HomeMy WebLinkAboutDDW-2024-013056Sanitary Survey - Deficiency Report
PWS Number:UTAH29004 Deficiency Points:115 Survey Date:10/01/2024
Survey Name:BONA VISTA WATER
DISTRICT
Surveyor:Nella Forsberg
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST002 | AIRPORT TANK #2 (2 MG)
121B. Overflow line covered with #4 mesh non-corrodible screen
Rule: R309-545-13(3)Rule requires overflow pipes to be screened with #4 mesh non-corrodible screens
installed at a location least susceptible to damage by vandalism. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:There is a small gap where the piping has broken off. This has been repaired but has been
covered with #14 instead of #4. This will be replaced with #4.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V012 END OF STORAGE TANK OVERFLOW PIPE LACKS NO. 4 SCREEN
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST008 | NO. OGDEN SMALL TANK (0.25 MG)
186. Access opening locked
Rule: R309-545-14(3)Rule requires the lid to any access opening to have a locking device. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:The tank is currently empty and dry. Two large rocks are on top of this tank but there is
currently no lock on the access opening. Bona Vista PWS states that they have disconnected
the line to the tank and are working with DDW to remove this tank from the inventory.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V029 STORAGE TANK ACCESS OPENING LACKS A LOCK
Sanitary Survey Category: FW
SDWIS Severity Code: Minor Deficiency
Storage Tanks | ST008 | NO. OGDEN SMALL TANK (0.25 MG)
190A. Mild deterioration or spalling?
Rule: R309-545-6(1) and 545-9(1)Rule requires all water storage tanks to have suitable watertight roofs and sidewalls
that shall also exclude birds, animals, insects, and excessive dust.
Notes:At least one crack and spalling present.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: V021 STORAGE TANK ROOF OR SIDEWALLS SHOW SIGNS OF MILD OR MODERATE
DETERIORATION
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST009 | NO OGDEN 3 MG TANK
204B. Severe deterioration or spalling?
Rule: R309-545-6(1) and 545-9(1)Rule requires all water storage tanks to have suitable watertight roofs and sidewalls
that shall also exclude birds, animals, insects, and excessive dust. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:Water is seeping out of up to 4 cracks. DDW considers this severe.
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V022 STORAGE TANK ROOF OR SIDEWALLS SHOW SIGNS OF SEVERE
DETERIORATION