN 520 FOR APPLICABLE CONDITIONS.
2. FIRE SPRINKLER RISER WITH POTABLE WATER SERVICE: A SITE SPECIFIC DESIGN IS REQUIRED.
THE FIRE PROTECTION SPRINKLER SYSTEM AND POTABLE WATER SYSTEM DESIGN SHALL BE
APPROVED BY THE FIRE MARSHAL AND THE PARK CITY BUILDING DEPARTMENT. THE POTABLE
WATER SERVICE CONNECTION AND METER ASSEMBLY DESIGN SHALL BE APPROVED BY THE PARK
CITY BUILDING DEPARTMENT AND THE CITY ENGINEER. DESIGN AND CONSTRUCTION SHALL COMPLY
WITH APPLICABLE BUILDING AND PLUMBING CODES.
3. BACKFLOW PREVENTION: PROVIDE A DOUBLE CHECK BACKFLOW ASSEMBLY (DCBA) OR REDUCED
PRESSURE PRINCIPLE BACKFLOW ASSEMBLY (RPBA) ON THE FIRE SPRINKLER RISER ASSEMBLY.
STYLE TO BE DETERMINED BY THE BUILDING AND WATER DEPARTMENT BASED ON DEGREE OF
HAZARD POSED BY FIRE SPRINKLER PROTECTION SYSTEM. BEFORE A CERTIFICATE OF OCCUPANCY
CAN BE ISSUED BY THE BUILDING DEPARTMENT, BACKFLOW ASSEMBLY TESTING FOR PROPER
OPERATION (PER CITY REQUIREMENTS BY A CERTIFIED TESTER RECOGNIZED BY THE CITY) IS
REQUIRED AND A REPORT SUBMITTED.
4. CONNECTIONS TO THE WATER SYSTEM ARE NOT PERMITTED PRIOR TO THE POTABLE WATER METER
ASSEMBLY OR THE FIRE SPRINKLER RISER BACKFLOW ASSEMBLY. THIS INCLUDES OUTSIDE
IRRIGATION SUPPLY.
5. CLEARANCES: PROVIDE ADEQUATE CLEARANCES FROM FIRE RISER AND AROUND WATER METER
ASSEMBLY. MAINTAIN: 9” MINIMUM FROM WALL TO FACE OF POTABLE WATER PIPING
18” CLEAR ON EACH SIDE OF METER ASSEBLY
36” CLEAR IN FRONT OF METER ASSEMBLY
6. LOCATE METER ASSEMBLY TWO (2) TO FOUR (4) FEET ABOVE THE FLOOR. POSITION METER
HORIZONTAL WITH DIAL POINTING UP.
7. VERIFY METER LAY LENGTH WITH WATER DEPARTMENT PRIOR TO INSTALLING PIPING
8. PROVIDE ISOLATION VALVES AT METER INLET AND OUTLET
9. FOR MULTIPLE METERS PROVIDE A MANIFOLD WITH A MAIN VALVE PRIOR TO THE MANIFOLD AND
INDIVIDUAL VALVES LOCATED PRIOR TO AND AFTER METERS.
10. PROVIDE A FLOOR DRAIN IN THE FIRE RISER ROOM WITHIN 10 FEET OF THE WATER METER LOCATION.
11. PROVIDE PIPE LABELS ON THE POTABLE WATER LINE BETWEEN THE FIRE RISER AND THE WATER
METER DESIGNATING PIPE AS “POTABLE WATER”.
12. PROVIDE PIPE ANCHORAGE TO SUPPORT METER ASSEMBLY INDEPENDENT OF THE POTABLE WATER
SUPPLY PIPING AND BUILDING PLUMBING. PROVIDE PIPE STANDS OR UNISTRUT WALL STANDOFFS.
DO NOT SUPPORT METER ASSEMBLY FROM OTHER PIPING.
13. PROVIDE A WALL PENETRATION AND CONDUIT FOR REMOTE RADIOREAD METER TRANSEIVER UNIT
(MXU) DEVICE(S). COORDINATE ROUTING AND WALL PENETRATION LOCATION WITH THE WATER
DEPARTMENT. REFERENCE WATER STANDARD PLANS 520 AND 530.
14. PROVIDE 1/2” EMT CONDUIT AND SUPPORTS FOR MXU SIGNAL WIRE IF DISTANCE TO WALL
PENETRATION EXCEEDS 10 FEET.
15. INSPECTION: CONTACT THE CITY ENGINEER FOR INSPECTION OF THE POTABLE WATER SYSTEM
METER ASSEMBLY INSTALLATION.
16. REFER TO STD. PLAN 500 AND THE SPECIFICATIONS FOR FLUSHING, HYDROSTATIC TESTING, AND
DISINFECTING REQUIREMENTS
17. BUILDING OWNER IS RESPONSIBLE TO HAVE THE BACKFLOW PREVENTER FLOW TESTED AND
INSPECTED INTERNALLY AT LEAST ONCE PER YEAR, OR MORE AS CONDITIONS WARRANT, IN
ACCORDANCE WITH NFPA 13 AND NFPA 25 AND A REPORT SUBMITTED TO THE PARK CITY BUILDING
DEPARTMENT
PARK CITY MUNICIPAL CORPORATION
WATER
DATE
METER VAULT
FRAME AND COVER /
MXU DEVICE LOCATION
STD. PLAN
10/2020
529 S REV.
0
LEGEND AND APPROVED PARTS LIST
ITEM DESCRIPTION ACCEPTABLE
MANUFACTURER MODELS
① METER VAULT FRAME AND COVER, MARKED “WATER” D&L SUPPLY L-2320, OR APPROVED EQUAL
② METER VAULT FRAME AND COVER,
TRAFFIC RATED, MARKED “WATER” D&L SUPPLY A-1019, OR APPROVED EQUAL
③ 2” TAP AND PLUG, REQUIRED
FORD OR
APPROVED
EQUAL
PLUG: PTP-3-25
④ 2” TAP WITH RECESSED PLUG, REQUIRED
(PLAN VIEW ‘B’)
⑤NOTCH INNER FROST FREE LID FOR SIGNAL WIRE
(PLAN VIEW ‘A’)
⑥ MXU AND WIRING, SUPPLIED AND INSTALLED BY PCMC
⑦ METER VAULT, MATERIALS VARY
DETAIL NOTES
1. REFER TO STD. PLAN 592 AND 593 FOR METER VAULT ADJUSTMENT AND GRADING REQUIREMENTS
2. PROVIDE TAPS FOR STANDARD AND ALTERNATE MXU LOCATIONS
3. PROVIDE PLUGS FOR ALL OPENINGS
4. REMOVE ALL BURRS FROM TAPS AND NOTCHES
5. REFER TO STD PLAN 530 FOR REMOTE MXU REQUIREMENTS
PARK CITY MUNICIPAL CORPORATION
WATER
DATE
METALLIC PIPE
CORROSION PROTECTION
STD. PLAN
10/2020
534.1 REV.
0
PCMC WATER SYSTEM – CORROSION PROTECTION REQUIREMENTS:
PCMC HAS EXPERIENCED EXTERNAL CORROSION OF WATER DISTRIBUTION MATERIALS IN VARYING
DEGREES THROUGHOUT THE CITY. TO MAXIMIZE THE LIFE CYCLE OF WATER SYSTEM IMPROVEMENTS, AS
IMPACTED BY THE IMMEDIATE SITE CONDITIONS AND THE SELECTION OF MATERIALS, THE CITY HAS
IDENTIFIED KEY DESIGN AND CONSTRUCTION REQUIREMENTS.
1. FOR PROJECTS WITH LESS THAN 300 FEET OF NEW WATER PIPE AND APPURTENANCES,
CORROSION PROTECTION SHALL BE ADDRESSED IN THE FOLLOWING MANNER:
a. IN ADDITION TO THE REQUIRED POLYETHYLENE WRAP, APPLY A WAX TAPE COATING SYSTEM TO
VALVE BONNET BOLTS,SADDLES, CORP STOPS, STAINLESS REPAIR CLAMPS AND ALL OTHER
BURIED BOLTS, NUTS, CONNECTORS, RESTAINER GLAND BOLTS, AND COUPLING HARDWARE, AWWA
C217. COATING SYSTEM TO INCLUDE A 4-MIL MINIMUM WAX TAPE PRIMER, FILLER MATERIAL, 45-MIL
MINIMUM WAX TAPE AND PROTECTIVE OUTER WRAP. WHEN WAX TAPING A STAINLESS CLAMP THE
ENTIRE CLAM SHOULD BE WRAPPED NOT JUST BOLTS.
