HomeMy WebLinkAboutDAQ-2024-011223 1 DAQC-1064-24 Site ID 10237 (B5) MEMORANDUM TO: FILE – PACIFICORP – Hunter Power Plant THROUGH: Harold Burge, Major Source Compliance Section Manager FROM: Rob Leishman, Environmental Scientist DATE: October 17, 2024 SUBJECT: PacifiCorp Hunter Power Plant (Hunter), Major, NSPS, Emery County, FRS # UT0000004901500101 INSPECTION TYPE: State Electronic Data Report (SEDR) Review REVIEW DATE: October 17, 2024 SOURCE LOCATION: Castle Dale/Emery County SOURCE CONTACT: Terry Guthrie – 435-748-6059 Jay Howard – 435-748-6519 APPLICABLE REGULATIONS: Title V Operating Permit PERMIT NUMBER: 1500101004 DATE OF PERMIT: September 4, 2020 Date of Last Revision: November 19, 2021 SOURCE REVIEW EVALUATION: SOURCE INSPECTION EVALUATION: With the exception of sources that only monitor for opacity, quarterly report memoranda will only address the findings of the quarterly report. Approval Order and Title V permit conditions addressing continuous emission monitoring requirements will be addressed in Hunter’s relative accuracy performance specification test review memorandum. SEDR Review: Third Quarter 2024 % Monitor Availability (MA) Performance Test Dates (N/A to Opacity) Summary of Excess Emissions During Point Source Operation Point Source Op. hrs. Channel MA CGA Lin RATA Point Source Channel Hrs. Limitation 1 2208 SO2 99% 08/19/24 10/19/23 1 SO2 0.00 1.2 lb/MMBtu - 3 hr ra 1 2208 NOx 97% 08/19/24 10/19/23 1 SO2 0.00 0.12 lb/MMBtu - 30 DRA 1 8 2 2 Third Quarter 2024 % Monitor Availability (MA) Performance Test Dates (N/A to Opacity) Summary of Excess Emissions During Point Source Operation Point Source Op. hrs. Channel MA CGA Lin RATA Point Source Channel Hrs. Limitation 1 2208 CO2 99% 08/19/24 10/19/23 1 SO2 0.00 0.2 lb/MMBtu - 30 DRA 1 2208 Opacity 99% 1 NOx 0.00 0.7 lb/MMBtu - 3 hr ra 1 2208 CO 97% 08/19/24 10/19/23 1 NOx 0.00 0.26 lb/MMBtu - 30 DRA 2 2207 SO2 100% 08/20/24 05/02/24 1 Opacity 0.00 20 Percent - 6 min 2 2207 NOx 99% 08/20/24 05/02/24 1 CO 0.00 3990 lb/hr - 8 hr Block Ave 2 2207 CO2 100% 08/20/24 05/02/24 1 CO 0.00 0.34 lb/MMBtu - 30 DRA 2 2207 Opacity 99% 2 SO2 0.00 1.2 lb/MMBtu - 3 hr ra 2 2207 CO 100% 08/20/24 05/02/24 2 SO2 0.00 0.12 lb/MMBtu - 30 DRA 3 2079 SO2 99% 08/26/24 10/25/23 2 SO2 0.00 0.2 lb/MMBtu - 30 DRA 3 2079 NOx 97% 08/26/24 10/25/23 2 NOx 0.00 0.7 lb/MMBtu - 3 hr ra 3 2079 CO2 99% 08/26/24 10/25/23 2 NOx 0.00 0.26 lb/MMBtu - 30 DRA 3 2079 Opacity 99% 2 Opacity 0.00 20 Percent - 6 min 3 2079 CO 99% 08/26/24 10/25/23 2 CO 0.00 3990 lb/hr - 8 hr Block Ave 2 CO 0.00 0.34 lb/MMBtu - 30 DRA 3 SO2 0.00 0.12 lb/MMBtu - 30 DRA 3 SO2 0.00 0.2 lb/MMBtu - 30 DRA 3 NOx 0.00 0.34 lb/MMBtu - 30 DRA 3 Opacity 0.00 20 Percent - 6 min 3 CO 0.00 0.2 lb/MMBtu - 30 DRA 3 CO 0.00 2406 lb/hr - 8 hr Block Ave Summary of SO2 Emission Reduction Percent Removal Required % Reduction Point Source Channel Min Max Days in violation Status 1 SO2 94% 95% 80% 0 In compliance 2 SO2 94% 96% 80% 0 In compliance 3 SO2 94% 95% 90% 0 In compliance 3 Excess Emission Report - Hourly Summary Point Source Channel Startup & Shutdown Control Equipment Problems Process Problems Other Known Causes Unknown Causes Emission Limit 1 SO2 0 0 0 0 0 1.2 lb/MMBtu - 3 hr ra 1 SO2 0 0 0 0 0 0.12 lb/MMBtu - 30 DRA 1 SO2 0 0 0 0 0 0.2 lb/MMBtu - 30 DRA 1 NOx 0 0 0 0 0 0.7 lb/MMBtu - 3 hr ra 1 NOx 0 0 0 0 0 0.26 lb/MMBtu - 30 DRA 1 Opacity 0 0 0 0 0 20 Percent - 6 min 1 CO 0 0 0 0 0 3990 lb/hr - 8 hr Block Ave 1 CO 0 0 0 0 0 0.34 lb/MMBtu - 30 DRA 2 SO2 0 0 0 0 0 1.2 lb/MMBtu - 3 hr ra 2 SO2 0 0 0 0 0 0.12 lb/MMBtu - 30 DRA 2 SO2 0 0 0 0 0 0.2 lb/MMBtu - 30 DRA 2 NOx 0 0 0 0 0 0.7 lb/MMBtu - 3 hr ra 2 NOx 0 0 0 0 0 0.26 lb/MMBtu - 30 DRA 2 Opacity 0 0 0 0 0 20 Percent - 6 min 2 CO 0 0 0 0 0 3990 lb/hr - 8 hr Block Ave 2 CO 0 0 0 0 0 0.34 lb/MMBtu - 30 DRA 3 SO2 0 0 0 0 0 0.12 lb/MMBtu - 30 DRA 3 SO2 0 0 0 0 0 0.2 lb/MMBtu - 30 DRA 3 NOx 0 0 0 0 0 0.34 lb/MMBtu - 30 DRA 3 Opacity 0 0 0 0 0 20 Percent - 6 min 3 CO 0 0 0 0 0 0.2 lb/MMBtu - 30 DRA 3 CO 0 0 0 0 0 2406 lb/hr - 8 hr Block Ave CMS Performance Summary - Hourly Summary Point Source Channel Monitor Malfunction Non-monitor Malfunction QA Calibrations Other Known Causes Unknown Causes 1 SO2 0 0 5 18 0 1 NOx 46 0 9 13 0 1 CO2 0 0 5 18 0 1 Opacity 1 0 11 1 0 1 CO 24 0 15 25 0 2 SO2 0 0 5 2 0 2 NOx 9 0 2 2 0 2 CO2 0 0 2 2 0 2 Opacity 2 0 10 2 0 4 CMS Performance Summary - Hourly Summary Point Source Channel Monitor Malfunction Non-monitor Malfunction QA Calibrations Other Known Causes Unknown Causes 2 CO 0 0 2 2 0 3 SO2 0 0 1 10 0 3 NOx 57 0 1 1 0 3 CO2 0 0 1 10 0 3 Opacity 0 0 10 3 0 3 CO 0 0 1 10 0 Type Code 280 (COMS Attenuator Filters) Procedure 3 Point Source & Location Attenuator I.D. Attenuator Certification Date Certified Attenuator Opacity OPLR, SECR, or PLCF, Corrected Opacity Value Range Low, Mid, & High Certification 1-year or 5-year Unit 1 - 1A S13263 6/28/24 17.40 1.00 17.4 Low 1 Unit 1 - 1A S13268 6/28/24 26.60 1.00 26.6 Mid 1 Unit 