HomeMy WebLinkAboutDAQ-2024-011895
1
DAQC-1200-24
Site ID 12524 (B5)
MEMORANDUM
TO: FILE – PACIFICORP – Currant Creek Power Plant
THROUGH: Harold Burge, Major Source Compliance Section Manager
FROM: Rob Leishman, Environmental Scientist
DATE: December 4, 2024
SUBJECT: PacifiCorp – Currant Creek Power Plant (Currant Creek), Major, NSPS, HAPs, Title IV,
Juab County, FRS # UT00000049002300026
INSPECTION TYPE: State Electronic Data Report (SEDR) Review
REVIEW DATE: December 4, 2024
SOURCE LOCATION: Near Mona Reservoir/Juab County
SOURCE CONTACT: David Blackburn – 435-623-3816
APPLICABLE
REGULATIONS: Approval Order DAQE-AN12524009-15 dated January 23, 2015 - New Source
Performance Standards (NSPS) Subparts A, Da, Dc, and GG, applies to this
source.
SOURCE INSPECTION
EVALUATION: With the exception of sources that only monitor for opacity, quarterly report
memoranda will only address the findings of the quarterly report. Approval
Order and Title V permit conditions addressing continuous emission
monitoring requirements will be addressed in Currant Creek’s relative accuracy
performance specification test review memorandum.
SEDR Review
Third Quarter 2024
% Monitor Availability (MA) Performance Test Dates
(N/A to Opacity)
Summary of Excess Emissions During Point
Source Operation
Point
Source
Op.
hrs. Channel MA CGA Lin RATA Point
Source Channel Hrs. Limitation
HRSG1A 1951 NOx 100% 09/03/24 01/30/24 HRSG1A NOx 0.00
2.25 ppmvd at
15%O2 - 3
hour
HRSG1A 1951 CO 100% 09/03/24 01/30/24 HRSG1A CO 0.00
3 ppmvd at
15%O2 - 3
hour
1 8 2
2
Third Quarter 2024
% Monitor Availability (MA) Performance Test Dates
(N/A to Opacity)
Summary of Excess Emissions During Point
Source Operation
Point
Source
Op.
hrs. Channel MA CGA Lin RATA Point
Source Channel Hrs. Limitation
HRSG1A 1951 O2 100% 09/03/24 01/30/24 HRSG1B NOx 0.00
2.25 ppmvd at
15%O2 - 3
hour
HRSG1B 2136 NOx 100% 09/04/24 01/31/24 HRSG1B CO 0.00
3 ppmvd at
15%O2 - 3
hour
HRSG1B 2136 CO 100% 09/04/24 01/31/24
HRSG1B 2136 O2 99% 09/04/24 01/31/24
Excess Emission Report - Hourly Summary
Point
Source Channel
Startup
&
Shutdown
Control
Equipment
Problems
Process
Problems
Other
Known
Causes
Unknown
Causes
Emission
Limit
HRSG1A NOx 0 0 0 0 0 2.25 ppmvd at 15%O2 - 3 hour
HRSG1A CO 0 0 0 0 0 3 ppmvd at 15%O2 - 3 hour
HRSG1B NOx 0 0 0 0 0 2.25 ppmvd at 15%O2 - 3 hour
HRSG1B CO 0 0 0 0 0 3 ppmvd at 15%O2 - 3 hour
CMS Performance Summary - Hourly Summary
Point
Source Channel Monitor
Malfunction
Non-monitor
Malfunction
QA
Calibrations
Other
Known
Causes
Unknown
Causes
HRSG1A NOx 0 2 0 4 0
HRSG1A CO 3 2 0 3 0
HRSG1A O2 4 2 0 3 0
HRSG1B NOx 0 2 1 1 0
HRSG1B CO 0 2 0 3 0
HRSG1B O2 8 2 0 3 0
Pollutant Concentration
Exceeded Span of CEM
Monitor Outage During
Point Source Operation
Alternate
Sampling CEM Modifications
0 Hours 45 Hours 0 Hours 0 Events
3
SOURCE INSPECTION
SUMMARY EVALUATION: Currant Creek maintains its CEMS as required in R307-170 and 40 CFR 60.13.
CURRENT
RECOMMENDATIONS: This report was submitted late on November 20, 2024, with a revised report
being submitted on November 25, 2024, to fix errors noted in the first rendition.
The report was due by October 30, 2024. A warning letter should be sent for
the late SEDR.
