HomeMy WebLinkAboutDERR-2024-012616Line Test
Facility Information
Name:Fast Stop 1116 Certification/Inspection #:56500
Address:370 N Main St State ID:2000340
Phone Number:Form Completed By:Larry Vasquez Date:11/27/2024
Tank Test Information
Tank #:T1 RUL T2 PUL T3 DSL
Capacity:19975 19975 19975
Product:Unleaded Premium Diesel
Line Test Information
Line #:RUL PUL DSL
LineType:Pressure Pressure Pressure
Line Material:DW Flex DW Flex DW Flex
Line ID Size (in):2 2 2
Line Length (ft):400 400 300
Pump Type:Red Jacket Red Jacket Red Jacket
Associated Tank:T1 RUL T2 PUL T3 DSL
Test Equip. Mfg.:Triangle Triangle Triangle
Test Pressure (PSI):50 50 50
Initial Cyl. Level:260 180 250
Final Cyl. Level:240 150 230
Change in Time (mins):15 15 15
Change in Vol:-20.0000 -30.0000 -20.0000
Change in Temp (F):0 0 0
Coeff. Of Thermal Expansion (g/F):0.00070 0.00070 0.00045
Line Vol (gal):65.25 65.25 48.94
Leak Rate (GPH):-0.0211 -0.0317 -0.0211
Result:Pass Pass Pass
Notes
TIGHTNESS TESTING CERTIFICATION
CGRS certifies that the systems in the above table have been tested utilizing leak detection methods which meet the prescribed leak rate testing standard of 0.10
gph with a minimum probability of detection of 95% and a 5% probability of a false alarm. CGRS further certifies that the protocol for each test method was strictly
adhered to, and that all precision tightness testing performed by CGRS was conducted in accordance with EPA 40 CFR parts 280.43(c) and 280.44(b) and the
National Fire Protection Association, Bulletin NFPA 329 criteria.
Contractor Printed Name:Larry Vasquez Contractor Signature:
Certification Number:TMI-301