1 - 1A S13249 6/28/24 46.90 1.00 46.9 High 1 Unit 1 - 1B S13263 6/28/24 17.40 1.00 17.4 Low 1 Unit 1 - 1B S13268 6/28/24 26.60 1.00 26.6 Mid 1 Unit 1 - 1B S13249 6/28/24 46.90 1.00 46.9 High 1 Unit 2 - 2A S13263 6/28/24 17.40 1.00 17.4 Low 1 Unit 2 - 2A S13268 6/28/24 26.60 1.00 26.6 Mid 1 Unit 2 - 2A S13249 6/28/24 46.90 1.00 46.9 High 1 Unit 2 - 2B S13263 6/28/24 17.40 1.00 17.4 Low 1 Unit 2 - 2B S13268 6/28/24 26.60 1.00 26.6 Mid 1 Unit 2 - 2B S13249 6/28/24 46.90 1.00 46.9 High 1 Unit 3 - 3 S13263 6/28/24 17.40 1.00 17.4 Low 1 Unit 3 - 3 S13268 6/28/24 26.60 1.00 26.6 Mid 1 Unit 3 - 3 S13249 6/28/24 46.90 1.00 46.9 High 1 Unit 3 - 3 S13263 6/28/24 17.40 1.00 17.4 Low 1 Unit 3 - 3 S13268 6/28/24 26.60 1.00 26.6 Mid 1 Unit 3 - 3 S13249 6/28/24 46.90 1.00 46.9 High 1 Type Code 281 (Procedure 3 - COMS Filter Audit Calibration Error) Point Source Location Audit Date Opacity Monitor Response (Average of 5) Mean Difference Calibration Error (≤ 3%) Low Mid High Unit 1 1A 7/15/24 18 -0.320 0.005 Unit 1 1A 7/15/24 26 -0.660 0.011 5 Type Code 281 (Procedure 3 - COMS Filter Audit Calibration Error) Point Source Location Audit Date Opacity Monitor Response (Average of 5) Mean Difference Calibration Error (≤ 3%) Low Mid High Unit 1 1A 7/15/24 48 0.780 0.011 Unit 1 1B 7/15/24 17 -0.100 0.009 Unit 1 1B 7/15/24 27 -0.130 0.018 Unit 1 1B 7/15/24 47 -0.160 0.013 Unit 2 2A 7/16/24 17 -0.150 0.008 Unit 2 2A 7/16/24 25 -0.940 0.010 Unit 2 2A 7/16/24 47 0.400 0.004 Unit 2 2B 7/16/24 18 0.910 0.012 Unit 2 2B 7/16/24 27 -0.130 0.004 Unit 2 2B 7/16/24 48 1.120 0.025 Unit 3 3 7/22/24 17 -0.050 0.001 Unit 3 3 7/22/24 27 0.140 0.012 Unit 3 3 7/22/24 48 0.980 0.010 Unit 3 3 7/22/24 17 -0.630 0.009 Unit 3 3 7/22/24 25 -1.240 0.017 Unit 3 3 7/22/24 48 0.630 0.008 Type Code 282 (Annual Zero Alignment Audit) Procedure 3 Point Source Location Audit Date Alternative Zero Alignment (Yes or No) COM Clear Condition Zero Response (CCZR) COM Simulated Zero Response (CSZR) Zero Alignment Error Difference (CCZR)- (CSZR) Adjustment to COM Simulated Zero Response (CSZR) (Yes or No) 1 1A 2/12/24 no 0.25 0.03 0 yes 1 1B 2/12/24 no -2.35 -0.03 -2 yes 2 2A 2/6/24 no 100.00 -0.02 100 yes 2 2B 2/6/24 no 0.83 -0.15 1 yes 3 3A 3/6/24 no 0.49 0.04 0 yes 3 3B 3/5/24 no 0.35 -0.07 0 yes Summary of SO2 Emission Reduction Percent Removal Required Percent Reduction Point Source Channel Min Max Days in violation 1 SO2 94% 95% 80% 0 2 SO2 94% 96% 80% 0 3 SO2 94% 95% 90% 0 6 Pollutant Concentration Exceeded Span of CEM Monitor Outage During Point Source Operation Alternate Sampling CEM Modifications 0 Hours 333 Hours 0 Hours 0 Events SOURCE INSPECTION SUMMARY EVALUATION: PacifiCorp Hunter Power Plant maintains its CEMS as required in R307-170 and 40 CFR 60.13. CURRENT RECOMMENDATIONS: All deviations appear to be a result of breakdown or process related problems that do not warrant issuing a violation. Periods of excess emissions that were recorded by the CMS in service on each point source during this reporting period are summarized in the SEDR and described in Pivot Table 400 “Excess Emissions Review.” Hunter Power Plant was in compliance during this reporting period. No further enforcement actions should be taken. Hunter’s NSPS monitoring system meets the performance standards of 40 CFR 60, Appendix B Performance Specifications. Hunter’s acid rain monitoring system meets the performance standards of 40 CFR 75 Acid Rain Performance Specifications. HIGH PRIORITY VIOLATOR (HPV): No RECOMMENDATION FOR NEXT INSPECTION: Check DAS for daily zero and span drift. Check the QC program to ensure that monitor drift is being tracked and that the source can identify excessive drift. ATTACHMENTS: Excel spreadsheet review Pacificorp Hunter EER 3Q2024 Point Source Information Late Expired Cal. Gas Valid Cal. Gas Days Yes No 1 Type Code 100 (Company Information)Type Code Company Manager Company Name AIRS # Phone Number Environmental Contact 1 100 Laren Huntsman 01500101 435-748-6519 Jay Howard 1 100 0 0 0 0 1 Type Code 110 (Point Source Identification)Type Code Point Source Quarter 1 - 4 Year Point Source Operating Hrs. in Quarter 1 110 3 2024 2208 1 110 3 2024 2207.98 1 110 3 2024 2079.75 1 110 0 0 0 1 Type Code 200 (Monitor Identification)Type Code Point Source Channel Manufacturer Model No. Monitor SN Low Span High Span Installation Date Monitor Location 1 200 CO Thermo Scientific 48iQ 12111711815 0 2000 7/12/2021 Stack 1 200 CO2 Thermo Scientific 410iQ 12111711827 0 20 7/12/2021 Stack 1 200 NOx Thermo Scientific 42iQ 12111711830 0 400 7/12/2021 Stack 1 200 OpacityA Teledyne Lighthawk 560 ES 5603357 0 100 9/17/2021 1-1 BH 1 200 OpacityB Teledyne Lighthawk 560 ES 5603356 0 100 9/17/2021 1-2 BH 1 200 SO2 Thermo Scientific 43iQ 12111711833 60 600 7/12/2021 Stack 1 200 CO Thermo Scientific 48iQ 12111711816 0 2000 7/13/2021 Stack 1 200 CO2 Thermo Scientific 410iQ 12111711828 0 20 7/13/2021 Stack 1 200 NOx Thermo Scientific 42iQ 12111711831 0 400 7/13/2021 Stack 1 200 