All other deviations appear to be a result of breakdown or process related
problems that do not warrant issuing a violation. Periods of excess emissions
that were recorded by the CMS in service on each point source during this
reporting period are summarized in the SEDR and described in Pivot Table 400
“Excess Emissions Review.” Currant Creek was in compliance during this
reporting period. No further enforcement action is recommended.
Currant Creek’s NSPS monitoring system meets the performance standards of
40 CFR 60, Appendix B Performance Specifications.
Currant Creek’s acid rain monitoring system meets the performance standards
of 40 CFR 75 Acid Rain Performance Specifications.
HPV: No
RECOMMENDATION
FOR NEXT INSPECTION: Check DAS for daily zero and span drift.
Check the QC program to ensure that monitor drift is being tracked and that the
source can identify excessive drift.
ATTACHMENTS: Excel spreadsheet review
Pacificorp Currant Creek EER 3Q2024rev1
Point Source Information Late Expired Cal. Gas Valid Cal. Gas Days Yes No
1 Type Code 100
(Company Information)Type Code Company Manager Company Name AIRS # Phone Number
Environmental
Contact
1 100 Tyson Kessler 02300026 (435) 623-3813 David Blackburn
1 100 0 0 0 0
1 Type Code 110
(Point Source Identification)Type Code Point Source
Quarter
1 - 4 Year
Point Source
Operating Hrs. in
Quarter
1 110 3 2024 1951.5
1 110 3 2024 2136.4
1 110 0 0 0
1 Type Code 200
(Monitor Identification)Type Code Point Source Channel Manufacturer Model No. Monitor SN Low Span High Span Installation Date
Monitor
Location
1 200 CO THERMO 48iQ-LS 1192734481 10 1200 3/12/2020 Shelter
1 200 NOx THERMO 42iQ-LS 1192634350 10 200 10/7/2019 Shelter
1 200 O2 THERMO 48iQ-LS 1192734481 0 25 3/12/2020 Shelter
1 200 CO THERMO 48iQ-LS 1192734482 10 1200 3/12/2020 Shelter
1 200 NOx THERMO 42iQ-LS 1192734472 10 200 3/12/2020 Shelter
1 200 O2 THERMO 48iQ-LS 1192734482 0 25 3/12/2020 Shelter
1 200 0 0 0 0 0 0 1/0/1900 0
1
Type Code310
(Excess Emissions)
SUMMARY REPORT
Type Code Channel
Total Hours of Excess
Emissions
Excess Emissions -
% of Total
Operating Hours
RC 701 Hours -
start
up/Shutdown
RC 702 Hours-
Control Equipment
Problems
RC 703 Hours -
Process Problems
RC 704, 706, 707
Hours -Other Known
Causes
RC 705 Hours -
Unknown
Causes
Emission
Limitation
Emission
Limitation
Units
Emission
Limitation
Averaging
Period
1 TRUE 310 NOx 0 0.00% 0 0 0 0 0 2.25 ppmvd at 15%O23 hour
1 TRUE 310 CO 0 0.00% 0 0 0 0 0 3 ppmvd at 15%O23 hour
1 TRUE 310 NOx 0 0.00% 0 0 0 0 0 2.25 ppmvd at 15%O23 hour
1 TRUE 310 CO 0 0.00% 0 0 0 0 0 3 ppmvd at 15%O23 hour
1 310 0 0 0 0 0 0 0 0 0
1 Type Code 300 (CMS
Performance Summary) Type Code Channel
Point Source Operating
Hours
Downtime - % of
Total Operating
Hours
Total CMS
Downtime
RC 721 Hours -
Monitor
Malfunction
RC 722 Hours -
Non-monitor
Malfunction
RC 723 Hours -
QA Calibrations
RC 724 Hours -
Other Known
Causes
RC 725
Hours -
Unknown
Causes
1 TRUE 300 NOx 1951.5 0.31% 6 0 2 0 4 0
