Loading...
HomeMy WebLinkAboutDERR-2024-012373NWTLI UST & AST Inspections Complete Site Compliance Testing & Upgrades Industrial Protective Linings & Coatings Fuel Polishing & Treatment 1 (888) TLC-TANK UNDERGROUND STORAGE TANK INTERNAL INSPECTION REPORT Two (2) 6,000-gallon USTs Prepared for: Johann Defa Hanna Country Store 40928 W State Rd 35 Hanna UT 84031 5 November 2024 Lining Inspection of two (2) USTs Guidance from the following: Utah DEQ DERR R311 UAC 40 CFR § 280.21(b)(1) API Publication 1631 NLPA Standard 631 NWTLI UST & AST Inspections Complete Site Compliance Testing & Upgrades Industrial Protective Linings & Coatings Fuel Polishing & Treatment 2 (888) TLC-TANK Hanna Country Store 5 November 2024 40928 W State Rd 35 Hanna UT 84031 801-299-0888 801-205-7807 mobile johanndefa@yahoo.com Hanna Country Store contracted NWTLI to inspect interior lining system on two (2) underground storage tanks (USTs) located at 40928 W State Rd 35, Hanna UT. The contract was to complete the following: purge, open and enter confined space; clean out interior of USTs and conduct an inspection of the interior lining using NPLA Standard 631 and API 1631 nationally recognized industry standards; reseat lid to form airtight seal at entry point. A complete description of events is detailed below. NWTLI field crew arrived on site 1 November 2024 to perform UST lining inspection work. Excavation was required as manways were not available. Total depth to top of tanks from grade was 3-4 feet deep. USTs were purged with eductor-type air mover (venturi) to maximize air volume. Atmospheres inside each tank were checked for Lower Explosion Level (LEL). When LEL was at a safe level, tanks were opened using pneumatic tools. After each tank was opened, a certified confined space rescue worker entered each tank with supplied air hood and fully protected clothing. USTs were cleaned out and sludge was collected in 55-gallon barrels, and left on-site for owner disposal. FINDINGS ON USTs: Tank #1 Diesel was opened and cleaned out, interior striker plates were observed under fill and monitoring ports as required by EPA. Inspection of tank interior found no evidence of pitting, rusting, physical damage, water leakage, cracks, streaking, discoloration or other signs of structural instability of the tan k or lining; a visual inspection of tank linings was conducted and at least 98% of linings was visible for inspection; linings are still performing according to original design specifications. There was no evidence of lining peeling, blistering, wrinkled surface or surface roughening. NWTLI UST & AST Inspections Complete Site Compliance Testing & Upgrades Industrial Protective Linings & Coatings Fuel Polishing & Treatment 3 (888) TLC-TANK Tank #2 Regular was opened and cleaned out, interior striker plates were observed under fill and monitoring ports as required by EPA. Inspection of tank interior found no evidence of pitting, rusting, physical damage, water leakage, cracks, streaking, discoloration or other signs of structural instability of the tank or lining; a visual inspection of tank linings was conducted and at least 98% of linings was visible for inspection; linings are still performing according to original design specifications. Th ere was no evidence of lining peeling, blistering, wrinkled surface or surface roughening. All tank linings were in compliance with industry standards and found to be in good condition and free of any cracks, damage or de-laminations at the time of final inspection. This report certifies that these inspected USTs are suitable for continued use for a minimum of five (5) years. UST lids were reseated with gasket material and bolted on entry points of USTs. Photographs were taken to show work in progress, overall condition of tank s and lining material, locations of interior openings and tank equipment. Based on tests performed, lining systems of USTs appear to be in good condition. Prior UST upgrade by installation of epoxy lining material has met State of Utah’s UST rules and regulations, and Federal EPA’s requirements 40 CFR §280.21 Upgrading of existing UST systems (b) (1) and in §280.33 Repairs allowed; National Leak Prevention Association Standard 631 Entry, Cleaning, Interior Inspection, Repair, and Lining Underground Storage Tanks; API Standard 1631 Interior Lining and Periodic Inspection of Underground Storage Tanks. Owners of UST systems should confirm with State, local or other implementing