Loading...
HomeMy WebLinkAboutDAQ-2024-011521 1 DAQC-1121-24 Site ID 16015 (B5) MEMORANDUM TO: FILE – HOLLY ENERGY PARTNERS – Light Oil Dock THROUGH: Harold Burge, Major Source Compliance Section Manager FROM: Rob Leishman, Environmental Scientist DATE: November 5, 2024 SUBJECT: Holly Energy Partners, Light Oil Dock (Holly LOD), Major, MACT, SIP, Title V, Davis County, FRS # UT00000049001100013 INSPECTION TYPE: State Electronic Data Report (SEDR) Review REVIEW DATE: November 5, 2024 SOURCE LOCATION: West Bountiful/Davis County SOURCE CONTACT: Daria Underwood – 214-954-3935 APPLICABLE REGULATIONS: Title V operating permit – 1100458001 – dated February 8, 2021 SOURCE INSPECTION EVALUATION: With the exception of sources that only monitor for opacity, quarterly report memoranda will only address the findings of the quarterly report. Approval Order and Title V permit conditions addressing continuous emission monitoring requirements will be addressed in Holly LOD’s relative accuracy performance specification test review memorandum. SOURCE REVIEW EVALUATION: Third Quarter 2024 % Monitor Availability (MA) Performance Test Dates (N/A to Opacity) Summary of Excess Emissions During Point Source Operation Point Source Op. hrs. Channel MA CGA Lin RATA Point Source Channel Hrs. Limitation LOD 2208 VOC 99% 08/26/24 11/21/23 LOD VOC 0.00 10000 ppm - 6 hour RA 1 8 2 2 Excess Emission Report - Hourly Summary Point Source Channel Startup & Shutdown Control Equipment Problems Process Problems Other Known Causes Unknown Causes Emission Limit LOD VOC 0 0 0 0 0 10000 ppm - 6 hour RA CMS Performance Summary - Hourly Summary Point Source Channel Monitor Malfunction Non-monitor Malfunction QA Calibrations Other Known Causes Unknown Causes LOD VOC 0 0 12 0 0 Pollutant Concentration Exceeded Span of CEM Monitor Outage During Point Source Operation Alternate Sampling CEM Modifications 0 Hours 0 Hours 0 Hours 0 Events SOURCE INSPECTION SUMMARY EVALUATION: Holly LOD maintains its CEMS as required in R307-170 and 40 CFR 60.13. CURRENT RECOMMENDATIONS: All deviations appear to be a result of breakdown or process related problems that do not warrant issuing a violation. Holly Energy Partners Light Oil Dock was in compliance during this reporting period. No further enforcement action is necessary. Holly LOD’s NSPS monitoring system meets the performance standards of 40 CFR 60, Appendix B Performance Specifications. HIGH PRIORITY VIOLATOR (HPV): No RECOMMENDATION FOR NEXT INSPECTION: Check DAS for daily zero and span drift. Check the QC program to ensure that monitor drift is being tracked and that the source can identify excessive drift. ATTACHMENTS: Excel spreadsheet review Holly LOD EER 3Q2024 Point Source Information Late Expired Cal. Gas Valid Cal. Gas Days Yes No 1 Type Code 100 (Company Information)Type Code Company Manager Company Name AIRS # Phone Number Environmental Contact 1 100 Mark T Cunningham 01100013 (214) 954-6690 Jason Leik0 1 100 0 0 0 0 1 Type Code 110 (Point Source Identification)Type Code Point Source Quarter 1 - 4 Year Point Source Operating Hrs. in Quarter 1 110 3 2024 2208 1 110 0 0 0 1 Type Code 200 (Monitor Identification)Type Code Point Source Channel Manufacturer Model No. Monitor SN Low Span High Span Installation Date Monitor Location 1 200 VOC IR 8400D 5086 5000 20000 8/8/2016 VRU 1 200 0 0 0 0 0 0 1/0/1900 0 1 Type Code310 (Excess Emissions) SUMMARY REPORT Type Code Channel Total Hours of Excess Emissions Excess Emissions - % of Total Operating Hours RC 701 Hours - start up/Shutdown RC 702 Hours- Control Equipment Problems RC 703 Hours - Process Problems RC 704, 706, 707 Hours -Other Known Causes RC 705 Hours - Unknown Causes Emission Limitation Emission Limitation Units Emission Limitation Averaging Period 1 TRUE 310 VOC 0 0.00% 0 0 0 0 0 10000 ppm 6 hour RA 1 310 0 0 0 0 0 0 0 0 0 1 Type Code 300 (CMS Performance Summary) Type Code Channel Point Source Operating Hours Downtime - % of Total Operating Hours Total CMS Downtime RC 721 Hours - Monitor Malfunction RC 722 Hours - Non-monitor Malfunction RC 723 Hours - QA Calibrations RC 724 Hours - Other Known Causes RC 725 Hours - Unknown Causes 1 TRUE 300 VOC 2208 0.54% 11.95 0 0 11.77 0.18 0 1 300 0 0 0 0 0 0 1 Type Code 250 (Performance Specification RATA Results) Type Code Channel Date of Most Current RATA Date of Preceding RATA Months Between RATA's Units