Loading...
HomeMy WebLinkAboutDERR-2024-011716 WESTECH EQUIPMENT 195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307 801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054 PRODUCT PIPING INTEGRITY TESTING Facility Name: Facilities Steam Plant Owner: Salt Lake Public Utilities Address: 261 East 500 South Address: 1530 South West Temple City, State, Zip: Salt Lake City, Utah 84111 City, State, Zip: Salt Lake City, Utah 84115 Facility I.D.#: 4000830 Phone #: 801-535-6904 Testing Company: Westech Phone #: 801-266-2545 Date: 10/24/24 This procedure is to test the integrity of product piping. Tests were performed with Petro-Tite line tester. Tank Number 1 Product Stored Red DSL Piping Run Supply Piping Type Flex D/W Test Pressure (PSI) 50 Test Duration (minutes) 30 Leak Rate (GPH) 0.004 Test Results ☒Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail Comments: Tester’s Name Taber DeHart, UT-0394 Tester’s Signature DSL WESTECH EQUIPMENT 195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307 801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054 MECHANICAL AND ELECTRONIC LINE LEAK DETECTOR PERFORMANCE TESTS Facility Name: Facilities Steam Plant Owner: Salt Lake Public Utilities Address: 261 East 500 South Address: 1530 South West Temple City, State, Zip: Salt Lake City, Utah 84111 City, State, Zip: Salt Lake City, Utah 84115 Facility I.D.#: 4000830 Phone #: 801-535-6904 Testing Company: Westech Phone #: 801-266-2545 Date: 10/24/24 This data sheet can be used to test the mechanical line leak detector (MLLD) and electronic line leak detector (ELLD) with submersible turbine pump (STP) systems. See PEI/RP 1200 Sections 9.1 and 9.2 for test procedures. Line Number 1 Product Stored Red DSL Leak Detector Manufacturer Red Jacket Leak Detector Model FX1DV Type Of leak Detector ☒MLLD ☐ELLD ☐MLLD ☐ELLD ☐MLLD ☐ELLD ☐MLLD ☐ELLD MLLD (ALL PRESSURE MEASURMENTS ARE MADE IN PSIG) STP full operating pressure 29 Check valve holding pressure 19 Line resiliency (ml) (line bleedback volume as measured from check valve holding pressure to 0 psig) 80 Step through time in seconds (time the MLLD hesitates at metering pressure before going to full operating pressure as measured from 0 sig with no leak induced on the line) 1 Metering pressure (STP pressure when simulated leak rate 3 gph at 10 psig) 14 Opening time in seconds (the time the MLLD opens to allow full pressure after simulated leak is stopped) 1 Does the STP pressure remain at or below the metering pressure for at least 60 seconds when the simulated leak is induced? ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No Does the leak detector reset (trip) when the line pressure is bled off to zero psig? ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No Does STP properly clycle on/off under normal fuel system operating conditions? ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No A "No" answer to any of the above questions indicates that the MLLD fails the test. ELLD (ALL PRESSURE MEASURMENTS ARE MADE IN PSIG) STP full operating pressure How many test cycles are observed before alarm/shutdown occurs? Does the simulated leak cause on alarm? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No A "No" answer to the above question indicates that the ELLD fails the test. Does the simulated leak cause an STP shutdown? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No Test Results ☒Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail Comments: Tester’s Name Taber DeHart, UT-0394 Tester’s Signature WESTECH EQUIPMENT 195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307 801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054 AUTOMATIC TANK GAUGE OPERATION INSPECTION Facility Name: Facilities Steam Plant Owner: Salt Lake Public Utilities Address: 261 East 500 South Address: 1530 South West Temple City, State, Zip: Salt Lake City, Utah 84111 City, State, Zip: Salt Lake City, Utah 84115 Facility I.D.#: 4000830 Phone #: 801-535-6904 Testing Company: Westech Phone #: 801-266-2545 Date: 10/24/24 This procedure is to determine whether the automatic tank gauge (ATG) is operating properly. See PEI/RP1200 Section 8.2 for the inspection procedure. This procedure is applicable to tank monitor stems that touch the bottom of the tank when in place. Tank Number 1 Product Stored Red DSL ATG Brand and Model TLS-4 1. Tank Volume, gallons 11,527 2. Tank Diameter, inches 91.9 3. After removing the ATG from the tank, it has been inspected and any damaged or missing parts replaced? ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No 4. Float moves freely on the stem without binding? ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No 5. Fuel float level agree with the value programmed into the console? ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No 6. Water float level agree with the value programmed into the console? ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No 7. Inch level from the bottom of the stem when 90% alarm is triggered? 75 8. Inch level at which the overfill alarm activates corresponds with the value programmed in the gauge? ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No 9. Inch level from the bottom when the water float first triggers an alarm? 1.5 10. Inch level at which the water float alarm activates corresponds with the value programmed in the gauge? ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No If any answers in Lines 3, 4, 5, or 6 are "No" the system has failed the test. Test Results ☒Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail Comments: Battery OK Tester’s Name Taber DeHart, UT-0394 Tester’s Signature WESTECH EQUIPMENT 195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307 801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054 LIQUID SENSER FUNCTIONALITY TESTING Facility Name: Facilities Steam Plant Owner: Salt Lake Public Utilities Address: 261 East 500 South Address: 1530 South West Temple City, State, Zip: Salt Lake City, Utah 84111 City, State, Zip: Salt Lake City, Utah 84115 Facility I.D.#: 4000830 Phone #: 801-535-6904 Testing Company: Westech Phone #: 801-266-2545 Date: 10/24/24 This procedure is to determine whether liquid sensors, located in the interstitial spaces of the UST systems, are able to detect the presence of water and fuel. See PEI/RP1200, Section 8.3 for the test procedure. Sensor Location L-1 STP L-2 INT Product Stored Red DSL Red DSL Type of Sensor ☐ Discriminating ☒ Non-Discrimi- nating ☐ Discriminating ☒ Non-Discrimi- nating ☐ Discriminating ☐ Non-Discrimi- nating ☐ Discriminating ☐ Non-Discrimi- nating ☐ Discriminating ☐ Non-Discrimi- nating ☐ Discriminating ☐ Non-Discrimi- nating ☐ Discriminating ☐ Non-Discrimi- nating Test Liquid ☒ Water ☐ Product ☒ Water ☐ Product ☐ Water ☐ Product ☐ Water ☐ Product ☐ Water ☐ Product ☐ Water ☐ Product ☐ Water ☐ Product Is the ATG Console clear of any active or recurring warnings or alarms regarding the leak sensor? If the sensor is in alarm and functioning, indicate why. ☒ Yes ☐ No ☒ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No Is sensor alarm circuit operational? ☒ Yes ☐ No ☒ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No Has sensor been inspected and in good operating condition? ☒ Yes ☐ No ☒ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No When placed in test liquid, does the sensor trigger an alarm? ☒ Yes ☐ No ☒ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No When alarm is trigger, is the sensor identified on the ATG console? ☒ Yes ☐ No ☒ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No Any “No” answers indicate the sensor fails the test. Test Results: ☒ Pass ☐ Fail ☒ Pass ☐ Fail ☐ Pass ☐ Fail ☐ Pass ☐ Fail ☐ Pass ☐ Fail ☐ Pass ☐ Fail ☐ Pass ☐ Fail Comments: Tester’s Name: Taber DeHart, UT-0394 Tester’s Signature WESTECH EQUIPMENT 195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307 801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054 SPILL BUCKET INTEGRITY TESTING HYDROSTATIC TEST METHOD SINGLE- AND DOUBLE-WALLED VACUUM TEST METHOD Facility Name: Facilities Steam Plant Owner: Salt Lake Public Utilities Address: 261 East 500 South Address: 1530 South West Temple City, State, Zip: Salt Lake City, Utah 84111 City, State, Zip: Salt Lake City, Utah 84115 Facility I.D.