b. WAX TAPE COATING MATERIALS:
i. DENSO NORTH AMERICA DENSO PRIMER, DENSYL TAPE AND/OR MASTIC, DENSO FIBER-WRAP
ii. TRENTON PRIMER, #1 WAX-TAPE, AND GUARD-WRAP
iii. OR APPROVED EQUAL (SUBMITTAL TO CITY AND WRITTEN APPROVAL REQUIRED PRIOR TO
INSTALLATION)
2. FOR PROJECTS EXCEEDING 300 FEET OF NEW WATER PIPE AND APPURTENANCES, CORROSION
PROTECTION SHALL BE ADDRESSED IN THE FOLLOWING MANNER:
a. THE DEVELOPER AND ITS’ DESIGN ENGINEER, GEOTECHNICAL ENGINEER, AND CORROSION
CONSULTANT SHALL PROVIDE A SITE SPECIFIC “CORROSION STUDY REPORT”. THE REPORT SHALL
INCORPORATE PROJECT SPECIFIC FINDINGS INTO CORROSION PROTECTION RECOMMENDATIONS
FOR THE PROPOSED WATER SYSTEM IMPROVEMENTS. THE REPORT SHALL INCLUDE AT A MINIMUM
THE FOLLOWING ITEMS:
i. DETAILED INFORMATION ON EXISTING CONDITIONS, SOIL TYPES, CLASSIFICATION, ETC.
ii. IDENTIFICATION OF STRAY CURRENT SOURCES AND ANY EXISTING CORROSION PROTECTION
SYSTEMS IN THE IMMEDIATE AREA
iii. IDENTIFICATION OF ANY POTENTIAL FOR HOT SPOTS OR VARYING SOIL CONDITIONS THAT
MAY WARRANT CHANGES TO THE CORROSION PROTECTION PLAN DURING CONSTRUCTION.
iv. FIELD SAMPLING AND TESTING RESULTS WITHIN THE PROPOSED PIPE ZONE BASED ON
REPRESENTATIVE SAMPLING OF THE DEVELOPMENT AREA CONDITIONS
v. SOIL RESISTIVITY TESTING RESULTS IDENTIFYING CORROSIVE SOIL CONDITIONS AND
LOCATIONS (WENNER 4-PIN SOIL RESISTIVITY TESTS AND SOIL BOX RESISTIVITY TESTS) AT
REPRESENTATIVE PIPE INSTALL DEPTHS
vi. LABORATORY ANALYSIS OF SOIL SAMPLES FOR PH, CHLORIDES, SULFATES, TOTAL SALTS,
AND CONDUCTIVITY
vii. DETERMINATION OF THE NEED FOR CORROSION PROTECTION BASED ON SOIL CORROSIVITY
CLASSIFICATION/SOIL RESISTIVITY AND RECOMMENDATION OF SUITABLE PIPE,
CONSTRUCTION MATERIALS, PIPE PROTECTION METHOD, PIPE EXTERIOR COATINGS, ETC.,
BASED ON SITE CORROSIVITY. SEE TABLE BELOW.
viii. SPECIFY IF THE INVESTIGATION INCLUDES ONLY THE INITIAL PHASE OR ALL FUTURE PHASES
PARK CITY MUNICIPAL CORPORATION
WATER
DATE
METALLIC PIPE
CORROSION PROTECTION
STD. PLAN
10/2020
534.2 REV.
0
b. FOLLOWING PCMC’S RECEIPT AND REVIEW OF THE CORROSION STUDY REPORT, THE DEVELOPER
WILL BE NOTIFIED OF THE CITY’S DETERMINATION AS TO REQUIRED PROTECTION OR THE DESIGN
TEAM WILL BE REQUESTED TO MEET AND REVIEW THE FINDINGS AND ESTABLISH THE FINAL WATER
SYSTEM DESIGN CRITERIA. THE CITY’S REVIEW WILL BE BASED ON THE FOLLOWING TABLE 1:
TABLE 1 - SOIL CORROSIVITY CLASSIFICATION VERSUS SOIL RESISTIVITY
c. REFER TO PERTINENT PCMC WATER STANDARD PLANS OR PROVIDE CONSTRUCTION DRAWING
DETAILS ASSOCIATED WITH CORROSION STUDY RECOMMENDATIONS AND THE PCMC FINAL
APPROVED WATER SYSTEM
WAX TAPE INSTALLATION PROCEDURES
WIRE BRUSH AND SCRAPE THE SURFACE CLEAN OF DIRT, LOOSE COATING AND LOOSE RUST. APPLY A
THIN FILM OF WAX-TAPE® PRIMER. IF THE SURFACE IS WET, COLD OR RUSTY, RUB AND PRESS ON
PRIMER TO DISPLACE MOISTURE AND ENSURE ADHESION. THEN WRAP WAX-TAPE WRAP USING A 1″
OVERLAP. ON STRAIGHT PIPE APPLY SLIGHT TENSION TO ENSURE CONTACT WITH SURFACE. ON
IRREGULAR SURFACES ALLOW SLACK SO THE WRAP CAN BE MOLDED INTO CONFORMITY. IN EITHER
CASE, PRESS AND FORM THE WRAP SO THERE ARE NO AIR POCKETS OR VOIDS UNDER THE WRAP.
ALSO, PRESS AND SMOOTH OUT THE LAP SEAMS TO ENSURE THEY ARE SEALED AND APPLY
OUTERWRAP. THE WRAP DOES NOT REQUIRE CURING OR DRYING TIME SO IT CAN BE BACKFILLED
IMMEDIATELY.
CORROSIVITY RESISTIVITY, OHM-CM TREATMENT
EXTREMELY CORROSIVE LESS THAN 1,000 SITE SPECIFIC DESIGN REQUIRED
VERY CORROSIVE 1,000 TO 3,000 SITE SPECIFIC DESIGN REQUIRED
CORROSIVE 3,000 TO 6,000 NON-METALLIC PIPE – WAX TAPE COATING SYSTEM ON BOLTS
& NUTS, ANODE PROTECTED FITTINGS AND VALVES
MODERATELY CORROSIVE 6,000 TO 10,000 NON-METALLIC PIPE - WAX TAPE COATING SYSTEM ON BOLTS
AND NUTS ON PIPE, FITTINGS, AND VALVES
MILDLY CORROSIVE MORE THAN 10,000
WAX TAPE COATING SYSTEM ON BOLTS AND NUTS ON PIPE,
FITTINGS, AND VALVES
*ALWAYS REQUIRED UNLESS SOILS TESTING IS PROVIDED
PARK CITY MUNICIPAL CORPORATION
WATER
DATE
WATER MAIN AND FIRE LINES
STD. PLAN
4/2014
540 S REV.
0
LEGEND AND APPROVED PARTS LIST
ITEM DESCRIPTION ACCEPTABLE
MANUFACTURER MODELS
①
DUCTILE IRON PIPE, 3” TO 12” DIAMETER, PRESSURE
CLASS 350, CEMENT-MORTAR LINING, ASPHALTIC
INTERIOR/EXTERIOR COATING, AWWA C150 / C151 /
C104
U.S. PIPE (1)
PACIFIC STATES
STANDARD JOINT PIPE: PUSH ON
TYTON JOINT
U.S. PIPE (1)
PACIFIC STATES
RESTRAINED JOINT PIPE:
THRUST-LOCK
TR FLEX
② POLYVINYL CHLORIDE (PVC) PIPE, C.I.O.D., C900, DR
18, INTEGRAL BELL JOINT JM EAGLE (1) STANDARD JOINT PIPE:
BLUE BRUTE
③
DUCTILE IRON FITTINGS, 3” TO 12” DIAMETER, FULL
BODY, PRESSURE CLASS 350, CEMENT MORTAR
LINED, ASPHALTIC EXTERIOR COATING, AWWA C153 /
C104
FLANGES: AWWA C110 / C115, CLASS 125 FLANGE
WITH FULL FACE OR RING FLANGE-TYTE GASKETS
U.S. PIPE (1)
PACIFIC STATES
PUSH ON STYLE FITTING:
TYTON JOINT
FLANGED FITTING:
U.S. PIPE (1)
PACIFIC STATES
RESTRAINED JOINT PIPE:
THRUST-LOCK
TR FLEX
④
FITTINGS – DUCTILE IRON MECHANICAL JOINT PIPE
WITH RETAINER GLANDS OR SST TIE ROD / NUT
RESTRAINTS, AWWA C110 / C111 / C104
EBBA IRON (1)
FITTINGS: MECHANICAL JOINT
RETAINER GLANDS:
MEGALUG SERIES 1100, STD T-
BOLTS AND NUTS
⑤ POLYETHYLENE ENCASEMENT, HIGH DENSITY CROSS
LAMINATED (HDCL) POLYETHYLENE FILM, AWWA C105
& AWWA C703E METHODS A & C
CHRISTY’S (1)
AWWA C703E METHOD A (4 MIL) AT
PIPE AND AWWA C703E METHOD C
(10 MIL) AT BOLT-TYPE JOINTS,
FITTINGS, AND VALVES
⑥DETECTABLE UNDERGROUND WARNING TAPE, 5-MIL
MINIMUM, ALUMINUM BACKING, BLUE BACKGROUND,
6” WIDE
SETON (1) 85525
⑦
TRACER WIRE: 12 GA. SOLID, BLUE PVC INSULATION;
WIRE-WIRE CONNECTORS SILICONE-FILLED WIRE
NUTS
CONNECTORS:
IDEAL
INDUSTRIES (1)
TWISTER DB PLUS OR APP’D
EQUAL
⑧
WAX TAPE COATING SYSTEM, APPLY TO ALL BURIED
BOLTS AND NUTS INCLUDING MECHANICAL JOINT
RESTRAINT SYSTEMS, AWWA C 217. REFER TO STD.
