HomeMy WebLinkAboutDDW-2024-014396Danielle Zebelean <dzebelean@utah.gov>
Green Canyon Well #5
6 messages
Lance Anderson <lance@cachelandmark.com>Fri, Sep 20, 2024 at 5:39 PM
To: Danielle Zebelean <dzebelean@utah.gov>
Approval to Equip the Well.zip
DDW-New Well Checklist.docx
North Logan Well 5-PNF Form DDW-2015-
004113.xlsm
Water Rights Approval.pdf
Danielle,
See the equipment plan for North Logan Green Canyon Well #5. Please let us know if you have any questions.
Thanks,
Lance Anderson
435-713-0099 o
Danielle Zebelean <dzebelean@utah.gov>Mon, Sep 23, 2024 at 7:39 AM
To: Michael Newberry <mnewberry@utah.gov>
Got this for north Logan!
Dani Zebelean, P.E.
Environmental Engineer III | Division of Drinking Water
M: (385) 278-5110
Hours: M - Th 7 am to 5 pm
drinkingwater.utah.gov
Emails to and from this email address may be considered public records and thus subject to Utah GRAMA
requirements.
[Quoted text hidden]
Danielle Zebelean <dzebelean@utah.gov>Mon, Sep 23, 2024 at 7:40 AM
To: Lance Anderson <lance@cachelandmark.com>
Cc: Zachary Root <zac@northlogancity.org>
Thank you Lance!
I am out this week in Castle Valley for Sanitary Surveys but should be able to get to this in the next couple of weeks.
12/18/24, 8:36 AM State of Utah Mail - Green Canyon Well #5
https://mail.google.com/mail/u/0/?ik=82c167e5f1&view=pt&search=all&permthid=thread-f:1810760352275197715&simpl=msg-f:181076035227519771…1/3
Dani Zebelean, P.E.
Environmental Engineer III | Division of Drinking Water
M: (385) 278-5110
Hours: M - Th 7 am to 5 pm
drinkingwater.utah.gov
Emails to and from this email address may be considered public records and thus subject to Utah GRAMA
requirements.
[Quoted text hidden]
Michael Newberry <mnewberry@utah.gov>Mon, Sep 23, 2024 at 7:40 AM
To: Danielle Zebelean <dzebelean@utah.gov>
Ok, thanks!..I'll enter this into the system and send the email.
Michael Newberry, P.E.
Permitting Section Manager | Division of Drinking Water
P: (385) 515-1464
drinkingwater.utah.gov
Emails to and from this email address may be considered public records and thus subject to Utah GRAMA
requirements.
[Quoted text hidden]
Danielle Zebelean <dzebelean@utah.gov>Wed, Nov 13, 2024 at 8:00 AM
To: Lance Anderson <lance@cachelandmark.com>
Cc: Zachary Root <zac@northlogancity.org>
Hi Lance,
Sorry, a few weeks turned into more than a month to review this project. I have a couple of questions on the submittals
before issuing the equipping approval.
For the well equipping:
What was the stabilized drawdown for the well? The report and data did not seem to conclude that the 1950
gpm constant rate test resulted in stabilized drawdown. Is the equipped rate considered where it would be
stable? The excerpt from the report had the next step down in flow rate at 1600 gpm, where a 1750 gpm
pump is being installed.
For the chlorinator:
Since North Logan is above a population of 3300 people they will need to have a continuous analyzer
installed to monitor the point of entry (POE) residual. Since the chlorine injection is last on the discharge
piping where is the POE going to be located? By rule the POE needs to be before the first connection.
Sheet A1.0 called out Detail A for the chlorine vent outside on Sheet M3.0 but the detail does not exist on
that page. Is it somewhere else?
Please also confirm the chlorine vent line has a #14 screen.
What is the design chlorine dose rate for the gas chlorinator?
Just confirming but the well goes straight to the distribution system correct? Or does the water go into a
storage tank first before going to the distribution system?
Let me know if you have any questions on this.
Thanks!
12/18/24, 8:36 AM State of Utah Mail - Green Canyon Well #5
https://mail.google.com/mail/u/0/?ik=82c167e5f1&view=pt&search=all&permthid=thread-f:1810760352275197715&simpl=msg-f:181076035227519771…2/3
Dani Zebelean, P.E.
Environmental Engineer III | Division of Drinking Water
M: (385) 278-5110
Hours: M - Th 7 am to 5 pm
drinkingwater.utah.gov
Emails to and from this email address may be considered public records and thus subject to Utah GRAMA
requirements.
[Quoted text hidden]
Lance Anderson <lance@cachelandmark.com>Thu, Dec 12, 2024 at 10:51 AM
To: Danielle Zebelean <dzebelean@utah.gov>
Dani,
See updated plans and response for North Logan City. Let us know if you have any questions.
Thank you,
Lance Anderson
---------- Forwarded message ---------
From: Ashley McAllister <amcallister@cachelandmark.com>
Date: Thu, Dec 12, 2024 at 10:50 AM
Subject: Re: Green Canyon Well #5
To: Lance Anderson <lance@cachelandmark.com>
Lance,
I have included the response to the comments and the supporting documents. These are also saved in
the correspondence folder.
Thanks,
Ashley
On Wed, Dec 11, 2024 at 11:46 AM Lance Anderson <lance@cachelandmark.com> wrote:
[Quoted text hidden]
3 attachments
GC Well 5 Response.docx
59K
240801 Well 5 Exhibit.pdf
1307K
680-2006 Construction Set_Revised.pdf
10929K
12/18/24, 8:36 AM State of Utah Mail - Green Canyon Well #5
https://mail.google.com/mail/u/0/?ik=82c167e5f1&view=pt&search=all&permthid=thread-f:1810760352275197715&simpl=msg-f:181076035227519771…3/3