agency on requirements for periodic lining inspections. NWTLI recommends an interior lining inspection within five (5) years from the date of this report. If applicable, cathodic protection system should be maintained by a state licensed Cathodic Protection technician. UST system owners and operators must maintain records that demonstrate compliance with the requirements set forth, and be made available for inspection, by the implementing agency. NWTLI appreciates the opportunity to help your company with meeting regulatory compliance requirements. Sincerely, Brad C. Boston/NWTLI ICC U1 Cert# 8294153 NWTLI UST & AST Inspections Complete Site Compliance Testing & Upgrades Industrial Protective Linings & Coatings Fuel Polishing & Treatment 4 (888) TLC-TANK UST Recertification Form Hanna Country Store 5 Nov 2024 Facility ID Completion Date 40928 W SR-35 Hanna UT 84031 Rodolfo Rodriguez Site Address Coatings Expert Johann Defa 801-205-7807 Brad Boston Contact Name & Phone ICC Cert# 8294153 NONDESTRUCTIVE EXAMINATION RESULTS 6000-GALLON UST #1 Ø 8' x 16' TANK HEADS Top R 3/4 RSL R 1/4 Bot L 1/4 LSL L 3/4 FILL LLM 3 0.243 0.242 0.238 0.242 0.239 0.240 0.242 0.239 0.240 0.243 6 0.239 0.243 0.240 0.244 0.241 0.243 0.243 0.244 0.245 0.245 9 0.242 0.241 0.241 0.239 0.240 0.242 0.240 0.242 0.244 0.246 12 0.240 0.237 0.239 0.244 0.239 0.241 0.241 0.241 0.243 0.244 15 0.239 0.239 0.240 0.238 0.241 0.242 0.246 0.247 0.247 0.243 0.242 AVERAGE UT 101% of UL 58 §3.6 Table 3.1 6,000 Gal Ø 8’ x 16’L Diesel Nom. Tank Capacity Nom. Tank Dimensions Tank Contents UST Lining Recertification Acceptable 125 mil Pass Shore D Hardness Dry Film Thickness Holiday Test Meets NLPA Standard 631 & API 1631: [x] Pass [ ] Fail Tank meets R311, UAC requirements: [x] Pass [ ] Fail Signed: Date: 5 Nov 2024 Rodolfo Rodriguez/NCCER 6988764 NWTLI UST & AST Inspections Complete Site Compliance Testing & Upgrades Industrial Protective Linings & Coatings Fuel Polishing & Treatment 5 (888) TLC-TANK UST Recertification Form Hanna Country Store 5 Nov 2024 Facility ID Completion Date 40928 W SR-35 Hanna UT 84031 Rodolfo Rodriguez Site Address Coatings Expert Johann Defa 801-205-7807 Brad Boston Contact Name & Phone ICC Cert# 8294153 NONDESTRUCTIVE EXAMINATION RESULTS 6000-GALLON UST #2 Ø 8' x 16' TANK HEADS Top R 3/4 RSL R 1/4 Bot L 1/4 LSL L 3/4 FILL LLM 3 0.241 0.239 0.238 0.241 0.246 0.244 0.242 0.239 0.241 0.242 6 0.239 0.244 0.240 0.243 0.240 0.241 0.244 0.244 0.246 0.244 9 0.243 0.245 0.242 0.244 0.242 0.244 0.239 0.242 0.244 0.245 12 0.240 0.246 0.239 0.245 0.238 0.241 0.242 0.243 0.245 0.243 15 0.242 0.239 0.244 0.238 0.240 0.242 0.244 0.244 0.247 0.246 0.244 AVERAGE UT 101% of UL 58 §3.6 Table 3.1 6,000 Gal Ø 8’ x 16’L Regular Nom. Tank Capacity Nom. Tank Dimensions Tank Contents UST Lining Recertification Acceptable 125 mil Pass Shore D Hardness Dry Film Thickness Holiday Test Meets NLPA Standard 631 & API 1631: [x] Pass [ ] Fail Tank meets R311, UAC requirements: [x] Pass [ ] Fail Signed: Date: 5 Nov 2024 Rodolfo Rodriguez/NCCER 6988764 NWTLI UST & AST Inspections Complete Site Compliance Testing & Upgrades Industrial Protective Linings & Coatings Fuel Polishing & Treatment 6 (888) TLC-TANK PHOTO DOCUMENTATION View of Hanna Country Store, Hanna UT NWTLI UST & AST Inspections Complete Site Compliance Testing & Upgrades Industrial Protective Linings & Coatings Fuel Polishing & Treatment 7 (888) TLC-TANK November 2024 View of 6,000-gallon Diesel Tank #1 NWTLI UST & AST Inspections Complete Site Compliance Testing & Upgrades Industrial Protective Linings & Coatings Fuel Polishing & Treatment 8 (888) TLC-TANK November 2024 View of 6,000-gallon Diesel Tank #1 NWTLI UST & AST Inspections Complete Site Compliance Testing & Upgrades Industrial Protective Linings & Coatings Fuel Polishing & Treatment 9 (888) TLC-TANK November 2024 View of 6,000-gallon Regular Tank #2 NWTLI UST & AST Inspections Complete Site Compliance Testing & Upgrades Industrial Protective Linings & Coatings Fuel Polishing & Treatment 10 (888) TLC-TANK November 2024 View of 6,000-gallon Regular Tank #2 NWTLI UST & AST Inspections Complete Site Compliance Testing & Upgrades Industrial Protective Linings & Coatings Fuel Polishing & Treatment 11 (888) TLC-TANK View of closed lid on Diesel #1 View of closed lid on Regular #2 NWTLI UST & AST Inspections Complete Site Compliance Testing & Upgrades Industrial Protective Linings & Coatings Fuel Polishing & Treatment 12 (888) TLC-TANK