1 TRUE 300 CO 1951.5 0.41% 8 3 2 0 3 0
1 TRUE 300 O2 1951.5 0.46% 9 4 2 0 3 0
1 TRUE 300 NOx 2136.4 0.19% 4 0 2 1 1 0
1 TRUE 300 CO 2136.4 0.23% 5 0 2 0 3 0
1 TRUE 300 O2 2136.4 0.61% 13 8 2 0 3 0
1 300 0 0 0 0 0 0
1 Type Code 250
(Performance Specification
RATA Results)
Type Code Channel
Date of Most Current
RATA
Date of Preceding
RATA
Months Between
RATA's
Units of
Measurement CEM Value Reference Method
Value
Relative
accuracy Pass/ Fail
1 364 Days 250 NOx 01/30/24 01/31/23 11.96712329 ppmvd @ 15 O2 1.7 1.9 12.40% Pass
1 364 Days 250 NOx 01/30/24 01/31/23 11.96712329 lb/mmBtu 0.006 0.007 |d?| = 0.001 Pass
1 364 Days 250 NOx 01/30/24 01/31/23 11.96712329 lb/hr 13 14.6 14.10% Pass
1 364 Days 250 O2 01/30/24 01/31/23 11.96712329 Percent 11.6 11.6 0.70% Pass
1 364 Days 250 CO 01/30/24 01/31/23 11.96712329 ppmvd @ 15 O2 1.16 1.25 4.70% Pass
1 364 Days 250 CO 01/30/24 01/31/23 11.96712329 lb/hr 5.4 5.9 11.30% Pass
1 364 Days 250 NOx 01/31/24 02/01/23 11.96712329 ppmvd @ 15 O2 1.73 1.76 1.90% Pass
1 364 Days 250 NOx 01/31/24 02/01/23 11.96712329 lb/mmBtu 0.006 0.007 |d?| = 0.000 Pass
1 364 Days 250 NOx 01/31/24 02/01/23 11.96712329 lb/hr 13.1 13.2 2.50% Pass
1 364 Days 250 O2 01/31/24 02/01/23 11.96712329 Percent 11.3 11.3 0.90% Pass
1 364 Days 250 CO 01/31/24 02/01/23 11.96712329 ppmvd @ 15 O2 1.63 1.46 |d|+CC = 0.17 Pass
1 364 Days 250 CO 01/31/24 02/01/23 11.96712329 lb/hr 7.5 6.7 13.00% Pass
1 0 Days 250 0 01/00/00 01/00/00 0 0 0 0 0.00% 0
Point Source
Point Source
Point Source
HRSG1A
HRSG1B
0
HRSG1B
HRSG1B
HRSG1B
HRSG1B
HRSG1B
HRSG1B
HRSG1B
0
HRSG1B
HRSG1B
HRSG1B
0
HRSG1A
HRSG1A
HRSG1A
PacifiCorp Currant Creek Power Plant
0
HRSG1A
HRSG1A
HRSG1A
HRSG1B
HRSG1B
HRSG1B
0
HRSG1A
HRSG1A
HRSG1A
HRSG1A
HRSG1A
HRSG1A
HRSG1A
HRSG1A
HRSG1B
0
Pacificorp Currant Creek EER 3Q2024rev1
1 Type Code 260
(CGA Results)Type Code Channel Date Audit Point No. Cylinder ID
Cylinder
Expiration Date
Type of
Certification
Units of
Measurement CEM Value Cylinder
Value
Precision
%Pass/ Fail Range - High or
Low
1 Valid Cal. Gas 260 CO 09/03/24 Low DT0038172 09/15/25 P1 ppm 2.8 2.57 11.11% PASS Low
1 Valid Cal. Gas 260 CO 09/03/24 Mid DT0043945 09/20/25 P1 ppm 6.3 5.56 12.71% PASS Low
1 Valid Cal. Gas 260 CO 09/03/24 Low DT0017730 02/19/27 P1 ppm 338.93 333 1.80% PASS High
1 Valid Cal. Gas 260 CO 09/03/24 Mid SA10452 11/20/25 P1 ppm 749.9 666 12.60% PASS High
1 Valid Cal. Gas 260 CO 09/04/24 Low DT0042508 09/15/25 P1 ppm 2.5 2.53 1.19% PASS Low
1 Valid Cal. Gas 260 CO 09/04/24 Mid DT0014586 04/04/25 P1 ppm 5.9 5.44 8.46% PASS Low
1 Valid Cal. Gas 260 CO 09/04/24 Low DT0010340 10/19/28 P1 ppm 348.3 333.7 4.40% PASS High
1 Valid Cal. Gas 260 CO 09/04/24 Mid DT0025811 05/09/30 P1 ppm 691.6 668 3.50% PASS High
1 260 0 01/00/00 0 0 01/00/00 0 0 0 0 0.00% 0 0
1 Type Code 270
(Linearity Test Results)Type Code Channel Date Audit Point No. Cylinder ID
Cylinder
Expiration Date
Type of
Certification
Units of
Measurement CEM Value Cylinder
Value
Precision
