HomeMy WebLinkAboutDERR-2024-011754GEORGE STURM
UTAH STATE FUEL NETWORK
4315 S 2700 W
SALT LAKE CITY, UT 84129
RE:Request for Petroleum Storage Tank Records
USU BLDG 50 HEATING PLANT, located at APPROX 950 N 900 E, LOGAN
Facility Identification No. 0100633
Dear GEORGE STURM:
PST operators are required to ensure that certain tests are conducted for their tank system.
Dates highlighted in "Yellow" - tests are due soon.
Dates highlighted in "Red" - tests are due and you are out of compliance.
Tank ID/Alt
ID
Description LTT
--------------------
LLD
Spill Bucket
--------------------
Overfill
Tank or Flex
--------------------
Pipe CP
ATG
--------------------
Sump
1/1 Diesel-Diesel #2 (U.L.S.)-20000 N/A N/A N/A 12/8/2024
N/A N/A N/A N/A
2/2 Diesel-Diesel #2 (U.L.S.)-20000 N/A N/A N/A 12/8/2024
N/A N/A N/A N/A
3/3 Diesel-Diesel #2 (U.L.S.)-20000 N/A N/A N/A 12/8/2024
N/A N/A N/A N/A
4/4 Diesel-Diesel #2 (U.L.S.)-20000 N/A N/A N/A 12/8/2024
N/A N/A N/A N/A
5/5 Diesel-Diesel #2 (U.L.S.)-20000 N/A N/A N/A 12/8/2024
N/A N/A N/A N/A
6/6 Diesel-Diesel #2 (U.L.S.)-20000 N/A N/A N/A 12/8/2024
195 North 1950 West - Salt Lake City, UT
Mailing Address: - P.O. Box 144840 - Salt Lake City, UT 84114-4840
Telephone (801) 536-4100 - Fax (801) 359-8853 - T.D.D. (801) 536-4414
www.deq.utah.gov
Printed on 100% recycled paper
October 17, 2024
State of Utah
SPENCER J. COX
Governor
DEIDRE HENDERSON
Lieutenant Governor
Department of
Environmental Quality
Kimberly D. Shelley
Executive Director
DIVISION OF ENVIRONMENTAL
RESPONSE AND REMEDIATION
Brent H. Everett
Director
N/A N/A N/A N/A
LTT - Line Tightness Test
LLD - Line Leak Detector
Overfill ±Overfill Device
Tank or Flex/Pipe CP - Corrosion Tests
ATG ±Automatic Tank Gauging
Sump - Tank Top Sump and applicable Dispenser Sumps
Please note that UDC tests are not listed, but are required on your facility's next sump test
cycle starting July 1, 2023, if applicable. Also, effective immediately pressure vent valves
must be tested every three years for gasoline tanks.
Please submit a copy of the required tests to the DERR within 30 days of the date due.
If you have any questions please call DeAnn Rasmussen at 801-536-4100.
195 North 1950 West - Salt Lake City, UT
Mailing Address: - P.O. Box 144840 - Salt Lake City, UT 84114-4840
Telephone (801) 536-4100 - Fax (801) 359-8853 - T.D.D. (801) 536-4414
www.deq.utah.gov
Printed on 100% recycled paper
October 17, 2024
State of Utah
SPENCER J. COX
Governor
DEIDRE HENDERSON
Lieutenant Governor
Department of
Environmental Quality
Kimberly D. Shelley
Executive Director
DIVISION OF ENVIRONMENTAL
RESPONSE AND REMEDIATION
Brent H. Everett
Director
APPLIED ENVIRONMENTAL SERVICES, L.C.
PO BOX 1073 BOUNTIFUL, UTAH 84011 801-540-9258
TEI 5000 NON VOLUMETRIC, TEI 4000 VOLUMETRIC, TEI ULLAGE, TEI LT3
PRECISION TANK & LINE TEST RESULTS SUMMARY
INVOICE ADDRESS:TANK LOCATION: WORK ORDER #
TECH # 94027
TECHNICIAN: SM
STATE TECH #
STATE FUEL NETWORK
PO BOX 141152
SALT LAKE CITY, UTAH 84141-1152
UTAH STATE UNIVERSITY
HEATING PLANT
LOGAN, UTAH
24120
UT 0121
DATE:
10-16-2024
TIME START:
10:00
TIME END:
17:00
GROUNDWATER DEPTH:
N/A DW TKS
TANK TANK
CAPACITY
19951
19951
19951
19951
19951
19951
PRODUCT
DSL
DSL
DSL
DSL
DSL
DSL
TANK
PASS
PASS
PASS
PASS
PASS
PASS
VENT
PASS
PASS
PASS
PASS
PASS
PASS
PRODUCT
LINE
PASS
PASS
PASS
PASS
PASS
PASS
LINE LEAK
DETECTOR
N/A
N/A
N/A
N/A
N/A
N/A
WATER IN
TANK
0.0"
0.0"
0.0"
0.0"
0.0"
0.0"
PUMP
TYPE
SUCTION
SUCTION
SUCTION
SUCTION
SUCTION
SUCTION
TANK
MATERIAL
DWF
DWF
DWF
DWF
DWF
DWF
1.