PLAN 534.
DETAIL NOTES
1. COORDINATE PIPE SIZE WITH APPROVED PLANS PRIOR TO ORDERING MATERIALS
2. LOCATE MAIN, FITTINGS, VALVES, AND FIRE LINES PER APPROVED PLANS
3. DUCTILE IRON PIPE IS REQUIRED WHEN WATER SYSTEM DESIGN PRESSURE EXCEEDS 150
PRESSURE RATING
4. PROVIDE “DOMESTIC” DUCTILE IRON FITTINGS
5. PROVIDE DUCTILE IRON RESTRAINED JOINT PIPE ON FIRE LINES, HYDRANT LINES, AND WHERE
REQUIRED ON THE APPROVED PLANS
6. PROVIDE 316 STAINLESS STEEL BOLTS AND NUTS WITH ANTI-SEIZE LUBRICATION ON ALL FLANGED
CONNECTIONS
7. REFER TO STANDARD PLAN 534 FOR SUPPLEMENTAL EXTERNAL CORROSION PROTECTION
REQUIREMENTS. WHEN CATHODIC PROTECTION IS REQUIRED REFER TO STD. PLANS 534-538.
8. REFER TO SPECIFICATIONS FOR FLUSHING, HYDROSTATIC TESTING, AND DISINFECTING
REQUIREMENTS
9. (1) DENOTES “OR EQUAL” MANUFACTURER AND MODEL. SUBMIT IN ACCORDANCE WITH CITY
STANDARDS
PARK CITY MUNICIPAL CORPORATION
WATER
DATE
WATER SERVICE LINE
3/4” TO 2” METERS
STD. PLAN
10/2020
541 S REV.
LEGEND AND APPROVED PARTS LIST
ITEM DESCRIPTION ACCEPTABLE
MANUFACTURER MODELS
① BRONZE SERVICE SADDLE:
DI & AC PIPE; DOUBLE STRAP
PVC PIPE; TWO-PIECE BOLTED
MUELLER
DI & AC PIPE: BR2B SERIES,
1-1/2” SERVICE, CC THDS;
2” SERVICE FIP THDS
PVC PIPE: H-13000 SERIES,
1-1/2” SERVICE, CC THDS;
2” SERVICE FIP THDS
FORD
DI & AC PIPE: STYLE 202B
1-1/2” SERVICE, CC THDS;
2” SERVICE, FIP THDS
PVC PIPE:
1-1/2” SERVICE, STYLE S902, CC
THDS;
2” SERVICE, STYLE S912, FIP THDS
② BRASS CORPORATION STOP, INLET IP THREAD,
OUTLET CTS COMPRESSION
MUELLER B-25008N
FORD FB1100-(SERVICE SIZE)-Q-NL
③
POLYETHYLENE ENCASEMENT, HIGH DENSITY CROSS
LAMINATED (HDCL) POLYETHYLENE FILM, AWWA C105
& AWWA C703E METHOD C
CHRISTY’S OR
APPROVED
EQUAL
AWWA C703E METHOD C
(4 MIL)
④ DETECTABLE UNDERGROUND WARNING TAPE, 5-MIL
MINIMUM, ALUMINUM BACKING BLUE BACKGROUND,
6” WIDE
SETON OR
APPV’D EQUAL 85525
⑤
WATER SERVICE LINE: HIGH-DENSITY POLYETHYLENE
TUBING (CTS), BLUE, SDR 9, AWWA C901
1-1/2" DIA. SERVICE: 3/4" AND 1” SINGLE METER
1-1/2" DIA. SERVICE: 3/4” AND 1” DUAL METERS
2" DIA. SERVICE: 1-1/2” AND 2” SINGLE METER
2" DIA. SERVICE: 1-1/2” DUAL METERS
ADS OR APPV’D
EQUAL
⑥
WATER SERVICE LINE: HIGH-DENSITY POLYETHYLENE
TUBING (CTS), BLUE, SDR 9, AWWA C901; OR,
TYPE K COPPER, SOFT, AWWA C800
ADS OR APPV’D
EQUAL
⑦ TRACER WIRE: 12 GA. SOLID, BLUE PVC INSULATION;
WIRE-WIRE CONNECTORS SILICONE-FILLED WIRE
NUTS
IDEAL
INDUSTRIES
TWISTER DB PLUS OR APP’D
EQUAL
DETAIL NOTES
1. COORDINATE SERVICE SIZE WITH CITY PRIOR TO ORDERING MATERIALS
2. LOCATE SERVICE PER APPROVED PLANS
3. NO SERVICE LINE FITTINGS ALLOWED BETWEEN CORPORATION STOP AND METER VAULT CURB STOP
VALVE
4. APPLY WAX TAPE COATING SYSTEM TO SERVICE SADDLE BOLTS AND NUTS, AWWA C217. SYSTEM TO
INCLUDE FILLER MATERIAL, TAPE COATING, AND PROTECTIVE OUTERWRAP. DENSO NORTH AMERICA,
TRENTON, OR APPROVED EQUAL (STD. PLAN 534)
METHOD A
METHOD B
TABLE OF DIMENSIONS
OBSTRUCTION
SEWER
MAIN
STORM
DRAIN OR
CULVERT
OTHER
'a'18"SEE STD.
PLAN 546
12" MIN
'b'5'-0"3'-0" MIN
5' MIN (7' MIN ABOVE ELEV 7,300')
'a
'
FINISH GRADE
'b'
SERVICE LINE
SERVICE LINE
FINISH GRADE
'a
'
OBSTRUCTION
OBSTRUCTION
'b'
NOTES:
1.ALL CULINARY WATER MAINS AND LATERALS
SHALL BE INSTALLED ABOVE SEWER LINES
UNLESS APPROVED BY PARK CITY AND UTAH
DIVISION OF DRINKING WATER.
STD. PLANDATE
REV.
WATER
PARK CITY MUNICIPAL CORPORATION 543WATER SERVICE LINE LOOP
TABLE OF DIMENSIONS
OBSTRUCTION 'a''b'
SEWER 18" MIN 20' MIN
STORM DRAIN
OR CULVERT
SEE STD.
PLAN 546 O.D. + 6'
OTHER 12" MIN O.D. + 4'
METHOD A
SUPPLY AND INSTALL
LOCKING FOLLOWERS (TYP)
OBSTRUCTION
RESTRAINED SLEEVE
OR COUPLINGS (TYP)
WATER
MAIN (TYP)
THRUST BLOCKS AND
RESTRAINTS (STD.
PLAN 561 AND 562)
'b'
'a
'
24" MIN
NOTES:
1.RESTRAINED JOINT PIPE REQUIRED
2.ALL CULINARY WATER MAINS AND LATERALS
SHALL BE INSTALLED ABOVE SEWER LINES
UNLESS APPROVED BY PARK CITY AND UTAH
DIVISION OF DRINKING WATER.
STD. PLANDATE
REV.
WATER
PARK CITY MUNICIPAL CORPORATION 544-AWATER MAIN LOOP
TABLE OF DIMENSIONS
OBSTRUCTION 'a''b'
SEWER 18" MIN 20' MIN
STORM DRAIN
OR CULVERT
SEE STD.
PLAN 546 O.D. + 6'
OTHER 12" MIN O.D. + 4'
METHOD B
TABLE OF DIMENSIONS
OBSTRUCTION 'a'
SEWER 18" MIN
STORM DRAIN
OR CULVERT
SEE STD. PLAN
546
OTHER 12" MIN
METHOD C
WATER
MAIN (TYP)
RESTRAINED SLEEVE
OR COUPLINGS (TYP)
OBSTRUCTION
SUPPLY AND INSTALL
LOCKING FOLLOWERS (TYP)
THRUST BLOCKS AND
RESTRAINTS (STD.
PLAN 561 AND 562)
'b'
'a
'
24" MIN
WATER MAIN
OBSTRUCTION
TO WATER MAIN OR
APPURTENANCE
'a
'
THRUST BLOCKS AND
RESTRAINTS (STD.
PLAN 561 AND 562)
WATER MAIN
SUPPLY AND INSTALL
LOCKING FOLLOWERS (TYP)
NOTES:
1.RESTRAINED JOINT PIPE
REQUIRED
2.ALL CULINARY WATER MAINS
AND LATERALS SHALL BE
INSTALLED ABOVE SEWER
LINES UNLESS APPROVED BY
PARK CITY AND UTAH
DIVISION OF DRINKING
WATER.
STD. PLANDATE
REV.
WATER
PARK CITY MUNICIPAL CORPORATION 544-BWATER MAIN LOOP
NOTES:
HDPE PIPE WATERLINE LOOP MINIMUM REQUIREMENTS:
1.GENERAL: PIPE SHALL BE HDPE 4710 DR11 WITH AN INSIDE DIAMETER EQUAL TO OR GREATER THAN
THE CONNECTING PIPE ON BOTH ENDS.
2.PIPE SHALL BE FUSION WELDED ALONG LENGTH AND FULLY RESTRAINED AT TRANSITIONS TO
DIFFERING PIPE MATERIALS WITH FLANGES OR OTHER CITY APPROVED METHOD.