%Pass/ Fail Range - High or
Low
1 Valid Cal. Gas 270 NOx 09/03/24 Low DT0038172 09/15/25 P1 ppm 1.7 2.6 0.90% PASS Low
1 Valid Cal. Gas 270 NOx 09/03/24 Mid DT0043945 09/20/25 P1 ppm 5.1 5.6 8.90% PASS Low
1 Valid Cal. Gas 270 NOx 09/03/24 High DT0055802 04/24/27 P1 ppm 9.1 9.1 0.40% PASS Low
1 Valid Cal. Gas 270 NOx 09/03/24 Low EB0020343 06/27/26 P1 ppm 50.5 52.8 4% PASS High
1 Valid Cal. Gas 270 NOx 09/03/24 Mid CC189567 11/24/25 P1 ppm 107.1 109 2% PASS High
1 Valid Cal. Gas 270 NOx 09/03/24 High CC364256 07/10/32 P1 ppm 180.8 179 1% PASS High
1 Valid Cal. Gas 270 O2 09/03/24 Low DT0017730 02/19/27 P1 Percent 6.3 6.3 0.00% PASS 0
1 Valid Cal. Gas 270 O2 09/03/24 Mid SA10452 11/20/25 P1 Percent 13.9 13.8 0.70% PASS 0
1 Valid Cal. Gas 270 O2 09/03/24 High CC272996 06/02/31 P1 Percent 23.3 23 1.30% PASS 0
1 Valid Cal. Gas 270 NOx 09/04/24 Low DT0042508 09/15/25 P1 ppm 1.9 2.6 0.70% PASS Low
1 Valid Cal. Gas 270 NOx 09/04/24 Mid DT0014586 04/04/25 P1 ppm 4.8 5.5 12.70% PASS Low
1 Valid Cal. Gas 270 NOx 09/04/24 High DT0009010 01/06/25 P1 ppm 8.3 9 7.40% PASS Low
1 Valid Cal. Gas 270 NOx 09/04/24 Low EB0074935 07/13/26 P1 ppm 48.1 50.2 4.20% PASS High
1 Valid Cal. Gas 270 NOx 09/04/24 Mid CC188124 06/08/29 P1 ppm 107.9 110.3 2.20% PASS High
1 Valid Cal. Gas 270 NOx 09/04/24 High EB0141282 02/15/32 P1 ppm 176.8 178.8 1.10% PASS High
1 Valid Cal. Gas 270 O2 09/04/24 Low DT0010340 10/19/28 P1 Percent 6.2 6.3 2% PASS 0
1 Valid Cal. Gas 270 O2 09/04/24 Mid DT0025811 05/09/30 P1 Percent 13.5 13.5 0% PASS 0
1 Valid Cal. Gas 270 O2 09/04/24 High CC219564 04/04/32 P1 Percent 22.6 22.5 0% PASS 0
1 270 0 01/00/00 0 0 01/00/00 0 0 0 0 0.00% 0 0
1
Type Code 210
(Pollutant Concentration
Exceeded Span of CEM)
Type Code Channel Start Date Start Time End Date End Time Hours
1 0 210 0 1/0/00 0:00 1/0/00 0:00
1
1 None Reported
1 0 TC 220 Hours 44.57 TC 220 Hours 0.00 TC 230 Hours 0.00 Events 0.00 Hours 0.00 Events 0.00 0.00
1 45.00 TC 300 Hours 0.43 FALSE
None Reported None Reported None Reported None Reported None Reported None Reported
HRSG1B
HRSG1B
HRSG1B
Point Source
Point Source
Point Source
Yes
HRSG1A
HRSG1A
Type Code 550
(Changes in Operation in
Control Equipment When
CEM Data Not Available)
Type Code 500
(Boiler Operating Days
w/o 18 Hours of Data)
Type Code 450
(Data Excluded)
Type Code 210
(Pollutant Concentration
Exceeded Span of CEM)
Type Code 220
(Monitor Outage
During Point Source Operation)
Type Code 230
(Manual Sample - Alternate
Sampling During Monitor
Outage)
Type Code 240
(CEM Modifications)
Type Code 530
(Excess Emissions During
Emergency Conditions)
HRSG1A
HRSG1A
HRSG1B
HRSG1B
HRSG1B
HRSG1B
0
HRSG1B
0
HRSG1A
HRSG1A
HRSG1A
HRSG1A
HRSG1B
HRSG1A
HRSG1A
HRSG1A
HRSG1A
HRSG1A
HRSG1B
HRSG1B
HRSG1B
HRSG1B
0
Pacificorp Currant Creek EER 3Q2024rev1
Relative Accuracy Overview
Point Source Channel
Date of Most
Current
RATA
Date of
Preceding
RATA
Months Between
RATA's
Units
Measured CEM Value Reference Method
Value
Relative