#: 4000830 Phone #: 801-535-6904 Testing Company: Westech Phone #: 801-266-2545 Date: 10/24/24 This procedure is to test the leak integrity of single- and double-walled spill buckets. See PEI/RP1200 Section 6.2 for hydrostatic test method, Section 6.3 for single-walled vacuum test method and Section 6.4 for double-walled vacuum test method. Tank Number 1 Product Stored Red DSL Spill Bucket Capacity 5-Gallon Manufacturer OPW Construction ☐Double-walled ☒Single-walled ☐Double-walled ☐Single-walled ☐Double-walled ☐Single-walled ☐Double-walled ☐Single-walled Test Type ☒Hydrostatic ☐Vacuum ☐Double-walled ☐Single-walled ☐Hydrostatic ☐Vacuum ☐Double-walled ☐Single-walled ☐Hydrostatic ☐Vacuum ☐Double-walled ☐Single-walled ☐Hydrostatic ☐Vacuum ☐Double-walled ☐Single-walled Spill Bucket Type ☐Product ☒Vapor ☐Product ☐Vapor ☐Product ☐Vapor ☐Product ☐Vapor Liquid and debris remove from spill bucket?* ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No Visual Inspection (no cracks, loose parts or separation of the bucket from the fill pipe.) ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No Tank Riser cap included in test? ☐Yes ☒No ☐NA ☐Yes ☐No ☐NA ☐Yes ☐No ☐NA ☐Yes ☐No ☐NA Drain valve included in test? ☒Yes ☐No ☐NA ☐Yes ☐No ☐NA ☐Yes ☐No ☐NA ☐Yes ☐No ☐NA Starting Level 8 15/16” Test Start Time 10:57 Ending Level 8 15/16” Test End Time 11:57 Test Period 1 Hour Level Change 0” Pass/fail criteria: Must pass visual inspection. Hydrostatic: Water level drop of less than 1/8 inch; Vacuum single-walled only: Maintain at least 26 inches water column; Vacuum double-walled: maintain at least 12 inches water column. Test Results ☒Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail Comments: *All liquids and debris must be disposed of properly Tester’s Name Taber DeHart, UT-0394 Tester’s Signature WESTECH EQUIPMENT 195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307 801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054 UST OVERFILL EQUIPMENT INSPECTION AUTOMATIC SHUTOFF DEVICE AND BALL FLOAT VALVE Facility Name: Facilities Steam Plant Owner: Salt Lake Public Utilities Address: 261 East 500 South Address: 1530 South West Temple City, State, Zip: Salt Lake City, Utah 84111 City, State, Zip: Salt Lake City, Utah 84115 Facility I.D.#: 4000830 Phone #: 801-535-6904 Testing Company: Westech Phone #: 801-266-2545 Date: 10/24/24 This data sheet is for inspecting automatic shutoff devices and ball float valve. See PEI/RP1200 Section 7 for inspection pro cedures. Product Grade Red DSL Tank Number 1 Tank Volume, gallons 11,527 Tank Diameter, inches 91.9 Overfill Prevention Device Brand OPW Type ☒ Automatic Shutoff Device ☐ Ball Float Valve ☐ Automatic Shutoff Device ☐ Ball Float Valve ☐ Automatic Shutoff Device ☐ Ball Float Valve ☐ Automatic Shutoff Device ☐ Ball Float Valve AUTOMATIC SHUTOFF DEVICE INSPECTION 1. Drop tube removed from tank? ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No 2. Drop tube and float mechanisms free of debris? ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No 3. Float moves freely without binding and poppet moves into flow path? ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No 4. Bypass valve in the drop tube open and free of blockage (if present)? ☒Yes ☐No ☐Not Present ☐Yes ☐No ☐Not Present ☐Yes ☐No ☐Not Present ☐Yes ☐No ☐Not Present 5. Flapper adjusted to shut off flow at 95% capacity? * ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No A "No" to any item in Lines 1-5 indicates a test failure. BALL FLOAT VALVE INSPECTION** 1. Tank top fitting vapor-tight and leak free? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No 2. Ball float cage free of debris? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No 3. Ball free of holes and cracks and moves freely in cage? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No 4. Vent hole in pipe open and near top of tank? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No 5. Ball float pipe proper length to restrict flow to 90% capacity? *** ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No A "No" to any item in Lines 1-5 indicates a test failure. Test Results ☒Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail Comments: *Use manufacturer’s suggested procedure for determining if automatic shutoff device will shut off flow at 95% capacity. **If a ball float valve is found to fail the inspection, another method of overfill must be used. ***Use manufacturer’s suggested procedure for determining if flow restriction device will restrict flow at 90% capacity. Tester’s Name Taber DeHart, UT-0394 Tester’s Signature