of Measurement CEM Value Reference Method Value Relative accuracy Pass/ Fail 1 342 Days 250 VOC 11/21/23 12/14/22 12 ppm 642 714 1.43% pass 1 0 Days 250 0 01/00/00 01/00/00 0 0 0 0 0.00% 0 1 Type Code 260 (CGA Results)Type Code Channel Date Audit Point No. Cylinder ID Cylinder Expiration Date Type of Certification Units of Measurement CEM Value Cylinder Value Precision %Pass/ Fail Range - High or Low 1 Valid Cal. Gas 260 VOC 08/26/24 1 P627795 07/09/32 Certified Master Gaspercent 5100 5110 -0.20% pass low 1 Valid Cal. Gas 260 VOC 08/26/24 2 R817032 07/10/32 Certified Master Gaspercent 10900 10960 -0.55% pass mid 1 260 0 01/00/00 0 0 01/00/00 0 0 0 0 0.00% 0 0 1 Type Code 270 (Linearity Test Results)Type Code Channel Date Audit Point No. Cylinder ID Cylinder Expiration Date Type of Certification Units of Measurement CEM Value Cylinder Value Precision %Pass/ Fail Range - High or Low 1 270 0 01/00/00 0 0 01/00/00 0 0 0 0 0.00% 0 0 1 Type Code 210 (Pollutant Concentration Exceeded Span of CEM) Type Code Channel Start Date Start Time End Date End Time Hours 1 0 0 0 1/0/00 0:00 1/0/00 0:00 1 1 None Reported 1 0 TC 220 Hours 0.00 TC 220 Hours 0.00 TC 230 Hours 0.00 Events 0.00 Hours 0.00 Events 0.00 0.00 1 11.95 TC 300 Hours 11.95 FALSE Yes None Reported None Reported None Reported None Reported None Reported Point Source Point Source Point Source Point Source Point Source Point Source Yes LOD 0 LOD LOD LOD 0 Type Code 550 (Changes in Operation in Control Equipment When CEM Data Not Available) Type Code 500 (Boiler Operating Days w/o 18 Hours of Data) Holly Energy Partners Operating, L.P. 0 Type Code 450 (Data Excluded) LOD 0 LOD 0 Type Code 210 (Pollutant Concentration Exceeded Span of CEM) Type Code 220 (Monitor Outage During Point Source Operation) Type Code 230 (Manual Sample - Alternate Sampling During Monitor Outage) Type Code 240 (CEM Modifications) Type Code 530 (Excess Emissions During Emergency Conditions) 0 LOD 0 0 0 Holly LOD EER 3Q2024 Relative Accuracy Overview Point Source Channel Date of Most Current RATA Date of Preceding RATA Months Between RATA's Units Measured CEM Value Reference Method Value Relative Accuracy Pass/ Fail LOD VOC 11/21/23 12/14/22 12 ppm 642 714.00 1.43% pass * NSPS CGA Third 2024 Audit Gas Ranges Audit Gas Ranges AP1 Low AP2 Low AP1 High AP2 High LOD VOC 8/26/24 20000 5110 4000 to 6000 LOD VOC 8/26/24 20000 10960 10000 to 12000 Point Source Channel Audit Date Low Span Audit Gas Used High Span Audit Gas Used Holly LOD EER 3Q2024 Monitoring Information TC 210, 230, & 240 Type Code 210 (Pollutant Concentration Exceeded Span of CEM) - 500 (All) * Sum of Hours Column Labels Row Labels (blank) Grand Total (blank)0 0 Grand Total 0 0 * Type Code 230 (Manual Sample - Alternate Sampling During Monitor Outage) - 500 (All) * Sum of Hours Column Labels Row Labels (blank) VOC Grand Total (blank)0 0 LOD 0 0 Grand Total 0 0 0 * Type Code 240 (CEM Modifications) - 100 (All) * Count of Channel Column Labels Row Labels (blank) Grand Total (blank) (blank) Grand Total Holly LOD EER 3Q2024 Type Code 220 (Monitor Outage During Point Source Operation) - 600 (All) * Sum of Hours Column Labels Row Labels (blank) Grand Total (blank) (blank) 0 0 LOD VOC 0 0 0 Grand Total 0 0 Holly LOD EER 3Q2024 VOC/THC * VOC/THC Type Code 460 (VOC/THC) - 6000 (All) VOC/THC * VOC/THC Count of Magnitude of Emissions Column Labels VOC/THC Row Labels 0 Grand Total VOC/THC LOD VOC/THC #N/A 1 1 VOC/THC Grand Total 1 1 Holly LOD EER 3Q2024 Type Code 500 Before February 28, 2005 (Boiler Operating Days w/o 18 Hours of Data) After February 28, 2005 (90% Operating Hours For each 30 BOD) - 500 (All) * Count of Channel Column Labels Row Labels Grand Total Grand Total * Type Code 510 (F-factor, Equations & Conversion Factors) - 500 (All) Count of F-factor Column Labels Row Labels Grand Total Grand Total * Type Code 520 (Minimum Data Not Obtained <22/30 BODs) - 500 (All) Count of Channel Column Labels Row Labels Grand Total Grand Total * Type Code 530 (Excess Emissions During Emergency Conditions) - 500 (All) Count of Date Column Labels Row Labels Grand Total Grand Total * Type Code 540 (Fuel Pre-treatment Credit SO2) - 500 (All) Count of Date Column Labels Row Labels Grand Total Grand Total * TypeCode 550 (Changes in Operation in Control Equipment When CEM Data Not Available) - 500 (All) Column Labels Row Labels Grand Total Grand Total