OpacityA Teledyne Lighthawk 560 ES 5603359 0 100 9/16/2021 2-1 BH 1 200 OpacityB Teledyne Lighthawk 560 ES 5603358 0 100 9/16/2021 2-2 BH 1 200 SO2 Thermo Scientific 43iQ 12111711834 60 600 7/12/2022 Stack 1 200 CO Thermo Scientific 48iQ 12111711817 0 2000 7/13/2021 Stack 1 200 CO2 Thermo Scientific 410iQ 12111711829 0 20 7/13/2021 Stack 1 200 NOx Thermo Scientific 42iQ 12111711832 0 400 7/13/2021 Stack 1 200 OpacityA Teledyne Lighthawk 560 ES 5603360 0 100 9/15/2021 3-1 BH Duct 1 200 OpacityB Teledyne Lighthawk 560 ES 5603361 0 100 9/15/2021 3-2 BH Duct 1 200 SO2 Thermo Scientific 43iQ 12111711835 60 600 7/13/2021 Stack 1 200 0 0 0 0 0 0 1/0/1900 0 1 Type Code310 (Excess Emissions) SUMMARY REPORT Type Code Channel Total Hours of Excess Emissions Excess Emissions - % of Total Operating Hours RC 701 Hours - start up/Shutdown RC 702 Hours- Control Equipment Problems RC 703 Hours - Process Problems RC 704, 706, 707 Hours -Other Known Causes RC 705 Hours - Unknown Causes Emission Limitation Emission Limitation Units Emission Limitation Averaging Period 1 TRUE 310 SO2 0 0.00% 0 0 0 0 0 1.2 lb/MMBtu 3 hr ra 1 TRUE 310 SO2 0 0.00% 0 0 0 0 0 0.12 lb/MMBtu 30 DRA 1 TRUE 310 SO2 0 0.00% 0 0 0 0 0 0.2 lb/MMBtu 30 DRA 1 TRUE 310 NOx 0 0.00% 0 0 0 0 0 0.7 lb/MMBtu 3 hr ra 1 TRUE 310 NOx 0 0.00% 0 0 0 0 0 0.26 lb/MMBtu 30 DRA 1 TRUE 310 Opacity 0 0.00% 0 0 0 0 0 20 Percent 6 min 1 TRUE 310 CO 0 0.00% 0 0 0 0 0 3990 lb/hr 8 hr Block Ave 1 TRUE 310 CO 0 0.00% 0 0 0 0 0 0.34 lb/MMBtu 30 DRA 1 TRUE 310 SO2 0 0.00% 0 0 0 0 0 1.2 lb/MMBtu 3 hr ra 1 TRUE 310 SO2 0 0.00% 0 0 0 0 0 0.12 lb/MMBtu 30 DRA 1 TRUE 310 SO2 0 0.00% 0 0 0 0 0 0.2 lb/MMBtu 30 DRA 1 TRUE 310 NOx 0 0.00% 0 0 0 0 0 0.7 lb/MMBtu 3 hr ra 1 TRUE 310 NOx 0 0.00% 0 0 0 0 0 0.26 lb/MMBtu 30 DRA 1 TRUE 310 Opacity 0 0.00% 0 0 0 0 0 20 Percent 6 min 1 TRUE 310 CO 0 0.00% 0 0 0 0 0 3990 lb/hr 8 hr Block Ave 1 TRUE 310 CO 0 0.00% 0 0 0 0 0 0.34 lb/MMBtu 30 DRA 1 TRUE 310 SO2 0 0.00% 0 0 0 0 0 0.12 lb/MMBtu 30 DRA 1 TRUE 310 SO2 0 0.00% 0 0 0 0 0 0.2 lb/MMBtu 30 DRA 1 TRUE 310 NOx 0 0.00% 0 0 0 0 0 0.34 lb/MMBtu 30 DRA 1 TRUE 310 Opacity 0 0.00% 0 0 0 0 0 20 Percent 6 min 1 TRUE 310 CO 0 0.00% 0 0 0 0 0 0.2 lb/MMBtu 30 DRA 1 TRUE 310 CO 0 0.00% 0 0 0 0 0 2406 lb/hr 8 hr Block Ave 1 310 0 0 0 0 0 0 0 0 0 Point Source 0 3 1 2 3 0 3 1 1 1 2 2 2 3 3 3 3 Pacificorp Hunter 0 1 1 1 1 1 1 2 2 2 2 2 1 1 1 2 2 1 1 2 2 2 2 3 3 3 3 3 3 0 Pacificorp Hunter EER 3Q2024 1 Type Code 300 (CMS Performance Summary) Type Code Channel Point Source Operating Hours Downtime - % of Total Operating Hours Total CMS Downtime RC 721 Hours - Monitor Malfunction RC 722 Hours - Non-monitor Malfunction RC 723 Hours - QA Calibrations RC 724 Hours - Other Known Causes RC 725 Hours - Unknown Causes 1 TRUE 300 SO2 2208 1.03% 22.82 0 0 4.97 17.85 0 1 TRUE 300 NOx 2208 3.06% 67.67 45.82 0 8.93 12.92 0 1 TRUE 300 CO2 2208 1.03% 22.82 0 0 4.97 17.85 0 1 TRUE 300 Opacity 2208 0.56% 12.36 0.97 0 10.87 0.52 0 1 TRUE 300 CO 2208 2.89% 63.77 23.92 0 14.95 24.9 0 1 TRUE 300 SO2 2207.98 0.31% 6.91 0 0 4.93 1.98 0 1 TRUE 300 NOx 2207.98 0.59% 12.93 8.97 0 1.98 1.98 0 1 TRUE 300 CO2 2207.98 0.18% 3.96 0 0 1.98 1.98 0 1 TRUE 300 Opacity 2207.98 0.63% 14 1.77 0 9.88 2.35 0 1 TRUE 300 CO 2207.98 0.18% 3.96 0 0 1.98 1.98 0 1 TRUE 300 SO2 2079.75 0.52% 10.91 0 0 0.98 9.93 0 1 TRUE 300 NOx 2079.75 2.82% 58.74 56.78 0 0.98 0.98 0 1 TRUE 300 CO2 2079.75 0.52% 10.91 0 0 0.98 9.93 0 1 TRUE 300 Opacity 2079.75 0.61% 12.71 0.08 0 10.05 2.58 0 1 TRUE 300 CO 2079.75 0.52% 10.91 0 0 0.98 9.93 0 1 300 0 0 0 0 0 0 1 Type Code 250 (Performance Specification RATA Results) Type Code Channel Date of Most Current RATA Date of Preceding RATA Months Between RATA's Units of Measurement CEM Value Reference Method Value Relative accuracy Pass/ Fail 1 273 Days 250 CO 10/19/23 01/19/23 9 lb/mmBtu 0.2 0.2 10.90% pass 1 273 Days 250 CO 10/19/23 01/19/23 9 lb/hr 852.5 802.9 10.50% pass 1 273 Days 250 CO2 10/19/23 01/19/23 9 Percent 11.1 11.4 3.20% pass 1 273 Days 250 NOx 10/19/23 01/19/23 9 #/MMBtu 0.2 0.2 2.40% pass 1 273 Days 250 SO2 10/19/23 01/19/23 9 ppm 30.8 29.2 7.80% pass 1 261 Days 250 CO 05/02/24 08/15/23 8.6 lb/mmBtu 0.19 0.17 15.00% pass 1 261 Days 250 CO 05/02/24 08/15/23 8.6 lb/hr 546.8 496.1 14.40% pass 1 261 Days 250 CO2 05/02/24 08/15/23 8.6 Percent 10.7 10.6 1.80% pass 1 261 Days 250 NOx 05/02/24 08/15/23 8.6 #/MMBtu 0.1 0.1 0.40% pass 1 261 Days 250 SO2 05/02/24 08/15/23 8.6 ppm 34.6 35.4 2.70% pass 1 281 Days 250 CO 10/25/23 01/17/23 9.2 lb/mmBtu 0.1 0.1 11.80% pass 1 281 Days 250 CO 10/25/23 01/17/23 9.2 lb/hr 253.4 239.4 11.70% pass 1 281 Days 250 CO2 10/25/23 01/17/23 9.2 Percent 11.9 12.1 2.80% pass 1 281 Days 250 NOx 10/25/23 01/17/23 9.2 #/MMBtu 0.3 0.3 4.10% pass 1 281 Days 250 SO2 10/25/23 01/17/23 9.2 ppm 37.3 34.7 9.30% pass 1 0 Days 250 0 01/00/00 01/00/00 0 0 0 0 0.00% 0 1 Type Code 260 (CGA Results)Type Code Channel Date Audit Point No. Cylinder ID Cylinder Expiration Date Type of Certification Units