HomeMy WebLinkAboutDAQ-2024-011548t.t ,.tttF$nctor
December 30,2022
Director, Air Enforcement Division CERTIFIED MAIL: 7019 1120 0000 0070 7777
Office of Civil Enforcement
U.S. Environmental Protection Agency
Mail Code 2242-A
1200 Pennsylvania Avenue, NW
'ilH",?,;!i,?H'S^il,Air Program Director
Offrce of Enforcement, Compliance & Environmental Justice JAN - 5 2023Environmental Protection Agency, Region 8
1595 Wynkoop Street
Denver, Co 80202_ttze DMSION OF AIR eUALffy
Executive Secretary, Utah Air Quality Board
Division of Air Quality
Utah Dept. of Environmental Quality
195 North 1950 West
P.O. Box 144820
Salt Lake city, Utah 841164820
RE: Controlled Heater and Boiler NOx Reduction
Annual Progress Report
ln compliance with paragraph 46d of the Holly Refrning and Marketing Company Consent Decree
entered July 2,2008, the following is the annual progress report for Holly's program to reduce NOx
emissions from controlled heaters and boilers.
Crude Heater 8H1 was decommissioned as of Ma! 28,2015.
1. Controlled Heaters and Boilers for which NO- Control Technoloe.v was installeda. Crude Heater 8Hlb. NHDS Feed Heater l2H1c. Clark Compressor I l-2 (in lieu of Reformer Heater 6H1 - See Consent Decree Appendix
B, note a.)d. #5 Boiler 5l-5 I
e. #6 Boiler 51-6f. #8 Boiler 51-8g. FCCU Feed Heater 4-1
HF Sinclair Woods Cross Refining LLC
1070 W. 500 S, West Bountiful, UT 84087
801-299-6600 | HFSinclair.com
REVIEWEDInitials: Date: Nov 14, 2024Compliance Status: OKFile #: 10123 (B2)
Dhector, Air Enforcement Division, et. al.
December 30,2022
Page2
2. Tlpe of NO- Control Technologv that was inqtalled on each heater and boilera. Crude Heater 8Hl
Type:
Manufacturer:
Model:
Designed emission factors :
b.NHDS Feed Heater 12H1
Tlpe:
Manufacturer:
Model:
Designed emission factors:
Clark Compressor
Type:
Manufacturer:
Model:
Designed emission factors:
#5 Boiler 5l-5
Type:
Manufacturer:
Model:
Designed emission factors :
#6 Boiler 51-6
Tlpe:
Manufacturer:
Model:
Designed emission factors:
#8 Boiler 5l-8
Type:
Manufacturer:
Model:
Designed emission factors:
Next Generation Ultra Low-NOx Burners
Increase Performance, Inc.
IPLN-SR6
0.020 lb NOx/mmBTU corrected to 3%o Oz on clean
natural gas, natural draft
Next Generation Ultra [ow-NOx Bumers
Increase Performance, Inc.
IPLN.SRI2
0.020 lb NOx/mmBTU corrected to 3o/o Oz on clean
pratural gas, natural draft
I l-2 (in lieu of Reformer Heater 6Hl)
d.
$eRlaced existing gas driven compressor with an electric
driven compressor
N/A
N/A
Eliminated 100% of the emissions from the prior gas
drive.
Selective Catalytic Reduction
Nationwide Boiler Inc.
SCR-61 package
0.020 lb NOx/mmBTU corrected to 3%oOz
Decommissioned Boiler
[vra
N/A
Eliminated 100% of the emissions.
Selective Catalytic Reduction
Nationwide Boiler Inc.
SCR-80 package
0.020 lb NOx/mrnBTU corrected to 3o/o Oz
Director, Air Enforcement Division, et. al.
December 30,2022
Page 3
FCCU Feed Heater 4-l
Type:
Manufacturer:
Model:
Designed emission factors:
N/A
N/A
N/A
Fuel gas limit to 40 mmBTU/hr or less by physical
restriction.
ob.
3. Performance Test Results
Results of the performance tests on 8H1 and l2Hl were attached to the previous annual report dated
December 15, 2008. Results of the perfonnance test on #5 Boiler were attached to the previous annual
report dated December 22,2010. Results of the perfonnance test on #8 Boiler were attached to the
previous annual report dated Decemb er 3l , 2013 . No test is needed for the electric drive on the
replacement for the Clark Compressor ll-2, the decommissioning of the CO Boiler, or the restriction on
the FCCU Feed Heater.
4. Heaters and boilers scheduled to have NOx Coptrol Technoloey installed next calendar year
None.
Technoloe.v has been installed
Perrrit limits for NOx from 8Hl and 12Hl were proposed by Holly at a level of 0.10 lbs/mmBtu. The
established NOx permit limits for 8Hl and 12Hl incorporated into UDEQ permit DAQE-
AN0101230027-09 are 0.10 lbs/mmBtu. The permit limit for NOx from #5 Boiler was proposed by Holly
at a level of 0.03 lbs/mmBtu. The established NOx permit limit for #5 Boiler incorporated into UDEQ
pemrit DAQE-AN0101230036-10 is 0.03 lbs/mmBtu. The permit limit forNOx from #5 Boiler was
proposed by Holly at a level of 0.02 lbVmmBtu. The established NOx perrrit limit for #8 Boiler
incorporated into UDEQ permit DAQE-AN0101230041-13 is 0.02 lbs/mmBtu.
Sincerely,
tfuLEa op7c; tP,Fct F
Vice President & Refinery Manager
Director, Air Enforcement Division, et. al.
December 30,2022
Page 4
ec:
Director, Air Enforcement Division
Office of Civil Enforce,ment
c/o Matix New lVorld Engineering Inc.
26 Columbia Turnpike, 2d Floor
FlorhamPark, NJ 07932
MeganJ. Houdeshel
Dorsey & Whitney LLP
111 S. Main Sheet, Suite 2100
salt Lake city, uT 84lll-2176
csullivan@atrixneworld.com
foley.patrick@epa. gov
ga[agh€r.bob@epamail.epa. gov
M. Jennings
T. Go
R. Bagherian
Environmental File 2.6.3. I .046