3.FITTINGS ALONG THE LOOP LENGTH SHALL BE HDPE UNLESS OTHERWISE APPROVED BY OWNER.
4.BENDING RADIUS NOT TO EXCEED PIPE MANUFACTURES RECOMMENDATIONS.
5.REDUCERS AND TRANSITION COUPLINGS SHALL BE PROVIDED ON BOTH ENDS AS REQUIRED AND
SHALL BE HDPE OR DUCTILE IRON. CATHODIC PROTECTION REQUIRED ON FERROUS COMPONENTS
PER STD. PLAN 534
6.ALL CULINARY WATER MAINS AND LATERALS SHALL BE INSTALLED ABOVE SEWER LINES UNLESS
APPROVED BY PARK CITY AND UTAH DIVISION OF DRINKING WATER.
TABLE OF DIMENSIONS
OBSTRUCTION 'a''b'
SEWER 18" MIN 20' MIN
STORM DRAIN
OR CULVERT
SEE STD.
PLAN 546 O.D. + 6'
OTHER 12" MIN O.D. + 4'
HDPE METHOD
3 SEGMENT HDPE BENDS
AS REQUIRED (TYP)
OBSTRUCTION
RESTRAINED SLEEVE
OR COUPLINGS (TYP)
WATER
MAIN (TYP)
'b'
'a
'
FLANGED COUPLING
ADAPTER W/ BACK
UP RING (TYP)
STD. PLANDATE
REV.
WATER
PARK CITY MUNICIPAL CORPORATION 544-CWATER MAIN LOOP
ZONE 1 ZONE 2 ZONE 3
10'
6'
WA
T
E
R
L
I
N
E
SA
N
I
T
A
R
Y
S
E
W
E
R
L
I
N
E
HORIZONTAL SEPARATION REQUIREMENTS
18
"
18
"
ZO
N
E
2
ZO
N
E
3
ZO
N
E
4
ZO
N
E
1
WATERLINE
WATERLINE
SANITARY
SEWER LINE
VERTICAL SEPARATION REQUIREMENTS
NOTES:
1.SEE STD. PLAN 547-B FOR HORIZONTAL AND VERTICAL SEPARATION REQUIREMENT NOTES.
2.ALL CULINARY WATER MAINS AND LATERALS SHALL BE INSTALLED ABOVE SEWER LINES UNLESS
APPROVED BY PARK CITY AND UTAH DIVISION OF DRINKING WATER.
STD. PLANDATE
REV.
WATER
PARK CITY MUNICIPAL CORPORATION 547-A
WATER - SANITARY SEWER
SEPARATION
HORIZONTAL SEPARATION
NOTES:
1.ZONE 1:WATER LINE AND SEWER LINE SEPARATED 10 FEET OR GREATER - NO SPECIAL
REQUIREMENTS
ZONE 2:A) WATER LINE SEPARATED BY AT LEAST 6 FEET AT OUTSIDE PIPE WALLS
AND
B) BOTTOM OF WATER LINE IS AT LEAST 18 INCHES ABOVE TOP OF SEWER LINE
AND
C) WATER LINE CONSTRUCTED WITH MECHANICAL, RESTRAINED JOINT PIPE
AND
SITE SPECIFIC REQUIREMENTS APPROVED BY DIVISION OF ENVIRONMENTAL QUALITY,
DIVISION OF DRINKING WATER
ZONE 3:WATER LINE AND SEWER LINE SEPARATION LESS THAN 6 FEET - NOT ALLOWED
2.SERVICE LINE TAPS NOT ALLOWED IN ZONE 2.
3.SERVICE LINE TAPS WITHIN ZONE 3 ALLOWED ONLY BY SITE SPECIFIC APPROVAL BY DIVISION OF
ENVIRONMENTAL QUALITY, DIVISION OF DRINKING WATER
4.MAINTAIN 10 FEET HORIZONTAL SEPARATION AND 18 INCHES VERTICAL SEPARATION ABOVE SANITARY
SEWER FORCE MAINS
5.CONSULT SNYDERVILLE BASIN WATER RECLAMATION DISTRICT FOR SANITARY SEWER REQUIREMENTS
AND SEWER LINE MODIFICATIONS
VERTICAL SEPARATION
NOTES:
1.ZONE 1:WATER LINE ABOVE SEWER LINE AND SEPARATED 18 INCHES OR GREATER - NO SPECIAL
REQUIREMENTS
ZONE 2:WATER LINE ABOVE SEWER LINE SEPARATED LESS THAT 18 INCHES - LOOP WATER LINE,
REFER TO STD. PLAN 543. INSTALL CONTROLLED LOW-STRENGTH MATERIAL (CLSM),
“FLOWABLE FILL”, 150 PSI MAXIMUM MIX DESIGN WITHIN WATER PIPE ZONE AND TO 18
INCHES ABOVE SEWER LINE
ZONE 3:WATER LINE BELOW SEWER LINE SEPARATED LESS THAN 18 INCHES - LOOP WATER LINE,
REFER TO STD. PLAN 543. INSTALL CONTROLLED LOW-STRENGTH MATERIAL (CLSM),
“FLOWABLE FILL”, 150 PSI MAXIMUM MIX DESIGN WITHIN WATER PIPE ZONE AND TO 18
INCHES ABOVE SEWER LINE
ZONE 4:WATER LINE BELOW SEWER LINE SEPARATED GREATER THAN 18 INCHES - CENTER ONE FULL
UNCUT LENGTH OF WATER PIPE OVER THE CROSSING AND PROVIDE MECHANICAL
RESTRAINED PIPE JOINTS UNTIL THE WATER PIPE EXTENDS TO A DISTANCE OF 10 FEET
PERPENDICULAR TO EACH SIDE OF THE SEWER LINE. INSTALL CONTROLLED
LOW-STRENGTH MATERIAL (CLSM), “FLOWABLE FILL”, 150 PSI MAXIMUM MIX DESIGN WITHIN
WATER PIPE ZONE AND TO 18 INCHES ABOVE SEWER LINE
2.SERVICE LINE TAPS NOT ALLOWED IN ZONES 2 AND 3.
3.MAINTAIN 10 FEET HORIZONTAL SEPARATION AND 18 INCHES VERTICAL SEPARATION ABOVE SANITARY
SEWER FORCE MAINS
4.CONSULT SNYDERVILLE BASIN WATER RECLAMATION DISTRICT FOR SANITARY SEWER REQUIREMENTS
AND SEWER LINE MODIFICATIONS
5.ALL CULINARY WATER MAINS AND LATERALS SHALL BE INSTALLED ABOVE SEWER LINES UNLESS
APPROVED BY PARK CITY AND UTAH DIVISION OF DRINKING WATER.
STD. PLANDATE
REV.
WATER
PARK CITY MUNICIPAL CORPORATION 547-B
WATER - SANITARY SEWER
SEPARATION
PARK CITY MUNICIPAL CORPORATION WATER
DATE
BURIED VALVE AND
VALVE BOX
STD. PLAN
4/2014
570 S REV.
LEGEND AND APPROVED PARTS LIST
ITEM DESCRIPTION ACCEPTABLE
MANUFACTURER MODELS
① BUTTERFLY VALVE, NRS, AWWA C504 CLASS 250B,
250 PSI, SST BONNET BOLTS, FLANGED END
CONNECTIONS
MUELLER LINESEAL XPII, 5227 SERIES
CLOW MODEL 4500
②
GATE VALVE, NRS, AWWA C509, 250 PSI, SST BONNET
BOLTS, END CONNECTIONS PER FOLLOWING:
ON TEES: FLG x FLG
IN-LINE VALVES: MJ x MJ
OTHERS: MJ x MJ, OR PER DESIGN
MUELLER SERIES 2360
CLOW MODEL 2639
③ POLYETHYLENE ENCASEMENT, HIGH DENSITY CROSS
LAMINATED (HDCL) POLYETHYLENE FILM, AWWA C105
& AWWA C703E METHOD C
CHRISTY’S OR
APPROVED
EQUAL
AWWA C703E METHOD C
(4 MIL)
④
VALVE BOX, CAST IRON, TWO PIECE, SLIP TYPE WITH
CAST IRON DROP-IN COVER MARKED AS FOLLOWS:
ISOLATION VALVE: “WATER”
BUTTERFLY VALVE: “BFV”
ZONE VALVE: “ZONE”
FIRE LINE VALVE: “FIRE”
VALVE BOX RISER: LIMIT ONE PER VALVE BOX
D&L SUPPLY OR
APPV’D EQUAL
BOX AND LID: M-8042
RISER: M-8049 THRU M-8055
EXTENSION: M-8070
DETAIL NOTES
1. VALVES TO BE RATED FOR WORKING AND TEST PRESSURE OF WATER MAIN
2. PROVIDE FUSION BONDED EPOXY COATING ON GATE VALVE AND BUTTERFLY VALVE INTERIOR AND
EXTERIOR
3. PROVIDE 316 SST BOLTS AND NUTS WITH ANTI-SEIZE LUBRICANT ON FLANGED CONNECTIONS
4. DO NOT LOCATE VALVE AND VALVE BOX WITHIN CURB OR GUTTER
5. CENTER VALVE BOX ON VALVE OPERATING NUT
6. SET VALVE BOX PLUMB WITHOUT DEFLECTIONS IN VALVE BOX JOINTS
7. PROVIDE ADDITIONAL SLIP BASE FOR VALVE BOX ON 7’ BURY WATER MAIN
8. APPLY WAX TAPE COATING SYSTEM TO VALVE BONNET BOLTS AND ALL OTHER BURIED BOLTS AND
NUTS, AWWA C217. SYSTEM TO INCLUDE FILLER MATERIAL, TAPE COATING, AND PROTECTIVE
OUTERWRAP. DENSO NORTH AMERICA, TRENTON, OR APPROVED EQUAL (STD. PLAN 534)
LO
W
P
R
E
S
S
U
R
E
(1
5
0
P
S
I
)
HI
G
H
P
R
E
S
S
U
R
E
(2
5
0
P
S
I
)
BA
S
I
C
V
A
U
L
T
-
P
L
A
N
V
I
E
W
NT
S
NO
T
E
:
1.