of Measurement CEM Value Cylinder Value Precision %Pass/ Fail Range - High or Low 1 Valid Cal. Gas 260 CO 08/19/24 low CC16317 08/23/27 p1 ppm 496 516 -3.90% PASS 0 1 Valid Cal. Gas 260 CO 08/19/24 mid DT0027442 12/20/27 p1 ppm 1120.6 1118 0.20% PASS 0 1 Valid Cal. Gas 260 CO 08/20/24 low CC116787 07/06/28 p1 ppm 539.5 527 2.40% PASS 0 1 Valid Cal. Gas 260 CO 08/20/24 mid DT0019999 10/25/27 p1 ppm 1143 1135 0.70% PASS 0 1 Valid Cal. Gas 260 CO 08/26/24 low SA7143 08/23/27 p1 ppm 536.9 520 3.30% PASS 0 1 Valid Cal. Gas 260 CO 08/26/24 mid CC325166 10/25/27 p1 ppm 1146.4 1136 0.90% PASS 0 1 260 0 01/00/00 0 0 01/00/00 0 0 0 0 0.00% 0 0 Point Source Point Source Point Source 0 2 2 2 2 3 1 1 1 1 2 2 2 1 1 1 3 2 2 3 3 3 3 0 1 1 1 1 2 1 3 3 3 3 2 2 3 3 0 Pacificorp Hunter EER 3Q2024 1 Type Code 270 (Linearity Test Results)Type Code Channel Date Audit Point No. Cylinder ID Cylinder Expiration Date Type of Certification Units of Measurement CEM Value Cylinder Value Precision %Pass/ Fail Range - High or Low 1 Valid Cal. Gas 270 CO2 08/19/24 low CC16317 08/23/27 P1 percent 4.9 4.9 0.00% PASS 0 1 Valid Cal. Gas 270 CO2 08/19/24 mid CC142441 09/22/31 P1 percent 10.93 10.9 0.30% PASS 0 1 Valid Cal. Gas 270 CO2 08/19/24 high CC150885 11/15/30 P1 percent 18.27 18.1 0.90% PASS 0 1 Valid Cal. Gas 270 NOx 08/19/24 low CC16317 08/23/27 P1 ppm 109.77 109.2 1% PASS 0 1 Valid Cal. Gas 270 NOx 08/19/24 mid CC142441 09/22/31 P1 ppm 222.63 223 0% PASS 0 1 Valid Cal. Gas 270 NOx 08/19/24 high CC150885 11/15/30 P1 ppm 344.17 351 2% PASS 0 1 Valid Cal. Gas 270 SO2 08/19/24 low CC16317 08/23/27 P1 ppm 148.13 145.9 1.50% PASS 0 1 Valid Cal. Gas 270 SO2 08/19/24 mid CC142441 09/22/31 P1 ppm 327.03 329.5 0.70% PASS 0 1 Valid Cal. Gas 270 SO2 08/19/24 high CC150885 11/15/24 P1 ppm 511.57 531 3.70% PASS 0 1 Valid Cal. Gas 270 CO2 08/20/24 low CC116787 07/06/28 P1 percent 4.9 5 2.00% PASS 0 1 Valid Cal. Gas 270 CO2 08/20/24 mid CC230556 09/22/31 P1 percent 10.9 10.9 0.00% PASS 0 1 Valid Cal. Gas 270 CO2 08/20/24 high CC179361 08/26/27 P1 percent 17.83 17.7 0.80% PASS 0 1 Valid Cal. Gas 270 NOx 08/20/24 low CC116787 07/06/28 P1 ppm 111.6 110.4 1.10% PASS 0 1 Valid Cal. Gas 270 NOx 08/20/24 mid CC230556 09/22/31 P1 ppm 220.87 220 0.40% PASS 0 1 Valid Cal. Gas 270 NOx 08/20/24 high CC179361 08/26/27 P1 ppm 352.73 357 1.20% PASS 0 1 Valid Cal. Gas 270 SO2 08/20/24 low CC116787 07/06/28 P1 ppm 154.1 146.8 5% PASS 0 1 Valid Cal. Gas 270 SO2 08/20/24 mid CC230556 09/22/31 P1 ppm 332.3 328.9 1% PASS 0 1 Valid Cal. Gas 270 SO2 08/20/24 high CC179361 08/26/27 P1 ppm 519.9 532 2% PASS 0 1 Valid Cal. Gas 270 CO2 08/26/24 low SA7143 08/23/27 P1 percent 4.97 4.9 1.40% PASS 0 1 Valid Cal. Gas 270 CO2 08/26/24 mid CC318664 02/28/32 P1 percent 10.8 10.8 0.00% PASS 0 1 Valid Cal. Gas 270 CO2 08/26/24 high CC155742 08/26/27 P1 percent 17.63 17.6 0.20% PASS 0 1 Valid Cal. Gas 270 NOx 08/26/24 low SA7143 08/23/27 P1 ppm 113.9 110 3.50% PASS 0 1 Valid Cal. Gas 270 NOx 08/26/24 mid CC318664 02/28/32 P1 ppm 224.57 223 0.70% PASS 0 1 Valid Cal. Gas 270 NOx 08/26/24 high CC155742 08/26/27 P1 ppm 357.23 358 0.20% PASS 0 1 Valid Cal. Gas 270 SO2 08/26/24 low SA7143 08/23/27 P1 ppm 150.8 146.2 3.10% PASS 0 1 Valid Cal. Gas 270 SO2 08/26/24 mid CC318664 02/28/32 P1 ppm 321 320.6 0.10% PASS 0 1 Valid Cal. Gas 270 SO2 08/26/24 high CC155742 08/26/27 P1 ppm 531.4 539 1.40% PASS 0 1 270 0 01/00/00 0 0 01/00/00 0 0 0 0 0.00% 0 0 1 Type Code 210 (Pollutant Concentration Exceeded Span of CEM) Type Code Channel Start Date Start Time End Date End Time Hours 1 0 0 0 1/0/00 0:00 1/0/00 0:00 1 1 None Reported 1 0 TC 220 Hours 333.13 TC 220 Hours 0.00 TC 230 Hours 0.00 Events 0.00 Hours 0.00 Events 0.00 0.00 1 335.38 TC 300 Hours 2.25 FALSE None Reported None Reported Yes Yes None Reported None Reported 2 2 2 3 3 3 3 3 3 3 0 Point Source Point Source Yes Type Code 550 (Changes in Operation in Control Equipment When CEM Data Not Available) Type Code 500 (Boiler Operating Days w/o 18 Hours of Data) Type Code 450 (Data Excluded) Type Code 210 (Pollutant Concentration Exceeded Span of CEM) Type Code 220 (Monitor Outage During Point Source Operation) Type Code 230 (Manual Sample - Alternate Sampling During Monitor Outage) Type Code 240 (CEM Modifications) Type Code 530 (Excess Emissions During Emergency Conditions) 2 3 3 1 1 1 1 2 1 1 1 1 1 2 2 2 2 0 Pacificorp Hunter EER 3Q2024 Relative Accuracy Overview Point Source Channel Date of Most Current RATA Date of Preceding RATA Months Between RATA's Units Measured CEM Value Reference Method Value Relative Accuracy Pass/ Fail 2024 1 CO 10/19/23 01/19/23 9 lb/mmBtu 0.2 0.20 10.90% pass 1 CO 10/19/23 01/19/23 9 lb/hr 852.5 802.90 10.50% pass 1 CO2 10/19/23 01/19/23 9 Percent 11.1 11.40 3.20% pass 1 NOx 10/19/23 01/19/23 9 #/MMBtu 0.2 0.20 2.40% pass 1 SO2 10/19/23 01/19/23 9 ppm 30.8 29.20 7.80% pass 2 CO 05/02/24 08/15/23 8.6 lb/mmBtu 0.19 0.17 15.00% pass 2 CO 05/02/24 08/15/23 8.6 lb/hr 546.8 496.10 14.40% pass 2 CO2 05/02/24 