Loading...
HomeMy WebLinkAboutDDW-2024-012809Utah Department of Environmental Quality Division of Drinking Water Minimum Sizing Standards Date Standard Effective: Tue Jan 30 12:16:08 MST 2024 Peak Day Source Demand per ERC (gal/day): 1,359 Average Annual Demand per ERC (gal/day): 273,359 Equalization Storage per ERC (gal/day): 747 SMITHFIELD CITY PWS ID: UTAH03020 Admin Name: JOSHUA DANIEL WRIGHT Address: City, State, Zip: , Phone: 435-563-6226 Email: JWRIGHT@SMITHFIELDCITY.ORG System Type: Community Population: 10,223 DRAFT MINIMUM SIZING STANDARD MINIMUM SIZING STANDARD CALCULATIONS VARIABILITY Data from these reporting years: 2018, 2019, 2020, 2021, 2022, 2023 Peak Day Source Demand per ERC (gal/day): 1,359 Average Annual Demand per ERC (gal/year): 273,359 Equalization Storage per ERC (gal): 747 x x x (1 + 0.0) (1 + 0.0) (1 + 0.0) = = = 1,359 273,359 747 DWRi WATER USE DATA REPORTED Equalization per ERC (gal): 747 Existing Storage (gal): 4,000,000 ERCs: 4,869 Required Storage w/o Fire Flow: 3,637,143 Required Fire Storage (gal): 840,000 Required Storage w/Fire (gal): 4,477,143 Storage Deficiency: 477,143 Storage Deficiency (%): 10.7 Storage Deficient from Fire Requirement Year Peak Day Source Demand (gal/day) Average Annual Demand (gallons) ERCs Peak Demand per ERC (gal/day) Avg Annual Demand per ERC (gal/day) Equaliza tion Storage per ERC (gal/day) OP Days 2023 5,777,338 1,211,582,446.71 4,869 1,187 248,861 682 365 2022 5,301,595 1,053,883,596.75 4,862 1,091 216,778 594 365 2021 4,949,676 1,012,207,253.85 4,691 1,055 215,762 591 365 2020 6,073,862 1,221,498,092.64 4,468 1,359 273,359 747 366 2019 5,914,195 1,133,573,717.31 4,405 1,343 257,348 705 365 2018 5,585,086 1,074,578,393.76 4,395 1,271 244,512 670 365 Variability:0.108 0.0 0.0 0.0 Year Peak Month Average (gal/day) Peak Month Average per ERD (gal/day) Ratio of PD/ERC to Peak Month Avg/ERC 2023 5,501,100 1,130 1.05 2022 4,234,381 871 1.25 2021 4,702,450 1,002 1.05 2020 5,213,931 1,167 1.16 2019 5,397,564 1,225 1.1 2018 5,600,748 1,274 1 CAPACITY CALCULATIONS FOR STORAGE CAPACITY CALCULATIONS FOR SOURCES Peak Day Source Demand per ERC (gpm): 0.94 Existing Source Capacity (gpm): 5,287 ERCs: 4,869 Required Source Capacity (gpm): 4,577 Source Deficiency: 0 Source Deficiency (%): 0.0 No Source Deficiency SYSTEM STORAGE AND SOURCE INVENTORY Storage ID Storage Name Effective Volume (GAL) ST001 SMITHFIELD CANYON 1 MG (UPPER) TANK 1,000,000 ST002 PARSONS TANK 1MG 1,000,000 ST003 1/2 MG TANK INTERTIED TO ST002 (LOWER)500,000 ST004 DRY CANYON RESERVOIR 1.5 MG 1,500,000 Storage Totals: 4,000,000 GAL Source ID Source Name Flow Rate (GPM) WS004 FORRESTER ACRES WELL 1,100 WS005 BIRCH WELL 733 WS001 SMITHFIELD CANYON SPRINGS (8)1,139.3 WS002 MILES SPRING 101.5 WS003 PETERSEN SPRING 214.8 WS006 CENTRAL PARK WELL 2,000 Source Totals: 5,287 GPM