FO
R
G
E
N
E
R
A
L
N
O
T
E
S
,
S
E
E
S
T
D
.
P
L
A
N
5
7
3
-
A
,
A
N
D
F
O
R
K
E
Y
E
D
I
T
E
M
S
,
SE
E
S
T
A
N
D
A
R
D
P
L
A
N
5
7
3
-
C
.
3
A
N
D
C
.
4
.
2.
SE
E
P
R
O
J
E
C
T
S
I
T
E
P
L
A
N
F
O
R
A
C
T
U
A
L
L
O
C
A
T
I
O
N
O
F
V
E
N
T
S
T
A
N
D
P
I
P
E
S
,
HA
T
C
H
,
S
U
M
P
,
A
N
D
H
I
G
H
/
L
O
W
P
R
E
S
S
U
R
E
S
I
D
E
S
.
1
57
3
-
D
.
1
AI
R
V
E
N
T
ST
A
N
D
P
I
P
E
AI
R
V
E
N
T
ST
A
N
D
P
I
P
E
FO
R
A
I
R
RE
L
E
A
S
E
VA
L
V
E
S
,
S
E
E
ST
D
.
P
L
A
N
5
7
6
FO
R
D
E
T
A
I
L
S
21 18
5
4
23
17 22
17
'
-
6
"
2'
X
2
'
S
U
M
P
29
SL
O
P
E
T
R
E
N
C
H
T
O
DR
A
I
N
(
1
%
M
I
N
)
8'-0"
2'-8"
3'-6"1'-0"3'-6"
B
57
3
-
C
.
2
1
57
3
-
D
.
1
AI
R
V
E
N
T
ST
A
N
D
P
I
P
E
45
18 24
1'
-
6
"
(T
Y
P
)
6"
(T
Y
P
)
24
20
3
32
11 7
320
1%
S
L
O
P
E
16
26
13
14
12
15
10
6 8
9
1%SL
O
P
E
7
17
10
15
13
1%
S
L
O
P
E
573-C.1
#
STD. PLANDATE
REV.
WATER
PARK CITY MUNICIPAL CORPORATION
PRESSURE REDUCING
VALVE VAULT
33
34
MATERIAL LIST
ITEM PRESSURE REDUCING VALVE VAULT
6" CLA-VAL X 43 H (H STYLE STRAINER), FLANGED ENDS, 10 MESH SCREEN, CAGE SUPPORT, AND
O-RING
6" RESILIENT SEAT VALVE, FL X FL W/HAND WHEEL AND POSITION INDICATOR
6" PRESSURE REDUCING VALVE, CLA-VAL MODEL 92-01, STRAINERS, FLOW CONTROL SHUT OFF
COCKS, FLOW STABILIZER, STAINLESS STEEL TRIM, FLANGE X FLANGE, PRESSURE SUSTAINING
VALVE IS REQUIRED UNLESS NOTED OTHERWISE)
6" DISMANTLING JOINT, ROMAC DJ 400, OR EQUAL.
1" COMBINATION AIR VALVE WITH BALL VALVE ISOLATION, CLA-VAL MODEL 361-CAV564.3 OR
EQUAL. VENT ABOVE GRADE. OBTAIN OWNER APPROVAL FOR
VENT PIPE ROUTING. SEE STD. PLAN 576 FOR DETAILS (SIMILAR).
6" X 6" X 2" DI TEE FL X FL X IP THREAD WITH TAP FOR PRESSURE GAUGE (ITEM 17), AND HOSE
BIBBS (ITEM 22), AND AIR VALVE (ITEM 10)
2" BRASS OR RIGID COPPER PIPE, SCHEDULE 40, THREADED, TYPICAL
2" BRONZE 90° ELBOW, THREADED
2" BRONZE UNION COUPLING, THREADED
2" THREADED BRONZE BALL VALVE WITH HANDLE, 300 PSI, MUELLER 300
2" LIQUID FILLED PRESSURE GAUGE, GRADE B, UPSTREAM (0-300 PSI) DOWNSTREAM (0-200 PSI),
THREADED, WITH STEM VALVE - SEE STD. PLAN 573-D.1
8" MJ SOLID SLEEVE, MEGA-LUG RESTRAINTS WITH COR-TEN TEE BOLTS
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
STD. PLANDATE
REV.
WATER
PARK CITY MUNICIPAL CORPORATION 573-C.3
PRESSURE REDUCING
VALVE VAULT
MATERIAL LIST (CON'T)
ITEM PRESSURE REDUCING VALVE VAULT
2" STEEL PIPE SUPPORT STAND, ADJUSTABLE (2 REQUIRED ON 6" PIPE SYSTEM, 2 REQUIRED ON
2" PIPE SYSTEM), SEE STD. PLAN 578
CORE DRILL OPENING WITH LINK-SEAL PIPE-TO-WALL SEAL. TYPICAL ON ALL OPENING. FILL
OUTSIDE OPENINGS WITH NON-SHRINK GROUT AND CAULK
DRAIN SUMP, PIPE TO DAYLIGHT WITH DRAIN PIPE AND #4 SST RODENT PROTECTION SCREEN
ON END OF PIPE. ROUTE AS SHOWN ON SITE PLAN. IF NO PIPE-TO-DAYLIGHT OPTION IS
AVAILABLE, INSTALL A SUMP PUMP. SEE STD. PLAN 573-D.2
3/4" HOSE BIBBS, I.P. THREAD - SEE STD. PLAN 573-D.1
VAULT IN ACCORDANCE WITH 573-A AND 573-B
A. PRECAST CONCRETE VAULT RATED FOR HS-20 LOADING. MAY BE CAST IN PLACE PER CITY
APPROVAL. PROVIDE STAMPED STRUCTURAL DRAWINGS
B. WATERPROOF OUTSIDE WALLS AND TOP SLAB PER IBC CODE FOR BURIED FOUNDATIONS
MECHANICAL JOINT DUCTILE IRON RETAINER GLAND WITH CONCRETE THRUST BLOCK,
REINFORCE CONCRETE WITH (4) #4 EACH SIDE OF PIPE.
6"X6"X3" DI TEE FLANGE X FLANGE X FLANGE
2" CLA-VAC X 43H (H STYLE STRAINER), FLANGED ENDS, 10 MESH SST SCREEN, CAGE SUPPORT,
AND O-RING
3" PRESSURE RELIEF VALVE, CLA-VAL MODEL 50A-01 BKCX WITH MOUNTED LIMIT SWITCH OR
MICRO SWITCH WITH SCADA CONNECT FOR "OPEN" ALARM CONDITION, SEE STD. PLAN 573-D.2
IN-LINE GAUGE PRESSURE TRANSMITTER, ROSEMOUNT MODEL 3051TG 800 PSI ASSEMBLED TO
INTEGRAL, 2-VALVE, ROSEMOUNT 306 MANIFOLD. SEE STD. PLAN 573-D.1. 4-20 MA ANALOG
FRP GRATING, 1-1/2" THICK MIN. AND RATED FOR 300 LB/FT PEDESTRIAN TRAFFIC. INSIDE
TRENCH WIDTH TO BE 8" MINIMUM, AND 2-1/2" DEEP.
VAULT LADDER, SEE DETAIL 7 ON 573-D.4
SUMP PUMP: 2" SUMP PUMP, TSURUMI MODEL HSZ2.4S-62 OR EQUAL. SUMP PUMP REQUIRED IF
DRAIN TO DAYLIGHT NOT AVAILABLE, SEE STD. PLAN 573-D.2
6" DI PIPE. IF VAULT HAS POWER, THIS ITEM SHALL BE REPLACED WITH ITEMS 25 AND 27.
19
20
21
22
23
24
25
26
27
28
29
30
31
32
STD. PLANDATE
REV.
