HomeMy WebLinkAboutDDW-2024-012805Sanitary Survey - Deficiency Report PWS Number:UTAH03020 Deficiency Points:15 Survey Date:10/29/2024 Survey Name:SMITHFIELD CITY Surveyor:Cameron Draney Sanitary Survey Category: FW SDWIS Severity Code: Minor Deficiency Management and Operations | DS001 | UTAH03020 DISTRIBUTION SYSTEM 29A. System lacks required storage capacity due to fire demand Rule: R309-510-8(1)(b)Rule requires a public water system to provide equalization storage volume (to meet average day demands for indoor and irrigation water use), fire flow storage volume (if equipped with fire hydrants for fire suppression or required by the local fire code official), and emergency storage (if deemed appropriate by the water system or the Director). Notes:The current draft calculations based on 2021-2023 system data shows a storage deficiency of 477,143 gallons. Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: VF34 SYSTEM LACKS REQUIRED STORAGE CAPACITY DUE TO FIRE DEMAND BUT HAS SOP FOR FOLLOWING FIRE INCIDENT