Accuracy Pass/ Fail 2024
HRSG1A NOx 01/30/24 01/31/23 11.96712329 ppmvd @ 15 O2 1.7 1.90 12.40% Pass
HRSG1A NOx 01/30/24 01/31/23 11.96712329 lb/mmBtu 0.006 0.01 |d?| = 0.001 Pass
HRSG1A NOx 01/30/24 01/31/23 11.96712329 lb/hr 13 14.60 14.10% Pass
HRSG1A O2 01/30/24 01/31/23 11.96712329 Percent 11.6 11.60 0.70% Pass
HRSG1A CO 01/30/24 01/31/23 11.96712329 ppmvd @ 15 O2 1.16 1.25 4.70% Pass
HRSG1A CO 01/30/24 01/31/23 11.96712329 lb/hr 5.4 5.90 11.30% Pass
HRSG1B NOx 01/31/24 02/01/23 11.96712329 ppmvd @ 15 O2 1.73 1.76 1.90% Pass
HRSG1B NOx 01/31/24 02/01/23 11.96712329 lb/mmBtu 0.006 0.01 |d?| = 0.000 Pass
HRSG1B NOx 01/31/24 02/01/23 11.96712329 lb/hr 13.1 13.20 2.50% Pass
HRSG1B O2 01/31/24 02/01/23 11.96712329 Percent 11.3 11.30 0.90% Pass
HRSG1B CO 01/31/24 02/01/23 11.96712329 ppmvd @ 15 O2 1.63 1.46 |d|+CC = 0.17 Pass
HRSG1B CO 01/31/24 02/01/23 11.96712329 lb/hr 7.5 6.70 13.00% Pass
*
NSPS CGA Third 2024
Audit Gas Ranges Audit Gas Ranges
AP1 Low AP2 Low AP1 High AP2 High
HRSG1A CO 9/3/24 10 2.57 2 to 3
HRSG1A CO 9/3/24 10 5.56 5 to 6
HRSG1A CO 9/3/24 1200 333 240 to 360
HRSG1A CO 9/3/24 1200 666 600 to 720
HRSG1B CO 9/4/24 10 2.53 2 to 3
HRSG1B CO 9/4/24 10 5.44 5 to 6
HRSG1B CO 9/4/24 1200 333.7 240 to 360
HRSG1B CO 9/4/24 1200 668 600 to 720
*
Acid Rain Audit Linearity Third 2024
Low Span Gas Ranges High Span Gas Ranges
Low Mid High Low Mid High
HRSG1A NOx 9/3/24 10 2.6 2 to 3
HRSG1A NOx 9/3/24 10 5.6 5 to 6
HRSG1A NOx 9/3/24 10 9.1 8 to 10
HRSG1A NOx 9/3/24 200 52.8 40 to 60
HRSG1A NOx 9/3/24 200 109 100 to 120
HRSG1A NOx 9/3/24 200 179 160 to 200
HRSG1A O2 9/3/24 25 6.3 5 to 7.5
HRSG1A O2 9/3/24 25 13.8 12.5 to 15
HRSG1A O2 9/3/24 25 23 20 to 25
HRSG1B NOx 9/4/24 10 2.6 2 to 3
HRSG1B NOx 9/4/24 10 5.5 5 to 6
HRSG1B NOx 9/4/24 10 9 8 to 10
HRSG1B NOx 9/4/24 200 50.2 40 to 60
HRSG1B NOx 9/4/24 200 110.3 100 to 120
HRSG1B NOx 9/4/24 200 178.8 160 to 200
HRSG1B O2 9/4/24 25 6.3 5 to 7.5
HRSG1B O2 9/4/24 25 13.5 12.5 to 15
HRSG1B O2 9/4/24 25 22.5 20 to 25
Audit Gas Used
Point Source Channel Audit Date Low Span
Point Source Channel Audit Date Low Span
Audit Gas Used High Span Audit Gas Used
High SpanAudit Gas Used
Pacificorp Currant Creek EER 3Q2024rev1
Monitoring Information TC 210, 230, & 240
Type Code 210
(Pollutant Concentration Exceeded Span of CEM) - 500 (All)
*
Sum of Hours Column Labels
Row Labels (blank) Grand Total
(blank)0 0
Grand Total 0 0
*
Type Code 230
(Manual Sample - Alternate Sampling During Monitor Outage) - 500 (All)
*
Sum of Hours Column Labels
Row Labels (blank) Grand Total
(blank)0 0
Grand Total 0 0
*
Type Code 240
(CEM Modifications) - 100 (All)
*
Count of Channel Column Labels
Row Labels (blank) Grand Total
(blank)
(blank)
Grand Total
Pacificorp Currant Creek EER 3Q2024rev1
Type Code 220
(Monitor Outage During Point Source Operation) - 600 (All)
*
Sum of Hours Column Labels
Row Labels 722 724 721 723 Grand Total
HRSG1A
NOx
Communication lost, reset server, verifed data communication and
