HomeMy WebLinkAboutDDW-2024-012649Sanitary Survey - Deficiency Report PWS Number:UTAH07061 Deficiency Points:125 Survey Date:10/28/2024 Survey Name:VALLE DEL PADRES SUBDIV Surveyor:Joe Hadlock Sanitary Survey Category: SM SDWIS Severity Code: Recommendation Management and Operations | DS001 | UTAH07061 DISTRIBUTION SYSTEM 31. Does your water system have an Emergency Response Plan? Rule: R309-105-18 All suppliers are advised to develop contingency plans to cope with possible emergency situations. In many areas of the state the possibility of earthquake damage shall be realistically considered. Notes:Everyone can go home if the water stops working. Deficiency Points: 0 Days until points become effective on IPS: 0 SDWIS Deficiency Description: M001 NO CURRENT EMERGENCY RESPONSE PROGRAM Sanitary Survey Category: SO SDWIS Severity Code: Significant Deficiency Wells | WS001 | HOMEOWNER WELL 64. There are no unprotected cross-connections in well discharge piping. Rule: R309-105-12(1), R309-515-6(12)(d)(iii)Rule requires the well discharge piping to be protected against the entrance of contamination. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:There is a drain used to drain the line from the well to the tanks that doesn't have the 12" clearance about the ground. Deficiency Points: 50 Days until points become effective on IPS: 120 SDWIS Deficiency Description: S021 CROSS CONN EXISTS IN WELL HOUSE OR AT WELL HEAD Sanitary Survey Category: FW SDWIS Severity Code: Significant Deficiency Storage Tanks | ST001 | STORAGE FACILITY ST001 80C. Access opening lid properly gasketed Rule: R309-545-14(2)Rule requires the access opening to a tank to be furnished with a gasket between the lid and frame. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Gasket was worn out. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID AND FRAME Sanitary Survey Category: FW SDWIS Severity Code: Significant Deficiency Storage Tanks | ST002 | STORAGE FACILITY ST002 94C. Access opening lid properly gasketed Rule: R309-545-14(2)Rule requires the access opening to a tank to be furnished with a gasket between the lid and frame. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Gasket was worn out. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID AND FRAME Sanitary Survey Category: FW SDWIS Severity Code: Significant Deficiency Storage Tanks | ST003 | STORAGE FACILITY ST003 108C. Access opening lid properly gasketed Rule: R309-545-14(2)Rule requires the access opening to a tank to be furnished with a gasket between the lid and frame. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Gasket was worn out. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID AND FRAME