WATER
PARK CITY MUNICIPAL CORPORATION 573-C.4
PRESSURE REDUCING
VALVE VAULT
6" MAG METER. 33
2" MAG METER. 34
PARK CITY MUNICIPAL CORPORATION
WATER
DATE
AIR RELEASE / CAV MANHOLE
STD. PLAN
10/2020
574 S REV.
LEGEND AND APPROVED PARTS LIST
ITEM DESCRIPTION ACCEPTABLE
MANUFACTURER MODELS
① 5’ DIA. MANHOLE, PRECAST CONCRETE ECCENTRIC
CONE AND WALL SECTIONS ASTM C 478
② MANHOLE FRAME AND COVER (STD. PLAN 529)
③ POLYPROPYLENE ENCASED GRADE 60 STEEL STEPS AT
13” C-C, 13-1/2” TREAD WIDTH
M.A. INDUSTRIES
OR APP’D EQUAL PS2-PFDF
④
VALVE LARGER THAN 2”: DUCTILE IRON FLANGED TEE
WITH 4” BLIND FLANGE BRONZE AND NPT SERVICE TAP
VALVE 2” AND SMALLER: BRONZE SERVICE SADDLE
DI MAIN; DOUBLE STRAP
PVC MAIN; TWO-PIECE BOLTED
MUELLER
DI PIPE SADDLE: BR2B
SERIES, I.P. THDS;
PVC PIPE SADDLE: H-13000
SERIES, I.P. THDS
FORD
DI PIPE SADDLE: STYLE 202B
I.P. THDS;
PVC PIPE SADDLE:
STYLE S92, I.P. THDS
⑤ BRASS CORPORATION STOP, INLET I.P. THREAD, OUTLET
F.I.P. THREAD (VALVE INLET SIZE)
MUELLER B-20046N
FORD FB1100-(SERVICE SIZE)-Q-NL
⑥ BRONZE ANGLE VALVE, 300 PSI (VALVE INLET DIAMETER)
⑦BRASS NIPPLES X LENGTH AS REQUIRED, M.I.P., (VALVE
INLET DIAMETER)
⑧ BRASS 900 ELBOW, F.I.P. (VALVE INLET/OUTLET
DIAMETER)
⑨ COMBINATION AIR VACUUM / RELEASE VALVE, NPT, SIZE
PER ENGINEER DESIGN AND APPROVED PLANS
⑩ BRONZE TEE, F.I.P., THREADED, (VALVE OUTLET
DIAMETER X 3/4" DIA.)
⑪ DRAIN ASSEMBLY: 3/4” DIA. BRASS CLOSE NIPPLE, M.I.P.;
3/4" BRONZE BALL VALVE; 3/4" BRONZE PLUG MUELLER SERIES 300 VALVE; H-10035
⑫ BRONZE UNION, (VALVE OUTLET DIAMETER)
⑬ CAV ASSEMBLY SUPPORT, (1) 16”X8”X8” CMU BLOCK
⑭ 5/8” DIAMETER GALVANIZED STEEL ROD WITH 3”
DIAMETER HAND WHEEL TO FORM EXTENSION,
TOGETHER WITH A GALVANIZED EYELET STANDOFF
⑮ LIFTING EYE ABOVE AIR VALVE, GALVANIZED
⑯ TRACER WIRE: 12 GA. SOLID, BLUE PVC INSULATION;
WIRE-WIRE CONNECTORS SILICONE-FILLED WIRE NUTS IDEAL INDUSTRIES
TWISTER DB PLUS OR APP’D
EQUAL
DETAIL NOTES
1. ALL VALVES AND FITTINGS SHALL BE RATED FOR THE SAME WORKING AND TEST PRESSURES AS THE
CONNECTED WATERLINE
2. LOCATE VALVE, VAULT, AND AIR VENT PER APPROVED PLANS AND SET VAULT PLUMB
3. REFER TO STD. PLAN 575 FOR HEAT TRACE REQUIREMENTS
6"
MI
N
TRACER WIRE
(STD. PLAN 540, 541 AND 542)
WARNING TAPE,
12" ABOVE TOP OF PIPE
(STD. PLAN 540, 541 AND 542)
ENGINEER DIRECTED STABILIZATION
ROCK AS REQUIRED. ENCASE
DRAIN ROCK IN NON-WOVEN
GEOTEXTILE MATERIAL
PI
P
E
Z
O
N
E
SE
E
N
O
T
E
2
PI
P
E
B
E
D
D
I
N
G
SE
E
N
O
T
E
3
VA
R
I
E
S
TR
E
N
C
H
Z
O
N
E
,
SE
E
N
O
T
E
1
5'
M
I
N
(
7
'
M
I
N
A
B
O
V
E
E
L
E
V
7
3
0
0
'
)
,
10
'
M
A
X
12
"
MI
N
NOTES:
1.TRENCH ZONE
WATER MAIN, FIRE LINE, AND APPURTENANCES:
BACKFILL AND COMPACT PER PCMC DESIGN STANDARDS AND CONSTRUCTION SPECIFICATIONS UNLESS OTHERWISE REQUIRED
BY SPECIAL CONDITIONS
WATER SERVICE - NEW PAVEMENT AND LANDSCAPE AREA:
BACKFILL AND COMPACT PER PCMC DESIGN STANDARDS AND CONSTRUCTION SPECIFICATIONS UNLESS OTHERWISE REQUIRED
BY SPECIAL CONDITIONS
WATER SERVICE - EXISTING ROADWAY AND PAVED AREA:
BACKFILL TO PAVEMENT DEPTH WITH CONTROLLED LOW-STRENGTH MATERIAL (CLSM), "FLOWABLE FILL", 100 PSI MINIMUM AND
150 PSI MAXIMUM MIX DESIGN.
2.PIPE ZONE
BACKFILL MATERIAL SHALL BE TAMPED IN LAYERS AROUND THE PIPE AND TO A SUFFICIENT HEIGHT ABOVE THE PIPE TO ADEQUATELY
SUPPORT AND PROTECT THE PIPE. THE MATERIAL AND BACKFILL ZONES SHALL BE AS SPECIFIED BY THE APPLICABLE AWWA
STANDARD FOR THAT PIPE TYPE. DO NOT DROP PIPE OR ACCESSORIES INTO THE TRENCH. AS A MINIMUM:
WATER MAIN, FIRE LINE, AND APPURTENANCES:
SAND OR 3/4" MAXIMUM PARTICLE SIZE ROADBASE COMPACT TO 96% OF MODIFIED PROCTOR DENSITY
WATER SERVICE:
SAND COMPACTED TO 96% OF MODIFIED PROCTOR DENSITY
3.PIPE BEDDING
WATER MAIN, FIRE LINE, AND APPURTENANCES:
SAND OR 3/4" ROADBASE COMPACT TO 96% OF MODIFIED PROCTOR DENSITY
WATER SERVICE:
SAND COMPACTED TO 96% OF MODIFIED PROCTOR DENSITY
A CONTINUOUS AND UNIFORM BEDDING SHALL BE PROVIDED IN THE TRENCH FOR ALL BURIED PIPE. STONES LARGER THAN 3/4" AS
DESCRIBED IN NOTE 2 SHALL BE REMOVED FOR A DEPTH OF AT LEAST 6 INCHES BELOW THE BOTTOM OF THE PIPE.
4.PROVIDE TRENCH PLATING AS REQUIRED FOR CLSM BACKFILL INSTALLATIONS
5.COMPLY WITH APPLICABLE PARK CITY SOILS ORDINANCE REQUIREMENTS
WATERLINE
(STD. PLAN 540, 541 AND 542)
FINISH GRADE
12" CLR MIN
24" CLR MAX
STD. PLANDATE
REV.
WATER
PARK CITY MUNICIPAL CORPORATION 580
WATER TRENCH BEDDING
AND BACKFILL
PARK CITY MUNICIPAL CORPORATION
WATER
DATE
NFPA 13D RESIDENTIAL FIRE
SPRINKLER LINES
STD. PLAN
5/2014
595 S REV.
0
DETAIL NOTES
1. REFER TO STD. PLAN 520 FOR GENERAL REQUIREMENTS – METER, METER VAULT, AND SERVICE
LINE
2. REFER TO STD. PLANS FOR WATER SERVICE REQUIREMENTS
3. REFER TO THE STATE OF UTAH, DEPARTMENT OF ENVIRONMENTAL QUALITY DIVISION OF DRINKING
WATER LIST OF APPROVED BACKFLOW PREVENTION DEVICES. APPROVED DEVICES CAN BE FOUND
AT THE FOLLOWING STATE OF UTAH WEBSITE:
HTTP://DRINKINGWATER.UTAH.GOV/DOCUMENTS/COMPLIANCE/APPENDIXB_1-19-11.PDF
4. BACKFLOW ASSEMBLY SELECTION AND INSTALLATION SHALL CONFORM TO THE APPROVED
INSTALLATION ORIENTATION ONLY.
5. ALL BACKFLOW PREVENTION DEVICES USED WITHIN THE STATE OF UTAH SHALL HAVE THIRD PARTY
CERTIFICATION AS MENTIONED ABOVE.
6. ALL BACKFLOW PREVENTERS HAVE TO BE TESTED PERIODICALLY TO ENSURE THAT THEY ARE
FUNCTIONING PROPERLY. A VISUAL CHECK OF AIR GAPS IS SUFFICIENT, BUT MECHANICAL
BACKFLOW PREVENTERS HAVE TO BE TESTED BY A STATE CERTIFIED BACKFLOW SPECIALIST, WITH
PROPERLY CALIBRATED GAUGE EQUIPMENT. TO OBTAIN A LIST OF STATE CERTIFIED TESTERS
EITHER CALL US OR REFER TO THE STATE OF UTAH WEBSITE PAGE OF BACKFLOW TESTERS.
