Loading...
HomeMy WebLinkAboutDDW-2024-013224Sanitary Survey - Deficiency Report PWS Number:UTAH29020 Deficiency Points:75 Survey Date:10/07/2024 Survey Name:UINTAH TOWN WATER SYSTEM Surveyor:Nella Forsberg Sanitary Survey Category: DS SDWIS Severity Code: Significant Deficiency Distribution | DS001 | UTAH29020 DISTRIBUTION SYSTEM 44A. Open end of vent line covered with #14 mesh screen Rule: R309-550-6(6)(b)Rule states the open end of the air relief vent pipe from automatic valves shall be provided with a #14 mesh, non-corrodible screen and a downward elbow, and where possible, be extended to at least one foot above grade. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:#1 is now compliant. The cover was cemented to the base, but it has been removed to reveal #14 screen, downturn, and greater than 12 inches above grade. #2 was compliant at survey. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: D004 AIR RELIEF VALVE PIPE LACKS NO. 14 SCREEN Sanitary Survey Category: FW SDWIS Severity Code: Significant Deficiency Storage Tanks | ST002 | BYBEE TANK 2 REPLACEMENT 81A. Overflow line discharges at least 12 inches above ground or the flood rim of receiving basin? Rule: R309-545-13 Rule requires all water storage tanks to be provided with an overflow that discharges at an elevation between 12 and 24 inches above the ground surface or the rim of the receiving basin. Notes:During the survey there was less than a 12 inch clearance present. This has been corrected. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V011 END OF STORAGE TANK OVERFLOW LACKS A CLEARANCE OF BETWEEN 12 AND 24 INCHES FROM GROUND SURFACE Sanitary Survey Category: FW SDWIS Severity Code: Significant Deficiency Storage Tanks | ST003 | BYBEE TANK 1 95A. Overflow line discharges at least 12 inches above ground or the flood rim of receiving basin? Rule: R309-545-13 Rule requires all water storage tanks to be provided with an overflow that discharges at an elevation between 12 and 24 inches above the ground surface or the rim of the receiving basin. Notes:During the survey there was less than a 12 inch clearance present. This has been corrected to greater than 12" clearance. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V011 END OF STORAGE TANK OVERFLOW LACKS A CLEARANCE OF BETWEEN 12 AND 24 INCHES FROM GROUND SURFACE