HomeMy WebLinkAboutDERR-2024-012018Utah Department of Environmental Quality - UST Release Detection
TANK OWNERSHIP
Name CLARK'S COUNTRY MARKET
Address P.O. BOX 127
TROPIC, UT 84776
Contact CLARK'S COUNTRY MARKET
Phone
Email rustlersrestaurant1@gmail.com
TANK LOCATION
Name CLARK'S COUNTRY MARKET
Address 141 N. MAIN
TROPIC, UT 84776
A Operator None
Phone None
B Operator SAME
Phone SAME
Facility ID: 6001049 Inspection Date: 10/28/2024
DISPENSER DETAILS
DISP
ID/ALT
ID
SUBSTANCE UDC PIPE FLEX LOC
INSTALL
DATE
UDC
INSTALL
DATE
FIRE
VALVE
SAT
PRESENT
UDC
TEST
DISP
FLEX
CP
TEST
1 - 1/2 Gas/Diesel No None None No No None None
2 - 3/4 Gas/Diesel No None None No No None None
TANK DETAILS
Tank ID/Alt ID 1 / 1
E-Gen/AST No / Yes
Siphon/Compart No / No
Tank Status Currently In Use
Installed/Cap/Loc Jan. 1, 1995 / 8000 /
Substance Stored Gasoline / Regular
Tank Material-Mod Asphalt Coated or Bare Steel-
ATG /
LTT Test None
LLD Test None
Pipe Material-Mod Galvanized Steel / None
Pipe type/STP Cont Pressure/Suction combo / No
STP Flex
Connectors
LLD Model
Spill/Overfill/Sm
Delivery
5 gal. Per Prod. APST Cont.
Sump / / No
PST Fund/Other
Type Yes / None
Tank/Pipe Rel Det TankLDNotListed
PipeLineTightness
CP Tank Test None
CP Pipe Test None
Tank ID/Alt ID 2 / 2
E-Gen/AST No / Yes
Siphon/Compart No / No
Tank Status Currently In Use
Installed/Cap/Loc Jan. 1, 1995 / 8000 /
Substance Stored Gasoline / Premium
Tank Material-Mod Asphalt Coated or Bare Steel-
ATG /
LTT Test None
LLD Test None
Pipe Material-Mod Galvanized Steel / None
Pipe type/STP Cont Pressure/Suction combo / No
STP Flex
Connectors
LLD Model
Spill/Overfill/Sm
Delivery
5 gal. Per Prod. APST Cont.
Sump / / No
PST Fund/Other
Type Yes / None
Tank/Pipe Rel Det TankLDNotListed
PipeLineTightness
CP Tank Test None
CP Pipe Test None
2024-10-28 Page 1 of 5
Tank ID/Alt ID 3 / 3
E-Gen/AST No / Yes
Siphon/Compart No / No
Tank Status Currently In Use
Installed/Cap/Loc Jan. 1, 1995 / 8000 /
Substance Stored Diesel / Diesel #2 (U.L.S.)
Tank Material-Mod Asphalt Coated or Bare Steel-
ATG /
LTT Test None
LLD Test None
Pipe Material-Mod Galvanized Steel / None
Pipe type/STP Cont Pressure/Suction combo / No
STP Flex
Connectors
LLD Model
Spill/Overfill/Sm
Delivery
5 gal. Per Prod. APST Cont.
Sump / / No
PST Fund/Other
Type Yes / None
Tank/Pipe Rel Det TankLDNotListed
PipeLineTightness
CP Tank Test None
CP Pipe Test None
INSPECTION COMMENTS
None
2024-10-28 Page 2 of 5
FACILITY RESPONSES
Financial Responsibility
Financial responsibility method is ok?Yes
The above accurately represents the
facility's release detection records Yes
TANK RESPONSES
Tank 1 Pressure Piping Leak Detection
Does the pressurized piping system
have a valid annual line tightness test
or valid monthly monitoring?
Yes
Tank 1 Spill/Overfill
Does the spill bucket have a valid 3-
year test, valid monthly monitoring for
DW buckets, or the tank is exempt?
