HomeMy WebLinkAboutDERR-2024-012616Line Test Facility Information Name:Fast Stop 1116 Certification/Inspection #:56500 Address:370 N Main St State ID:2000340 Phone Number:Form Completed By:Larry Vasquez Date:11/27/2024 Tank Test Information Tank #:T1 RUL T2 PUL T3 DSL Capacity:19975 19975 19975 Product:Unleaded Premium Diesel Line Test Information Line #:RUL PUL DSL LineType:Pressure Pressure Pressure Line Material:DW Flex DW Flex DW Flex Line ID Size (in):2 2 2 Line Length (ft):400 400 300 Pump Type:Red Jacket Red Jacket Red Jacket Associated Tank:T1 RUL T2 PUL T3 DSL Test Equip. Mfg.:Triangle Triangle Triangle Test Pressure (PSI):50 50 50 Initial Cyl. Level:260 180 250 Final Cyl. Level:240 150 230 Change in Time (mins):15 15 15 Change in Vol:-20.0000 -30.0000 -20.0000 Change in Temp (F):0 0 0 Coeff. Of Thermal Expansion (g/F):0.00070 0.00070 0.00045 Line Vol (gal):65.25 65.25 48.94 Leak Rate (GPH):-0.0211 -0.0317 -0.0211 Result:Pass Pass Pass Notes TIGHTNESS TESTING CERTIFICATION CGRS certifies that the systems in the above table have been tested utilizing leak detection methods which meet the prescribed leak rate testing standard of 0.10 gph with a minimum probability of detection of 95% and a 5% probability of a false alarm. CGRS further certifies that the protocol for each test method was strictly adhered to, and that all precision tightness testing performed by CGRS was conducted in accordance with EPA 40 CFR parts 280.43(c) and 280.44(b) and the National Fire Protection Association, Bulletin NFPA 329 criteria. Contractor Printed Name:Larry Vasquez Contractor Signature: Certification Number:TMI-301