HTTP://WWW.DRINKINGWATER.UTAH.GOV/DOCUMENTS/COMPLIANCE/BACKFLOW_TECHNICIANS_CO
MMER_AVAIL.PDF
7. FIRE SPRINKLER SYSTEM PUMPS, INTEGRAL TO THE FIRE SPRINKLER PIPING, TO MEET FIRE
SPRINKLER PRESSURE DESIGN REQUIREMENTS ARE CONSIDERED OUTSIDE THE INTENT OF UTAH
DDW REGULATION R309-550-11(3) AND DO NOT REQUIRE APPROVAL OF THE DDW IF THEIR
INSTALLATION CONFORMS TO UTAH ADOPTED PLUMBING CODE AND NATIONAL FIRE PROTECTION
ASSOCIATION (NFPA) 13 D. PUMPS SHALL BE CONNECTED ON THE BUILDING SIDE OF THE WATER
METER VAULT AND SHALL BE APPROVED BY THE CITY ENGINEER AND BUILDING DEPARTMENT.
PARK CITY MUNICIPAL CORPORATION
WATER
DATE
WATERLINE CASING
STD. PLAN
4/2014
597 S REV.
LEGEND AND APPROVED PARTS LIST
ITEM DESCRIPTION ACCEPTABLE
MANUFACTURER MODELS
① CASING END SEAL PIPELINE SEAL AND
INSULATOR, INC MODEL “S”
② CASING SPACER PIPELINE SEAL AND
INSULATOR, INC. C12G-2 OR APPROVED EQUAL
③ CARRIER PIPE: DUCTILE IRON RESTRAINED JOINT
(STD. PLAN 540)
DETAIL NOTES
1. PROVIDE CARRIER AND CASING SIZE, LOCATION, AND DEPTH PER APPROVED PLANS
2. INSTALL MECHANICAL JOINT A MAXIMUM OF 18” FROM EACH END OF CASING
3. IF REQUIRED BY APPROVED PLANS, INSTALL CLOSED CELL INSULATION IN ANNULAR SPACE BETWEEN
CARRIER PIPE AND CASING. INSTALLATION METHOD TO BE APPROVED BY CITY.
PUBLIC WATER SYSTEM
FIELD OBSERVATION
GUIDELINES
FOR PROJECTS WITHIN THE
PARK CITY WATER SERVICE DISTRICT
FORWARD
This manual provides information to assist the field representative in his duties of observing the
progress and quality of public water line construction within the Park City Water Service
District, Park City, Utah, and determining if the work is proceeding in accordance with Park City
Design Standards, Construction Specifications and Standard Drawings. The information,
checklists and procedures included in the manual are not all inclusive, but are intended to serve
as guidelines for the performance of periodic construction observations, required sampling and
testing observation by the field representative. It is important that field representatives
contact the Project Manager or the Park City Engineer for clarification if there are any
questions related to the requirements of the Park City Design Standards, Construction
Specifications, and Standard Drawings.
DISINFECTING
All new water mains, services, and appurtenances shall be disinfected in accordance with
AWWA Standard C651‐05.
The method typically employed by the Contractor to disinfect new water distribution systems is
to place calcium hypochlorite granules in the pipeline as it is being installed. Reference Park City
Design Standards and Construction Specifications, Appendix 703A. The field representative
should pay special attention to the following items:
Refer to Table No. 1 of the above referenced Appendix for the number of ounces to be
used per pipe diameter and pipe interval to achieve the necessary disinfection
concentration.
Active chlorine content of disinfecting solution within water service tubing (CTS) for
water services shall not exceed 12%.
Water mains shall be filled slowly to prevent "pushing" the calcium hypochlorite
granules to one end of the pipe line. If the new water lines are to be filled by introducing
water from the existing water distribution system, via opening the isolation valve
between the two systems, the field representative shall monitor the opening of the
valve. The field representative shall pay special attention to the following during water
system filling by the Contractor:
1. Verify that the static water pressure of the distribution system (typically 40 psi) is
capable of overcoming the static head required to fill the new water line.
2. Be certain a means of releasing air at the high point of the water system to be filled
is provided and is open.
3. The isolation valve shall be opened only slightly (existing water system valves are to
be operated only by Water Operations staff).
4. Listen for water passing the valve. The valve shall be closed immediately if it appears
that the water pressures begin to equalize on each side of the valve. Backflow of
chlorinated water into the existing water distribution system must not occur.
After the water mains and services have been filled by the Contractor, the field
representative shall sample and test the water for chlorine concentration. Observe the
following:
1. Select sampling frequency and locations to achieve representative samples. Typical
locations for samples at water meter services, taps or fire hydrants. The sampling
frequency will depend on length of the water line being chlorinated, availability of
sampling points, and results of chlorination concentration tests.
The field representative should observe the disinfection of the interior of all pipe,
fittings, valves, tapping sleeves, and other materials when existing water mains are cut
into or repaired. The Contractor can accomplish this by swabbing the materials with a
hypochlorite solution. Reference Park City Design Standards and Construction
Specifications, Appendix A.
Remember: Good disinfection practices improve the opportunity for successful
bacteriological test results.
WATER SYSTEM FLUSHING
Flushing of the installed water system is to be completed in two steps. The initial flushing is to
be performed following installation and disinfection of the water main but prior to hydrostatic
testing. The final flushing is to be performed following hydrostatic testing and leakage testing.
INITIAL FLUSHING
The following items should be considered by the field representative and may need to be
reviewed with the Park City Engineer:
1. When notified that the Contractor intends to begin the initial flushing but before the
Contractor utilizes water contact the Park City Water Department to be certain that
water is available from the City for flushing purposes. Inform the Contractor not to
begin flushing without authorization (existing water system valves are to be operated
only by Water Operations staff).
2. Review with the Contractor the proposed discharge location for flushing operations and
the method by which the Contractor intends to control the discharge of chlorinated
water from the water system. Fire hydrants are not acceptable points for initial
flushing operations.
Typically, Contractors will discharge the water into a water truck or tank and haul the
water offsite for disposal. Chlorinated water shall not be allowed to be discharged in a
manner that it could now onto vegetation or into streams, waterways, storm drains or
sanitary sewer systems.
3. Determine the required diameter of opening(s) for discharge from the water line. The
opening must be sized to achieve velocities capable of moving dirt and rock through the
pipe, approximately 6 to 8 feet per second. Note that required flowrate and opening
size(s) referenced in AWWA Table 3 Required Flow and Openings to Flush Pipelines, is
based on only 2.5 feet per second velocity at 40 psi pressure. Required opening size will
be determined based on site specific available water system pressure to achieve the
required velocity.
4. Determine the total volume of water to be expelled from the section of water system
being flushed. The entire contents of the water line must be discharged and replaced
with new water. To determine the volume required, ensuring that the entire pipe line
has been flushed, utilize the following formula:
V=(πd2/4)( L)(7.481); where: V = volume (gallons)
π/4 = area
d = pipe diameter (feet)
π = 3.141
5. If the section of water line to be flushed is very long, making the transport of sediment
and rock to the discharge location may be difficult, an intermediate discharge location
for flushing should be considered. The end of a fire service line, prior to setting the
hydrant, or a properly sized service tap could be utilized.
6. After initial flushing has been completed, perform sampling and testing for "low"
chlorination concentration.
FINAL FLUSHING
1. Utilize the same procedure for final flushing as for initial flushing, except that concerns
regarding the chlorine concentration of discharge water do not apply.
2. Fire hydrants are to be flushed and can be utilized as flushing locations.
3. Services are to be flushed at the meter vaults. Proper flushing of the service lines is
important since water samples for bacteriological testing are typically taken at the
service lines.
HYDROSTATIC TESTING
Hydrostatic testing is required for every section of water main (valve to valve). Testing every
section is intended to test both sides of isolation valves to ensure proper functioning of the
valve. Prior to hydrostatic testing and leakage testing the water system should be flushed and
tested for proper disinfection.
HYDROSTATIC TESTING
The specified hydrostatic test pressure is to be met at the highest elevation in the section of
water line being tested. The specified test pressure shall be achieved by means of a Contractor
supplied pump/gauge system connected to the pipe. The gauge shall have sufficient increments
to enable accurate readings to be taken.
To achieve proper hydrostatic test pressure at the highest elevation of the water line section
being tested, consider the locations available for installing the testing apparatus. To determine
the required test pressure at the test gauge, utilize the following formula:
Pg = Pr + (Hv – Hg) / 2.31; where: Pg = required gauge pressure reading (psi)
Pr = required test pressure (psi)
Hv = elevation at highest valve (feet)
Hg = elevation at gauge (psi)
Note: 1 psi = 2.31 feet of elevation, or 0.43 psi X elevation difference in feet.
The following items should be considered and may need to be reviewed with the Park City
Engineer:
The possibility of requiring/requesting a water valve to be installed in the water main to
reduce the pressure difference in the water line to be tested. This may occur when
there is a significant difference in elevation between water valves;
The installation of an additional service tap to accommodate proper testing.
