HomeMy WebLinkAboutDDW-2024-013056Sanitary Survey - Deficiency Report PWS Number:UTAH29004 Deficiency Points:115 Survey Date:10/01/2024 Survey Name:BONA VISTA WATER DISTRICT Surveyor:Nella Forsberg Sanitary Survey Category: FW SDWIS Severity Code: Significant Deficiency Storage Tanks | ST002 | AIRPORT TANK #2 (2 MG) 121B. Overflow line covered with #4 mesh non-corrodible screen Rule: R309-545-13(3)Rule requires overflow pipes to be screened with #4 mesh non-corrodible screens installed at a location least susceptible to damage by vandalism. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:There is a small gap where the piping has broken off. This has been repaired but has been covered with #14 instead of #4. This will be replaced with #4. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V012 END OF STORAGE TANK OVERFLOW PIPE LACKS NO. 4 SCREEN Sanitary Survey Category: FW SDWIS Severity Code: Significant Deficiency Storage Tanks | ST008 | NO. OGDEN SMALL TANK (0.25 MG) 186. Access opening locked Rule: R309-545-14(3)Rule requires the lid to any access opening to have a locking device. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:The tank is currently empty and dry. Two large rocks are on top of this tank but there is currently no lock on the access opening. Bona Vista PWS states that they have disconnected the line to the tank and are working with DDW to remove this tank from the inventory. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V029 STORAGE TANK ACCESS OPENING LACKS A LOCK Sanitary Survey Category: FW SDWIS Severity Code: Minor Deficiency Storage Tanks | ST008 | NO. OGDEN SMALL TANK (0.25 MG) 190A. Mild deterioration or spalling? Rule: R309-545-6(1) and 545-9(1)Rule requires all water storage tanks to have suitable watertight roofs and sidewalls that shall also exclude birds, animals, insects, and excessive dust. Notes:At least one crack and spalling present. Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: V021 STORAGE TANK ROOF OR SIDEWALLS SHOW SIGNS OF MILD OR MODERATE DETERIORATION Sanitary Survey Category: FW SDWIS Severity Code: Significant Deficiency Storage Tanks | ST009 | NO OGDEN 3 MG TANK 204B. Severe deterioration or spalling? Rule: R309-545-6(1) and 545-9(1)Rule requires all water storage tanks to have suitable watertight roofs and sidewalls that shall also exclude birds, animals, insects, and excessive dust. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Water is seeping out of up to 4 cracks. DDW considers this severe. Deficiency Points: 50 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V022 STORAGE TANK ROOF OR SIDEWALLS SHOW SIGNS OF SEVERE DETERIORATION