2.
3.
4.
5.
6.
PRODUCT LINES TESTED AT 20 PSI FOR 15 MIN
LINE RATES (GPH)
1.
2.
3.
5.
6.
DSL SUPPLY -.033
ADDITIONAL INFORMATION:ALL RETURN LINES AND REMOTE FILLS TESTED WITH TANKS
ALL SUPPLY LINES ARE MANIFOLDED INTO ONE LINE IN BOILER PLANT / EMERGENCY GENERATOR
CERTIFIED TECHNICIAN SIGNATURE:DATE:10-16-2024
These systems meet all requirements set forth by USEPA 40 CFR and has received third party certification.
4.
TEST METHODS USED FOR THIS LOCATION
TEI 5000 NON VOLUMETRIC TANK TEST TEI 4000 VOLUMETRIC TANK TEST TEI TANK ULLAGE TEST TEI LT3 LINE TESTX X
LINE LEAK DETECTOR TYPE & SIMULATED LEAK RATE
1.
2.
3.
M = MECHANICAL E = ELECTRONIC # = (GPH) RATE
4.
5.
6.
All tests were performed according to manufacturer protocol, and within the common practices of the industry. However due to the variables of
tightness testing, these results cannot be guaranteed. There are no warranties expressed, written or implied.
DEQ ID#0100633
Digitally signed by STEVEN B MARTIN
cn=STEVEN B MARTIN, o=AES, c=US
Date: 2024.10.17 10:18:35 -07'00'
Reason: I am the author of this document
UTAH STATE UNIVERSITY
BOILER PLANT
LOGAN, UTAH
0100633
APPLIED ENVIRONMENTAL SERVICES
STATE FUEL NETWORK
PO BOX 141152
SALT LAKE CITY, UT 84141
BRETT GURNEY
801-540-9258 10-16-2024
1
DSL
TLS 350
19951
119.51
X
X
X
X
X
100
18151
90.97
X
X
X
X
2
DSL
TLS 350
19951
119.51
X
X
X
X
X
100
18151
90.97
X
X
X
X
APPLIED ENVIRONMENTAL SERVICES, L.C. PO BOX 1073 BOUNTIFUL, UTAH 84011
801-540-9258 AESUTAH@AOL.COM
3 / 4
DSL/DSL
TLS 350
19951/19951
119.51/119.51
XX
XX
XX
XX
XX
100/100
18151/18151
90.97/90.97
XX
XX
XX
XX
5 / 6
DSL/DSL
TLS350
19951/19951
119.51/119.51
XX
XX
XX
XX
XX
100/100
18151/18151
90.97/90.97
XX
XX
XXX
XX
STEVEN B MARTIN
Digitally signed by STEVEN B MARTIN
cn=STEVEN B MARTIN, o=AES, c=US
Date: 2024.10.17 10:22:13 -07'00'
Reason: I am the author of this document
UTAH STATE UNIVERSITY
BOILER PLANT
LOGAN, UTAH
0100633
APPLIED ENVIRONMENTAL SERVICES
STATE FUEL NETWORK
PO BOX 141152
SALT LAKE CITY, UTAH 84141-1152
BRETT GURNEY 385-602-4872
801-540-9258 10-16-2024
TK1 PIPING
DSL
X
X
X
X
X
X
X
X
TK1 FILL
DSL
X
X
X
X
X
X
X
X
TK2 PIPING
DSL
X
X
X
X
X
X
X
X
TK2 FILL
DSL
X
X
X
X
X
X
X
X
TK3 PIPING
DSL
X
X
X
X
X
X
X
X
TK3 FILL
DSL
X
X
X
X
X
X
X
X
PAGE 1 OF 2
REMOTE FILLS RUN TO FILL SUMPS
STEVEN B MARTIN
APPLIED ENVIRONMENTAL SERVICES, L.C. PO BOX 1073 BOUNTIFUL, UTAH 84011
801-540-9258 AESUTAH@AOL.COM
Digitally signed by STEVEN B MARTIN
cn=STEVEN B MARTIN, o=AES, c=US
Date: 2024.10.17 10:24:20 -07'00'
Reason: I am the author of this document
AUTOMATIC TANK GAUGE OPERATION INSPECTION
Facility Name:
Address:
City, State, Zip Code:
Facility I.D. #
Testing Company:
Owner:
Address:
City, State, Zip Code:
Phone #
Testers Phone #
Date:
This procedure is to determine whether the ( ATG) is operating properly. See PEI/RP1200 Section 8.2 for the proper inspection procedure.