In achieving the required hydrostatic pressure at the highest elevation of the water line
section being tested, the hydrostatic pressures at the lowest elevation may exceed
acceptable pressures for the pipe, valves or fittings. Typically, if the calculated pressure
at the lowest elevation exceeds 300 psi, the City Engineer should be notified before
testing is performed.
HYDROSTATIC TESTING
The field representative shall perform all sampling for bacteriological testing and deliver
samples to the Summit County Health Department (or a pre‐approved state certified
laboratory) for analysis. To achieve consistent and representative sampling, the following
procedures shall be observed by the field representative:
Select the location and number of samples to be taken. Samples are typically taken at water
meter services and ends of the water line. Intervals of 200 feet between sampling locations
is preferred.
Procedures for obtaining samples for bacteriological testing of the water system are as
follows:
1. Obtain sample bottles from the Public Works Water Department office or Summit
County Health Department, if not available in the office.
2. When sampling, first disinfect or sterilize the discharge area.
3. Open the control valve slowly and allow water to flow for a short period.
4. Close the valve slightly to reduce the flowrate and fill the sample bottle to the fill line.
Place the lid on the sample bottle and seal shut. Note: Be sure to identify the location of
the sample bottle before obtaining other samples.
After all samples are taken, complete the identification form and add other pertinent
information to each sample bottle. Reference the sample identification form contained in
the Report Forms and Checklists section of this manual. Note: Pay special attention to Item
No. 2, "Investigative Sample (not included on official records)” on the identification form.
Always check this box on the form.
FIELD OBSERVATION REPORT FORMS AND CHECKLISTS
This section includes typical forms checklists that are to be used as generalized guidelines to
assist in the verification of the material and dimensional requirements of the Park City Design
Standards and Construction Specifications. Field Representatives are to utilize the checklists
during water system construction to assist the Contractor in understanding the requirements of
the final product and during the final walk‐through to verify consistency with the standards and
specifications. Additionally, the fire hydrant inspection forms, illustrating the placement of a
fire hydrant in three different terrain conditions, are to be completed during the Final Walk‐
through to provide the Park City Engineer with information regarding the hydrant's installed
elevation and location relative to the curb and gutter and the auxiliary valve.
FIELD OBSERVATION QUICK CHECKLIST
WATER LINE INSTALLATION:
□ Verify that marking tape and locator wire is installed above the water main in the trench
□ Verify that water main is bedded with approved gravel‐sand material
□ Verify that water main is installed at proper horizontal location (within pavement and
inside of curb & gutter limits) and depth. Require additional survey staking be provided if
necessary to determine design grades and curb & gutter alignment
□ Verify that correct polyethylene encasement is provided and properly installed
□ Verify that wax tape coating system is provided and properly installed on all buried bolts
& nuts. Verify the cathodic protection system (if required) is provided and properly
installed.
□ Verify that thrust blocking is of adequate size, extended to undisturbed soil and that the
pipe is wrapped with polyethylene before concrete is placed
□ Verify that service taps are at 45 degrees to the main with 2 feet minimum separation
□ Verify that every service corporation stop is open. This can be verified during flushing
procedures
□ Verify that water valves are properly set, valve boxes are clear of debris, and that a valve
key can be placed on the valve. This must be verified during the final walk‐through
FIELD OBSERVATION QUICK CHECKLIST
FIRE HYDRANT INSTALLATION:
□ Verify that adequate gravel is placed around the fire hydrant base
□ Verify that thrust blocking is properly placed and fire hydrant drain ports are not covered
by concrete.
□ Flush fire hydrant drain ports. Close main hydrant valve to the position at which the
drains open and allow flow through the drains under pressure for about ten seconds to
flush the drains. Then close hydrant valve completely.
□ Check fire hydrant barrels for drainage. Remove nozzle cap, open hydrant valve, allow
hydrant to run briefly and close hydrant valve. Place palm of hand over nozzle outlet.
Drainage should be sufficient to create a suction.
□ Check fire hydrant nozzle caps for thread damage from impact or cross threading
□ Verify that the auxiliary valve is in the wide open position.
□ Verify that fire hydrant markers are installed
□ Verify that fire hydrant is properly extended above grade and hydrant pad is properly
constructed. See Fire Hydrant Inspection Sheet.
FIELD OBSERVATION QUICK CHECKLIST
WATER METER INSTALLATION:
□ Verify that meter service assembly materials are in accordance with Checklist. See
checklists for specific size water meter.
□ Verify that water meter box is adjusted to grade. See meter box adjustment detail sheet.
□ Verify that water meter box is located properly. Require additional staking as required for
verification.
TYPICAL PROCESS FOR WATER SYSTEM CONSTRUCTION
1. INSTALL WATER MAIN AND FIRE
HYDRANTS
2. INSTALL WATER SERVICES
3. INITIAL FLUSHING OF WATER MAIN
4. INITIAL FLUSHING OF WATER SERVICES
5. PERFORM HYDROSTATIC AND LEAKAGE
TESTING ON WATER MAIN
6. PERFORM HYDROSTATIC AND LEAKAGE
TESTING ON FIRE HYDRANTS & WATER
SERVICES
7. FINAL FLUSHING OF WATER MAIN
8. FINAL FLUSHING OF FIRE HYDRANTS &
WATER SERVICES
9. PERFORM BACTERIOLOGICAL TESTING
10. ALLOW ACTIVATION OF WATER SYSTEM
If the Contractor elects to perform
hydrostatic testing of water services
independently of the water main, Items 3, 5,
7 and 9 will be performed on the water
main prior to installation of the water
services.
If water services are installed after water
main testing, the each services must be
disinfected separately.
Sampling and testing for "high" chlorine
concentration is performed prior to initial
flushing.
Sampling and testing for "low" chlorine
concentration is performed following final
flushing.
Permanent opening of isolation valves upon
receipt of successful bacteriological test
results.
WATER SYSTEM TESTING SUMMARY REPORT
PROJECT #
WATER SYSTEM SECTION
DISINFECTION: 703.2.12C & J
GRANULAR INJECTION, WHERE:
SAMPLE LOCATION:
TIME CHLORINE, PPM
START:
END:
RESULT:PASS
DISPOSAL OF CHLORINATED WATER:
FLUSHING: 703.2.12A
MAIN:
LENGTH OF SECTION: PIPE MAT'L: PIPE DIAMETER:inchesfeet
OTHER
FLUSH ORIFICE SIZE:STATION:
ESTIMATED TO BE FLUSHED:gal. ESTIMATED DURATION:min.
min.
INITIAL
ACTUAL DURATION:
FINAL INITIALS DATE:
SERVICES:
DATE:INITIAL FINAL INITIALS
HYDRANTS:
INITIAL FINAL INITIALS
INITIAL FINAL INITIALS
INITIAL FINAL INITIALS
SAMPLE TAKEN BY:P.O. No.:
SAMPLES DELIVERED TO:DATE:TIME:
SAMPLES ANALYZED BY:
SAMPLE NO. 1 TAKEN AT:PASS FAIL
SAMPLE NO. 2 TAKEN AT:PASS FAIL
SAMPLE NO. 3 TAKEN AT:PASS FAIL
DATE OF RESULT:(REFERENCE ATTACHED TESTING REPORT)
PROJECT NAME
CONTRACTOR
TYPE OF CHLORINE:
DATE
FAIL INITIALS
inches
LOT No's:
STATION:
STATION:
STATION:
BACTERIOLOGICAL SAMPLING: 703.2.12M
CITY WATER USED
DATE OF SAMPLE:
WATER SYSTEM TESTING SUMMARY REPORT (continued)
HYDROSTATIC TEST: 703.2.11
MAIN:DATE:DATE:
TEST PRESSURE @ START:psi @ START:psi
@ 30 min:psi @ 30 min:psi
@ 60 min:psi @ 60 min:psi
@ 90 min:psi @ 90 min:psi
@ FINISH:psi @ FINISH:psi
PASS FAIL PASS FAIL
INITIALS INITIALS
COMMENTS:
SERVICES:
LOTS SERVICED:
DATE:DATE:
TEST PRESSURE @ START:psi @ START:psi
@ 30 min:psi @ 30 min:psi
@ FINISH:psi @ FINISH:psi
PASS FAIL PASS FAIL
INITIALS INITIALS
COMMENTS:
HYDRANTS:
TEST DATE: TEST DATE:
@ START:psi @ START:psi @ START:psi
@ 30 min.:psi @ 30 min.:psi @ 30 min.:psi
@ FINISH:psi @ FINISH:psi @ FINISH:psi
PASS FAIL PASS FAIL PASS FAIL
INITIALS:INITIALS:INITIALS:
COMMENTS:
LEAKAGE TEST: 703.2.11
LENGTH OF SECTION:PIPE MAT'L.: DIAMETER:
LENGTH OF TEST:hours minutes
ACCEPTABLE LOSS, per AWWA C600. TABLE 6: gph per 1000 feet,total gallons
GALLONS USED:gallons
RESULT:PASS FAIL INITIALS
INITIAL TEST RETEST
INITIAL TEST RETEST
STREET & STATION:
TEST DATE:
DATE
STREET & STATION: STREET & STATION: