HomeMy WebLinkAboutDDW-2024-014171Jackson Engineering
3376 Stonehill Lane
Cottonwood Heights, Utah 84121
(801) 558-5293
Department of Environmental Quality November 23, 2024
Division of Drinking Water
195 North 1950 West
P.O. Box 144830
Salt Lake City, UT 84114-4830
RE: Operating Permit Request for JSSD Benloch Tank – 750,000 Gallons
Water System #26086, File #17762
To Whom It May Concern:
This letter’s purpose is to inform the Division of Drinking Water that Jordanelle Special Service
District’s Benloch Ranch concrete water storage tank has been constructed, leak tested, and
disinfected. JSSD has requested that we provide adequate information to your office so that an
Operating Permit may be obtained.
The following details each item of the Operating Permit Checklist:
• Certification of Rule Conformance: As a registered professional Engineer in the
State of Utah, I confirm that all conditions of the plan approval have been
accomplished.
• Utah Registered Engineer’s Statement: No changes to the plan set were necessary
during construction and the District are in procession of the approved construction
plan set.
• Colton Cieslak, a JSSD Inspector, was present during the disinfection and testing
of the tank and associated water lines. He witnessed that the water tank was
properly cleaned and disinfected per AWWA C652-11.
• The Bac-T samples are attached to this letter.
JSSD looks forward to receiving the Operating Permit from your office. If you have any questions
or concerns related to this request or these statements please contact or Steve Jackson at (801) 558-
5293.
Sincerely,
Steven L Jackson, P.E.
A: Absence: R: Routine
P: Presence: I: Investigative
Page 1 of 1
+
JORDANELLE SPECIAL SERVICE DISTRICT
JORDANELLE LABORATORY
Po. Box 519 Phone: 435-333-0475
Heber City Ut. 84032 Form: 28 Fax: 435-333-0513
Microbiological Analysis of Water Samples
Standard Methods 20th, 9223B, Presence/ Absence (P/A), Colilert
MONTH: May 2024 CUSTOMER: JSSD Dist SYSTEM #:
DATE
COLLECTED ID CODE UNIQUE
LAB ID # SAMPLING POINT TIME R,I CL2 SAMPLER
INITIALS RESULT
Total
Coliform
s E.coli
5/13/2024 B6018 R005217 Tank 0948 I 0.28 C.C. A A
5/13/2024 B6019 R005218 Tank 0949 I 1.33 C.C. A A
5/13/2024 B6025 R005219 Tank 0950 I 1.20 C.C. A A
5/13/2024 B6020 R005220 Pump Station 1000 I .02 C.C. A A
5/13/2024 B6022 R005221 Pump Station 1009 I .02 C.C. A A
Analyzed by: T.D.
Approved by: Date: 5/16/2024
Wade C. Webster
DDW-Eng-0010 Page 1 of 1 12/8/2015
Utah Division of Drinking Water ― Checklist for Issuing Operating Permits
(Per Utah Administrative Code, Rule R309-500-9)
Water System Name: Jordanelle SSD System Number: 26086
Project Description: Benloch Ranch Tank – 750,000 Gal File Number: 17762
Items 1 through 8 below must be submitted to the Division and found to be acceptable prior to operating
permit issuance. However, distribution lines without booster pumps may be placed into service prior to
submitting all of the items if a professional engineer (PE) responsible for the entire water system has been
identified to the Director and has received items 1 through 4 below. [In this case, a public water system will
submit all items needed to obtain an Operating Permit for each distribution system project after the new water lines
have been placed into service as determined by the water system’s designated PE.]
☒ 1. Certification of Rule Conformance by a PE that all conditions of Plan Approval have been
accomplished, and if applicable, changes made during construction were in conformance with
rules R309-500 through 550
☒ 2. As-built or record drawings incorporating all changes to approved plans and specifications,
unless no changes were made to the previously submitted and approved pre-construction
drawings
☒ 3. Confirmation that as-built or record drawings have been received by the water system
☒ 4. Evidence that bacteriological samples have been collected to verify proper flushing and
disinfection in accordance with the appropriate ANSI/AWWA Standards:
☐ ANSI/AWWA C651-14 AWWA Standard for Disinfecting Water Mains
Two consecutive sample sets at least 16 hours apart, none positive (every 1200 feet, end-
of-line, each branch, etc.)
☒ ANSI/AWWA C652-11 AWWA Standard for Disinfection of Water-Storage Facilities
One or more samples, none positive
☐ ANSI/AWWA C653-13 AWWA Standard for Disinfection of Water Treatment Plants
Two consecutive samples per unit, none positive, no less than 30 minutes apart
☐ ANSI/AWWA C654-13 AWWA Standard for Disinfection of Wells
Two consecutive samples, none positive, no less than 30 minutes apart
☐ 5. Water quality data, where appropriate [Guidance: Include appropriate raw and finished water data
that demonstrate satisfactory performance of the new treatment facility. Storage tank water shall be
analyzed for residual volatile organic compounds after tank interior painting or re-coating.]
☒ 6. If applicable, all other documentation that may have been required during the plan review
process
☒ 7. If applicable, confirmation that the water system owner has received the O&M manual for the
new facility