08/15/23 8.6 Percent 10.7 10.60 1.80% pass 2 NOx 05/02/24 08/15/23 8.6 #/MMBtu 0.1 0.10 0.40% pass 2 SO2 05/02/24 08/15/23 8.6 ppm 34.6 35.40 2.70% pass 3 CO 10/25/23 01/17/23 9.2 lb/mmBtu 0.1 0.10 11.80% pass 3 CO 10/25/23 01/17/23 9.2 lb/hr 253.4 239.40 11.70% pass 3 CO2 10/25/23 01/17/23 9.2 Percent 11.9 12.10 2.80% pass 3 NOx 10/25/23 01/17/23 9.2 #/MMBtu 0.3 0.30 4.10% pass 3 SO2 10/25/23 01/17/23 9.2 ppm 37.3 34.70 9.30% pass * NSPS CGA Third 2024 Audit Gas Ranges Audit Gas Ranges AP1 Low AP2 Low AP1 High AP2 High 1 CO 8/19/24 2000 516 400 to 600 1 CO 8/19/24 2000 1118 1000 to 1200 2 CO 8/20/24 2000 527 400 to 600 2 CO 8/20/24 2000 1135 1000 to 1200 3 CO 8/26/24 2000 520 400 to 600 3 CO 8/26/24 2000 1136 1000 to 1200 * Acid Rain Audit Linearity Third 2024 Low Span Gas Ranges High Span Gas Ranges Low Mid High Low Mid High 1 CO2 8/19/24 20 4.9 4 to 6 1 CO2 8/19/24 20 10.9 10 to 12 1 CO2 8/19/24 20 18.1 16 to 20 1 NOx 8/19/24 400 109.2 80 to 120 1 NOx 8/19/24 400 223 200 to 240 1 NOx 8/19/24 400 351 320 to 400 1 SO2 8/19/24 600 145.9 120 to 180 1 SO2 8/19/24 600 329.5 300 to 360 1 SO2 8/19/24 600 531 480 to 600 2 CO2 8/20/24 20 5 4 to 6 2 CO2 8/20/24 20 10.9 10 to 12 2 CO2 8/20/24 20 17.7 16 to 20 2 NOx 8/20/24 400 110.4 80 to 120 2 NOx 8/20/24 400 220 200 to 240 2 NOx 8/20/24 400 357 320 to 400 2 SO2 8/20/24 600 146.8 120 to 180 2 SO2 8/20/24 600 328.9 300 to 360 2 SO2 8/20/24 600 532 480 to 600 3 CO2 8/26/24 20 4.9 4 to 6 3 CO2 8/26/24 20 10.8 10 to 12 3 CO2 8/26/24 20 17.6 16 to 20 3 NOx 8/26/24 400 110 80 to 120 3 NOx 8/26/24 400 223 200 to 240 3 NOx 8/26/24 400 358 320 to 400 3 SO2 8/26/24 600 146.2 120 to 180 3 SO2 8/26/24 600 320.6 300 to 360 3 SO2 8/26/24 600 539 480 to 600 * Audit Gas Used Point Source Channel Audit Date Low Span Point Source Channel Audit Date Low Span Audit Gas Used High Span Audit Gas Used High SpanAudit Gas Used Pacificorp Hunter EER 3Q2024 Type Code 280 (COMS Attenuator Filters) Procedure 3 Point Source Location Attenuator I.D. Attenuator Certification Date Certified Attenuator Opacity OPLR, SECR, or PLCF, Corrected Opacity Value Range Low, Mid, & High Certification 1-year or 5-year Unit 1 1A S13263 6/28/24 17 1 17.4 Low 1 Unit 1 1A S13268 6/28/24 27 1 26.6 Mid 1 Unit 1 1A S13249 6/28/24 47 1 46.9 High 1 Unit 1 1B S13263 6/28/24 17.4 1 17.4 Low 1 Unit 1 1B S13268 6/28/24 26.6 1 26.6 Mid 1 Unit 1 1B S13249 6/28/24 46.9 1 46.9 High 1 Unit 2 2A S13263 6/28/24 17.4 1 17.4 Low 1 Unit 2 2A S13268 6/28/24 26.6 1 26.6 Mid 1 Unit 2 2A S13249 6/28/24 46.9 1 46.9 High 1 Unit 2 2B S13263 6/28/24 17.4 1 17.4 Low 1 Unit 2 2B S13268 6/28/24 26.6 1 26.6 Mid 1 Unit 2 2B S13249 6/28/24 46.9 1 46.9 High 1 Unit 3 3 S13263 6/28/24 17.4 1 17.4 Low 1 Unit 3 3 S13268 6/28/24 26.6 1 26.6 Mid 1 Unit 3 3 S13249 6/28/24 46.9 1 46.9 High 1 Unit 3 3 S13263 6/28/24 17.4 1 17.4 Low 1 Unit 3 3 S13268 6/28/24 26.6 1 26.6 Mid 1 Unit 3 3 S13249 6/28/24 46.9 1 46.9 High 1 * Opacity Monitor Response (Average of 5) Low Range Mid Range High Range Unit 1 1A 7/15/24 18 -0.320 0.110 0.136 0.005 Unit 1 1A 7/15/24 26 -0.660 0.358 0.444 0.011 Unit 1 1A 7/15/24 48 0.780 0.224 0.278 0.011 Unit 1 1B 7/15/24 17 -0.100 0.649 0.806 0.009 Unit 1 1B 7/15/24 27 -0.130 1.350 1.676 0.018 Unit 1 1B 7/15/24 47 -0.160 0.940 1.167 0.013 Unit 2 2A 7/16/24 17 -0.150 0.502 0.623 0.008 Unit 2 2A 7/16/24 25 -0.940 0.042 0.052 0.010 Unit 2 2A 7/16/24 47 0.400 0.000 0.000 0.004 Unit 2 2B 7/16/24 18 0.910 0.230 0.286 0.012 Unit 2 2B 7/16/24 27 -0.130 0.230 0.286 0.004 Unit 2 2B 7/16/24 48 1.120 1.085 1.347 0.025 Unit 3 3 7/22/24 17 -0.050 0.050 0.062 0.001 Unit 3 3 7/22/24 27 0.140 0.839 1.042 0.012 Unit 3 3 7/22/24 48 0.980 0.000 0.000 0.010 Unit 3 3 7/22/24 17 -0.630 0.179 0.222 0.009 Unit 3 3 7/22/24 25 -1.240 0.377 0.468 0.017 Unit 3 3 7/22/24 48 0.630 0.132 0.164 0.008 * Point Source Location Audit Date Alternitive Zero Alignment (Yes or No) COM Clear Condition Zero Response (CCZR) COM Simulated Zero Response (CSZR) Zero Alignment Error Difference (CCZR)-(CSZR) Adjustment to COM Simulated Zero Response (CSZR) (Yes or No) 1 1A 2/12/24 no 0.250 0.030 0.220 yes 1 1B 2/12/24 no -2.350 -0.030 -2.320 yes 2 2A 2/6/24 no 100.000 -0.020 100.020 yes 2 2B 2/6/24 no 0.830 -0.150 0.980 yes 3 3A 3/6/24 no 0.490 0.040 0.450 yes 3 3B 3/5/24 no 0.350 -0.070 0.420 yes Type Code 282 (Procedure 3 - Annual Zero Alignment Audit) Point Source Location Audit Date Mean Difference Standard Deviation Confidence Coefficient Calibration Error (≤ 3%) Type Code 281 (Procedure 3 - COMS Filter Audit Calibration Error) Pacificorp Hunter EER 3Q2024 Monitoring Information TC 210, 230, & 240 Type Code 210 (Pollutant Concentration Exceeded Span of CEM) - 500 (All) * Sum of Hours Column Labels Row Labels (blank) Grand Total (blank)0 0 Grand Total 0 0 * Type Code 230 (Manual Sample - Alternate Sampling During Monitor Outage) - 500 (All) * Sum of Hours Column Labels Row Labels (blank) Grand Total (blank)0 0 Grand Total 0 0 * Type Code 240 (CEM Modifications) - 100 (All) * Count of Channel Column Labels Row Labels (blank) Grand Total (blank) (blank) Grand Total Pacificorp Hunter EER 3Q2024 Type Code 220 (Monitor Outage During Point Source Operation) - 600 (All) * Sum of Hours Column Labels Row Labels 723 724 721 Grand Total 1 Opacity The monitor was unavailable during the daily monitor calibration as required by 40 CFR parts 60 and 75.7.50 7.50 Bad input status for all or part of averaging period, resulted in invalid averaging period.0.08 0.08 Opacity monitor optical surfaces were cleaned and inspected. Stack sets were conducted followed by an autocalibration. The monitor was then returned to service. 