Yes
Tank 2 Pressure Piping Leak Detection
Does the pressurized piping system
have a valid annual line tightness test
or valid monthly monitoring?
Yes
Tank 2 Spill/Overfill
Does the spill bucket have a valid 3-
year test, valid monthly monitoring for
DW buckets, or the tank is exempt?
Yes
Tank 3 Pressure Piping Leak Detection
Does the pressurized piping system
have a valid annual line tightness test
or valid monthly monitoring?
Yes
Tank 3 Spill/Overfill
Does the spill bucket have a valid 3-
year test, valid monthly monitoring for
DW buckets, or the tank is exempt?
Yes
Tank 1 Spill/Overfill
Tank has a spill prevention device?Yes
Are you able to visually inspect the spill
containment bucket(s) for functionality?
(i.e. are the buckets clean enough to
see cracks, etc?)
Yes
Is the spill containment bucket intact?Yes
Is the spill containment bucket(s) able
to contain a spill? (i.e. is there water,
product, debris, etc in the spill bucket
to prevent it from containing a spill?)
Yes
Tank 1 Suction Piping Leak Detection
U.S. suction piping has a valid LTT
every 3 years or monthly monitoring?Yes
Piping qualifies as Safe Suction.
(Documentation is available and
verifiable to show that piping operates
at less than atmospheric pressure, has
only one check valve (under pump),
and has proper slope of piping. If all
these criteria are met, no leak
detection is required on the piping.)
Yes
Tank 2 Spill/Overfill
Tank has a spill prevention device?Yes
Are you able to visually inspect the spill
containment bucket(s) for functionality?
(i.e. are the buckets clean enough to
see cracks, etc?)
Yes
Is the spill containment bucket intact?Yes
Is the spill containment bucket(s) able
to contain a spill? (i.e. is there water,
product, debris, etc in the spill bucket
to prevent it from containing a spill?)
Yes
Tank 2 Suction Piping Leak Detection
U.S. suction piping has a valid LTT
every 3 years or monthly monitoring?Yes
Piping qualifies as Safe Suction.
(Documentation is available and
verifiable to show that piping operates
at less than atmospheric pressure, has
only one check valve (under pump),
and has proper slope of piping. If all
these criteria are met, no leak
detection is required on the piping.)
Yes
2024-10-28 Page 3 of 5
Tank 3 Spill/Overfill
Tank has a spill prevention device?Yes
Are you able to visually inspect the spill
containment bucket(s) for functionality?
(i.e. are the buckets clean enough to
see cracks, etc?)
Yes
Is the spill containment bucket intact?Yes
Is the spill containment bucket(s) able
to contain a spill? (i.e. is there water,
product, debris, etc in the spill bucket
to prevent it from containing a spill?)
Yes
Tank 3 Suction Piping Leak Detection
U.S. suction piping has a valid LTT
every 3 years or monthly monitoring?Yes
Piping qualifies as Safe Suction.
(Documentation is available and
verifiable to show that piping operates
at less than atmospheric pressure, has
only one check valve (under pump),
and has proper slope of piping. If all
these criteria are met, no leak
detection is required on the piping.)
Yes
DISPENSER RESPONSES
Dispenser 3/4
Fire valve is anchored properly?Yes
Does the line tightness test port on the
fire valve have the manufacturers plug
installed in it? (no ball valves)
Yes
Is the fire valve located properly below
grade?Yes
Is the fire valve's fuseable link intact?Yes
Dispenser 1/2
Fire valve is anchored properly?Yes
Does the line tightness test port on the
fire valve have the manufacturers plug
installed in it? (no ball valves)
Yes
Is the fire valve located properly below
grade?Yes
Is the fire valve's fuseable link intact?Yes
MONTHLY LEAK DETECTION MONITORING
Oct '23 Nov '23 Dec '23 Jan '24 Feb '24 Mar '24 Apr '24 May '24 Jun '24 Jul '24 Aug '24 Sep '24
Tank 1 Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl
Line Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl
Tank 2 Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl
Line Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl
Tank 3 Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl
Line Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl
NON-COMPLIANCE ITEMS
All items are in compliance.