Tank Number
Product Stored:
ATG Brand and Model
1. Tank Volume, gallons
2. Tank Diameter, inches
3. After removing the ATG from the tank, has it
been inspected and any damaged or missing
parts replaced?
4. Float moves freely on the stem without
5. Fuel float level agrees with the
value programmed into the console?
6. Water float level agrees with the value
programmed into the console?
7. Inch level from bottom of stem when 90%
alarm is triggered.
8. Inch level at which the overfill alarm
activates corresponds with value programmed
in the gauge?
9. Inch level from the bottom when the water
float first triggers an alarm.
10. Inch level at which the float alarm activates
corresponds with value programmed in the
gauge?
If any answers in Lines 3,4,5, or 6 are "NO" the system has failed the test.
TEST RESULTS
Comments:
Testers Name: Steven B. Martin Testers Signature:
UTAH STATE UNIVERSITY
CENTRAL HEAT PLANT
LOGAN, UTAH
100633
AES UTAH TESTER # UT 0121
STATE FUEL NETWORK
PO BOX 141152
SALT LAKE CITY, UTAH 84141-1152
BRETT GURNEY 385-602-4872
801-540-9258
10-16-2024
1
DSL
TLS 350
19951
119.60
YES
YES
YES
YES
100
YES
2.0
YES
2
DSL
TLS 350
19951
119.50
YES
YES
YES
YES
100
YES
2.0
YES
PASS PASS PASS PASS PASS/PASS
3
DSL
TLS 350
19951
119.50
YES
YES
YES
YES
100
YES
2.0
YES
4
DSL
TLS 350
19951
119.50
YES
YES
YES
YES
100
YES
2.0
YES
5 / 6
DSL/DSL
TLS350
19951/19951
119.5/119.5
YES/YES
YES/YES
YES/YES
YES/YES
100/100
YES/YES
2.0/2.0
YES/YES
BATTERY BACKUP FUNCTIONS PROPERLY
Digitally signed by STEVEN B MARTIN
cn=STEVEN B MARTIN, o=AES, c=US
Date: 2024.10.17 10:20:27 -07'00'
Reason: I am the author of this document
AUTOMATIC TANK GAUGE OPERATION INSPECTION
Facility Name:
Address:
City, State, Zip Code:
Facility I.D. #
Testing Company:
Owner:
Address:
City, State, Zip Code:
Phone #
Testers Phone #
Date:
This procedure is to determine whether the ( ATG) is operating properly. See PEI/RP1200 Section 8.2 for the proper inspection procedure.
Tank Number
Product Stored:
ATG Brand and Model
1. Tank Volume, gallons
2. Tank Diameter, inches
3. After removing the ATG from the tank, has it
been inspected and any damaged or missing
parts replaced?
4. Float moves freely on the stem without
5. Fuel float level agrees with the
value programmed into the console?
6. Water float level agrees with the value
programmed into the console?
7. Inch level from bottom of stem when 90%
alarm is triggered.
8. Inch level at which the overfill alarm
activates corresponds with value programmed
in the gauge?
9. Inch level from the bottom when the water
float first triggers an alarm.
10. Inch level at which the float alarm activates
corresponds with value programmed in the
gauge?
If any answers in Lines 3,4,5, or 6 are "NO" the system has failed the test.
TEST RESULTS
Comments:
Testers Name: Steven B. Martin Testers Signature:
UTAH STATE UNIVERSITY
CENTRAL HEAT PLANT
LOGAN, UTAH
100633
AES UTAH TESTER # UT 0121
STATE FUEL NETWORK
PO BOX 141152
SALT LAKE CITY, UTAH 84141-1152
BRETT GURNEY 385-602-4872
801-540-9258
10-16-2024
1
DSL
TLS 350
19951
119.60
YES
YES
YES
YES
100
YES
2.0
YES
2
DSL
TLS 350
19951
119.50
YES
YES
YES
YES
100
YES
2.0
YES
PASS PASS PASS PASS PASS/PASS
3
DSL
TLS 350
19951
119.50
YES
YES
YES
YES
100
YES
2.0
YES
4
DSL
TLS 350
19951
119.50
YES
YES
YES
YES
100
YES
2.0
YES
5 / 6
DSL/DSL
TLS350
19951/19951
119.5/119.5
YES/YES
YES/YES
YES/YES
YES/YES
100/100
YES/YES
2.0/2.0
YES/YES
BATTERY BACKUP FUNCTIONS PROPERLY
Digitally signed by STEVEN B MARTIN
cn=STEVEN B MARTIN, o=AES, c=US
Date: 2024.10.17 10:20:27 -07'00'
Reason: I am the author of this document