0.65 0.65 Quarterly filter audit performed followed by auto calibration.2.72 2.72 Maintenance of another monitor required normal sampling to be interrupted. The system was returned to service following the maintenance. 0.27 0.27 The ERP on the Opcity monitor display was not functionig data was still good. Display was changed out 0.97 0.97 Power was loss to stack due to a problem with a load center or load center problem trouble shooting. The power was restored and the PLC recycled and comm restored between stack and DAHS. 0.08 0.08 Maintenance was inadvertanly hit. Monitor was taken out of maintenance no work was done on the monitors.0.08 0.08 CO2 Maintenance of another monitor required normal sampling to be interrupted. The system was returned to service following the maintenance. 17.85 17.85 Quarterly linearity testing performed.1.98 1.98 Performing scheduled annual maintenance, checks and inspections. Inspected or replaced sample pump, light source, critical orifices. Followed by auto calibration and abbreviated linearity test. 2.98 2.98 CO Maintenance of another monitor required normal sampling to be interrupted. The system was returned to service following the maintenance. 24.90 24.90 The NOx, CO wheel chopper motor failed. The motor was replaced and the monitor was returned to service.13.97 13.97 Failure of a monitor light source resulted in invalid data. The light source was replaced followed by a manual calibration, auto calibration, and an abbreviated linearity test. 2.98 2.98 8864 froze up causing bad data. Power was cycled and data started to record. Initiated autocalibration.1.98 1.98 An abbreviated lineraity test was initiated following monitor maintenance or to check system accuracy.9.98 9.98 Quarterly linearity testing performed.1.98 1.98 Performing scheduled annual maintenance, checks and inspections. Inspected or replaced sample pump, light source, critical orifices. Followed by auto calibration and abbreviated linearity test. 2.98 2.98 IR source on the analyzer failed. Source was replaced followed by an auto cal.4.98 4.98 NOx Pacificorp Hunter EER 3Q2024 Sum of Hours Column Labels Row Labels 723 724 721 Grand Total Maintenance of another monitor required normal sampling to be interrupted. The system was returned to service following the maintenance. 12.92 12.92 8864 froze up causing bad data. Power was cycled and data started to record. Initiated autocalibration.4.98 4.98 NOx ozinator transformer was arching causing the monitor to go into alarm. Transformer was replaced. Followed by an auto cal.0.98 0.98 The CEMS monitor readings locked up. The monitor was reset (powered down and then powered backup) followed by an auto calibration. 11.93 11.93 The monitor high voltage power supply or processor board failed resulting in invalid data. A new power supply or processor board was installed, out put voltages adjusted and the monitor was recalibrated and returned to service. 27.92 27.92 Quarterly linearity testing performed.5.95 5.95 Performing scheduled annual maintenance, checks and inspections. Inspected or replaced sample pump, light source, critical orifices. Followed by auto calibration and abbreviated linearity test. 2.98 2.98 SO2 Maintenance of another monitor required normal sampling to be interrupted. The system was returned to service following the maintenance. 17.85 17.85 Quarterly linearity testing performed.1.98 1.98 Performing scheduled annual maintenance, checks and inspections. Inspected or replaced sample pump, light source, critical orifices. Followed by auto calibration and abbreviated linearity test. 2.98 2.98 2 Opacity The monitor was unavailable during the daily monitor calibration as required by 40 CFR parts 60 and 75.7.25 7.25 Opacity monitor optical surfaces were cleaned and inspected. Stack sets were conducted followed by an autocalibration. The monitor was then returned to service. 