HomeMy WebLinkAboutDDW-2024-013023Sanitary Survey - Deficiency Report
PWS Number:UTAH24014 Deficiency Points:55 Survey Date:10/31/2024
Survey Name:OURAY PARK WATER
IMPROVEMENT DISTRICT
Surveyor:Joe Hadlock
Sanitary Survey Category: DS
SDWIS Severity Code: Significant Deficiency
Distribution | DS001 | UTAH24014 DISTRIBUTION SYSTEM
44A. Open end of vent line covered with #14 mesh screen
Rule: R309-550-6(6)(b)Rule states the open end of the air relief vent pipe from automatic valves shall be
provided with a #14 mesh, non-corrodible screen and a downward elbow, and where
possible, be extended to at least one foot above grade. This significant deficiency must
be corrected within 120 days of notification or have a corrective action plan approved
by DDW.
Notes:One of the air vents was missing a screen.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: D004 AIR RELIEF VALVE PIPE LACKS NO. 14 SCREEN
Sanitary Survey Category: FW
SDWIS Severity Code: Minor Deficiency
Storage Tanks | ST002 | STORAGE FACILITY ST002
79A. Mild deterioration or spalling?
Rule: R309-545-6(1) and 545-9(1)Rule requires all water storage tanks to have suitable watertight roofs and sidewalls
that shall also exclude birds, animals, insects, and excessive dust.
Notes:There were a few cracks in the lid that needed patched.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: V021 STORAGE TANK ROOF OR SIDEWALLS SHOW SIGNS OF MILD OR MODERATE
DETERIORATION
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Treatment - Chlorination General | TP001 | CHLORINATOR
111. Solution tanks and tank refilling line entry points are properly labeled to identify the chemicals
Rule: R309-525-11(8)(c)(vii)Rule requires tanks to be properly labeled to designate the chemical contained.
Notes:tank was not labeled.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TG03 SOLUTION TANKS AND CHEMICAL REFILL LINES NOT LABELED