returned to service.1.98 1.98
Monitor taken out of service to make repair on other monitor. Returned
to service.0.98 0.98
Performed routine maintenance, recalibrated.2.97 2.97
CO
Communication lost, reset server, verifed data communication and
returned to service.1.98 1.98
Performed needed maintenance, completed auto-cal and abbreviated
linearity.2.98 2.98
Performed routine maintenance, recalibrated.2.97 2.97
O2
Communication lost, reset server, verifed data communication and
returned to service.1.98 1.98
Monitor taken out of service to make repair on other monitor. Returned
to service.0.98 0.98
Performed needed maintenance. Recalibrated and returned to service.3.98 3.98
Performed routine maintenance, recalibrated.1.97 1.97
HRSG1B
NOx
Communication lost, reset server, verifed data communication and
returned to service.1.98 1.98
Performed routine maintenance, recalibrated.0.98 0.98
Unit placed in maintenance mode, replaced cylinder, calibrated and
returned to service.0.98 0.98
CO
Communication lost, reset server, verifed data communication and
returned to service.1.98 1.98
Performed routine maintenance, recalibrated.2.95 2.95
O2
Communication lost, reset server, verifed data communication and
returned to service.1.98 1.98
Performed needed maintenance. Recalibrated and returned to service.7.97 7.97
Performed routine maintenance, recalibrated.2.95 2.95
Grand Total 11.90 16.75 14.93 0.98 44.57
Pacificorp Currant Creek EER 3Q2024rev1
NOx *
NOx Type Code 420 (NOx) - 6000 (All)
NOx *
NOx Count of Magnitude of Emissions Column Labels
NOx Row Labels Grand Total
NOx Grand Total
NOx d *
NOx d Type Code 421 (Daily NOx Emissions) - 500 (All)
NOx d *
NOx d Count of Reason Code Column Labels
NOx d Row Labels Grand Total
NOx d Grand Total
CO *
CO Type Code 440
(CO) - 6000 (All)
CO *
CO Count of Magnitude of Emissions Column Labels
CO Row Labels Grand Total
CO Grand Total
O2 *
O2 Type Code 470
(TRS as O2) - 6000 (All)
O2 *
O2 Count of Magnitude of Emissions Column Labels
O2 Row Labels Grand Total
O2 Grand Total
Pacificorp Currant Creek EER 3Q2024rev1
Type Code 500
Before February 28, 2005 (Boiler Operating Days w/o 18 Hours of
Data) After February 28, 2005 (90% Operating Hours For each 30 BOD)
- 500
(All)
*
Count of Channel Column Labels
Row Labels Grand Total
Grand Total
*
Type Code 510
(F-factor, Equations & Conversion Factors) - 500 (All)
Count of F-factor Column Labels
Row Labels Grand Total
Grand Total
*
Type Code 520
(Minimum Data Not
Obtained <22/30 BODs) - 500
(All)
Count of Channel Column Labels
Row Labels Grand Total
Grand Total
*
Type Code 530
(Excess Emissions During Emergency Conditions) - 500 (All)
Count of Date Column Labels
Row Labels Grand Total
Grand Total
*
Type Code 540
(Fuel Pre-treatment Credit SO2) - 500 (All)
Count of Date Column Labels
Row Labels Grand Total
Grand Total
*
TypeCode 550
(Changes in Operation in Control Equipment When CEM Data Not
Available) - 500
(All)
Column Labels
Row Labels Grand Total
Grand Total