0.18 0.18 Quarterly filter audit performed followed by auto calibration.0.17 0.17 Power was loss to stack due to a problem with a load center or load center problem trouble shooting. The power was restored and the PLC recycled and comm restored between stack and DAHS. 0.08 0.08 Trouble shooting 8864 turned off 8864 and then turned back on and cleared the alarms.1.47 1.47 #N/A 0.47 0.47 Temporary loss of power to monitor resulted in loss of data. Power was restored and monitor returned to service.0.17 0.17 The monitor exhibited excessive drift. System components were inspected and or replace board level cal was performed on system boards followed by man and auto cal. 1.77 1.77 Invalid 6 minute due to process off time and/ or calibration during hour 0.17 0.17 CO2 Performing scheduled annual maintenance, checks and inspections. Inspected or replaced sample pump, light source, critical orifices. Followed by auto calibration and abbreviated linearity test. 1.98 1.98 Pacificorp Hunter EER 3Q2024 Sum of Hours Column Labels Row Labels 723 724 721 Grand Total Trouble shooting 8864 turned off 8864 and then turned back on and cleared the alarms.1.98 1.98 CO Performing scheduled annual maintenance, checks and inspections. Inspected or replaced sample pump, light source, critical orifices. Followed by auto calibration and abbreviated linearity test. 1.98 1.98 Trouble shooting 8864 turned off 8864 and then turned back on and cleared the alarms.1.98 1.98 NOx Performing scheduled annual maintenance, checks and inspections. Inspected or replaced sample pump, light source, critical orifices. Followed by auto calibration and abbreviated linearity test. 1.98 1.98 Trouble shooting 8864 turned off 8864 and then turned back on and cleared the alarms.1.98 1.98 Opacity monitor was intermittently showing missing and invalid data. Diagnostic actions were taken to find the cause of the spikes and missing data. Auto cal was completed following diagnostic work. 8.97 8.97 SO2 Performing scheduled annual maintenance, checks and inspections. Inspected or replaced sample pump, light source, critical orifices. Followed by auto calibration and abbreviated linearity test. 1.98 1.98 Daily Cal of the monitor was in the maintenance limit.2.95 2.95 Trouble shooting 8864 turned off 8864 and then turned back on and cleared the alarms.1.98 1.98 3 Opacity The monitor was unavailable during the daily monitor calibration as required by 40 CFR parts 60 and 75.6.75 6.75 Bad input status for all or part of averaging period, resulted in invalid averaging period.0.08 0.08 Opacity monitor optical surfaces were cleaned and inspected. Stack sets were conducted followed by an autocalibration. The monitor was then returned to service. 0.57 0.57 Quarterly filter audit performed followed by auto calibration.2.47 2.47 The monitor high voltage power supply or processor board failed resulting in invalid data. A new power supply or processor board was installed, out put voltages adjusted and the monitor was recalibrated and returned to service. 0.08 0.08 #N/A 0.18 0.18 Invalid 6 minute due to process off time and/ or calibration during hour 1.28 1.28 Rodded probe, cleaned or replaced ceramic filter, followed by auto calibration. No adjustments made to analyzers.0.08 0.08 Opacity monitor retro reflector lenses were cleaned and inspected. No adjustments were made to the analyzer. Followed by an auto cal. 1.13 1.13 Startup Calibration 0.08 0.08 CO2 Maintenance of another monitor required normal sampling to be interrupted. The system was returned to service following the maintenance. 8.95 8.95 Pacificorp Hunter EER 3Q2024 Sum of Hours Column Labels Row Labels 723 724 721 Grand Total Performing scheduled annual maintenance, checks and inspections. Inspected or replaced sample pump, light source, critical orifices. Followed by auto calibration and abbreviated linearity test. 0.98 0.98 Rodded probe, cleaned or replaced ceramic filter, followed by auto calibration. No adjustments made to analyzers.0.98 0.98 CO Maintenance of another monitor required normal sampling to be interrupted. The system was returned to service following the maintenance. 8.95 8.95 Performing scheduled annual maintenance, checks and inspections. Inspected or replaced sample pump, light source, critical orifices. Followed by auto calibration and abbreviated linearity test. 0.98 0.98 Rodded probe, cleaned or replaced ceramic filter, followed by auto calibration. No adjustments made to analyzers.0.98 0.98 NOx 8864 froze up causing bad data. Power was cycled and data started to record. Initiated autocalibration.32.90 32.90 The monitor high voltage power supply or processor board failed resulting in invalid data. A new power supply or processor board was installed, out put voltages adjusted and the monitor was recalibrated and returned to service. 6.98 6.98 Performing scheduled annual maintenance, checks and inspections. Inspected or replaced sample pump, light source, critical orifices. Followed by auto calibration and abbreviated linearity test. 0.98 0.98 Rodded probe, cleaned or replaced ceramic filter, followed by auto calibration. No adjustments made to analyzers.0.98 0.98 The monitor failed its daily/startup calibration. The monitor was recalibrated and returned to service.16.90 16.90 SO2 Maintenance of another monitor required normal sampling to be interrupted. The system was returned to service following the maintenance. 