2024-10-28 Page 4 of 5
Prepared by fueloperator.com
Inspection Information
Inspector:Viehweg, Kim
Record Created:Oct. 28, 2024, 3:48 p.m.
Inspection Date:Oct. 28, 2024
2024-10-28 Page 5 of 5
Underground Storage Tank Inspection Verification Form
Facility ID:6001049
Owner Name:CLARK'S COUNTRY MARKET Facility Name:CLARK'S COUNTRY MARKET
Owner Address:P.O. BOX 127 Street Address:141 N. MAIN
TROPIC, UT 84776 TROPIC, UT 84776
Operator A:No Data / No Data / Operator B:No Data / No Data /
Owner Email:rustlersrestaurant1@gmail.com UTM Coordinates X/Y:404506 / 4164864
Disp ID/Alt
ID
Substance UDC Pipe Flex Loc Install Date UDC Install Date Fire
Valve
Sat
Present
UDC Test Disp Flex CP
Test
1 - 1/2 Gas/Diesel No No No
2 - 3/4 Gasoline No No No
Tank ID/Alt ID:1 / 1 EGen/AST/Stat
e:
No / Yes /
Yes
Pipe Material-Mod:Galvanized Steel -
Siphon/Compart:No / No PVV/StageI:Yes Pipe Type/STP Cont:Pressure/Suction combo / No
Tank Status:Currently In Use STP Flex Connectors:
Installed/Cap/Loc:1/1/1995 / 8000 / LLD Model:
Substance Stored:Gasoline / Regular Spill/Overfill/Sm deliv:5 gal. Per Prod. APST Cont. Sump / / No
Tank Material-Mod:Asphalt Coated or Bare Steel - PST Fund/Other Type:Yes /
ATG: / Tank/Pipe Rel Det:OTHER / LTT / NONE
ATG Specs: / / STP Sump Test:Spill Bk Test:09/04/2024
ATG Test:Overfill Test:
LTT Test:LLD Test:CP Tank Test:CP Pipe Test:
Tank ID/Alt ID:2 / 2 EGen/AST/Stat
e:
No / Yes /
Yes
Pipe Material-Mod:Galvanized Steel -
Siphon/Compart:No / No PVV/StageI:Yes Pipe Type/STP Cont:Pressure/Suction combo / No
Tank Status:Currently In Use STP Flex Connectors:
Installed/Cap/Loc:1/1/1995 / 8000 / LLD Model:
Substance Stored:Gasoline / Premium Spill/Overfill/Sm deliv:5 gal. Per Prod. APST Cont. Sump / / No
Tank Material-Mod:Asphalt Coated or Bare Steel - PST Fund/Other Type:Yes /
ATG: / Tank/Pipe Rel Det:OTHER / LTT / NONE
ATG Specs: / / STP Sump Test:Spill Bk Test:09/04/2024
ATG Test:Overfill Test:
LTT Test:LLD Test:CP Tank Test:CP Pipe Test:
Tank ID/Alt ID:3 / 3 EGen/AST/Stat
e:
No / Yes /
Yes
Pipe Material-Mod:Galvanized Steel -
Siphon/Compart:No / No PVV/StageI:Yes Pipe Type/STP Cont:Pressure/Suction combo / No
Tank Status:Currently In Use STP Flex Connectors:
Installed/Cap/Loc:1/1/1995 / 8000 / LLD Model:
Substance Stored:Diesel / Diesel #2 (U.L.S.)Spill/Overfill/Sm deliv:5 gal. Per Prod. APST Cont. Sump / / No
Tank Material-Mod:Asphalt Coated or Bare Steel - PST Fund/Other Type:Yes /
ATG: / Tank/Pipe Rel Det:OTHER / LTT / NONE
ATG Specs: / / STP Sump Test:Spill Bk Test:09/04/2024
ATG Test:Overfill Test:
LTT Test:LLD Test:CP Tank Test:CP Pipe Test:
11/7/2024 Page 1 of 1