8.95 8.95 Performing scheduled annual maintenance, checks and inspections. Inspected or replaced sample pump, light source, critical orifices. Followed by auto calibration and abbreviated linearity test. 0.98 0.98 Rodded probe, cleaned or replaced ceramic filter, followed by auto calibration. No adjustments made to analyzers.0.98 0.98 Grand Total 77.15 117.68 138.30 333.13 Pacificorp Hunter EER 3Q2024 Opy * Opy Count of Magnitude of Emissions Column Labels Opy Row Labels Grand Total Opy Grand Total SO2 * SO2 Type Code 410 (SO2) - 6000 (All) SO2 * SO2 Count of Magnitude of Emissions Column Labels SO2 Row Labels Grand Total SO2 Grand Total NOx d * NOx d Type Code 421 (Daily NOx Emissions) - 500 (All) NOx d * NOx d Count of Reason Code Column Labels NOx d Row Labels y Grand Total NOx d 3 NOx d #N/A 2 2 NOx d Grand Total 2 2 CO * CO Type Code 440 (CO) - 6000 (All) CO * CO Count of Magnitude of Emissions Column Labels CO Row Labels Grand Total CO Grand Total Dat Ex * Dat Ex Type Code 450 (Data Excluded) - 6000 (All) Dat Ex * Dat Ex Count of Channel Column Labels Dat Ex Row Labels 724 721 723 Grand Total Dat Ex 3 Dat Ex CO 4 1 5 Dat Ex Rodded probe, cleaned or replaced ceramic filter, followed by auto calibration. No adjustments made to analyzers.1 1 Dat Ex Maintenance of another monitor required normal sampling to be interrupted. The system was returned to service following the maintenance. 3 3 Dat Ex Performing scheduled annual maintenance, checks and inspections. Inspected or replaced sample pump, light source, critical orifices. Followed by auto calibration and abbreviated linearity test. 1 1 Dat Ex NOx 1 13 1 15 Dat Ex Rodded probe, cleaned or replaced ceramic filter, followed by auto calibration. No adjustments made to analyzers.1 1 Dat Ex The monitor failed its daily/startup calibration. The monitor was recalibrated and returned to service.6 6 Dat Ex The monitor high voltage power supply or processor board failed resulting in invalid data. A new power supply or processor board was installed, out put voltages adjusted and the monitor was recalibrated and returned to service. 1 1 Dat Ex 8864 froze up causing bad data. Power was cycled and data started to record. Initiated autocalibration.6 6 Dat Ex Performing scheduled annual maintenance, checks and inspections. Inspected or replaced sample pump, light source, critical orifices. Followed by auto calibration and abbreviated linearity test. 1 1 Dat Ex SO2 4 1 5 Dat Ex Rodded probe, cleaned or replaced ceramic filter, followed by auto calibration. No adjustments made to analyzers.1 1 Dat Ex Maintenance of another monitor required normal sampling to be interrupted. The system was returned to service following the maintenance. 3 3 Dat Ex Performing scheduled annual maintenance, checks and inspections. Inspected or replaced sample pump, light source, critical orifices. Followed by auto calibration and abbreviated linearity test. 1 1 Dat Ex Grand Total 9 13 3 25 Pacificorp Hunter EER 3Q2024 Pacificorp Hunter EER 3Q2024 Type Code 500 Before February 28, 2005 (Boiler Operating Days w/o 18 Hours of Data) After February 28, 2005 (90% Operating Hours For each 30 BOD) - 500 (All) * Count of Channel Column Labels Row Labels 701 Grand Total 3 SO2 6 6 The unit was removed from service in a controlled fashion in order to repair a boiler tube leak. The tube leak was repaired and the unit was returned to service. 2 2 The unit was removed from service in a controlled manner in order to repair a feedwater heater. The heater was repaired and the unit returned to service. 3 3 The unit was removed from service in a controlled manner in order to repair a turbine control valve. The valve was repaired and the unit retruned to service. 1 1 NOx 6 6 The unit was removed from service in a controlled fashion in order to repair a boiler tube leak. The tube leak was repaired and the unit was returned to service. 2 2 The unit was removed from service in a controlled manner in order to repair a feedwater heater. The heater was repaired and the unit returned to service. 3 3 The unit was removed from service in a controlled manner in order to repair a turbine control valve. The valve was repaired and the unit retruned to service. 1 1 Grand Total 12 12 * Type Code 510 (F-factor, Equations & Conversion Factors) - 500 (All) Count of F-factor Column Labels Row Labels SO2 NOx Grand Total 1 1800 1 1 2 2 1800 1 1 2 3 1800 1 1 2 Grand Total 3 3 6 * Type Code 520 (Minimum Data Not Obtained <22/30 BODs) - 500 (All) Count of Channel Column Labels Row Labels Grand Total Grand Total * Type Code 530 (Excess Emissions During Emergency Conditions) - 500 (All) Count of Date Column Labels Row Labels Grand Total Grand Total * Type Code 540 (Fuel Pre-treatment Credit SO2) - 500 (All) Count of Date Column Labels Row Labels Grand TotalGrand Total * TypeCode 550 (Changes in Operation in Control Equipment When CEM Data Not Available) - 500 (All) Column Labels Row Labels Grand Total Grand Total