Facility ID: 4001465 Inspection Date: 10/23/2024
DISPENSER DETAILS
DISP
ID/ALT
ID
SUBSTANCE UDC PIPE FLEX LOC
INSTALL
DATE
UDC
INSTALL
DATE
FIRE
VALVE
SAT
PRESENT
UDC
TEST
DISP
FLEX
CP
TEST
1 - 1 Diesel No Booted Steel Flex None None Yes Yes None None
2 - 2 Diesel No Booted Steel Flex None None Yes Yes None None
TANK DETAILS
Tank ID/Alt ID 1 / 1
E-Gen/AST No / No
Siphon/Compart No / No
Tank Status Currently In Use
Installed/Cap/Loc Dec. 20, 1988 / 15000 / Single
Substance Stored Diesel / Diesel #2 (U.L.S.)
Tank Material-
Mod
Fiberglass Reinforced Plastic-
None
ATG /
LTT Test None
LLD Test May 21, 2024
Pipe Material-
Mod
Fiberglass Reinforced Plastic /
None
Pipe type/STP
Cont Pressurized / Yes
STP Flex
Connectors Steel Flex in Sump
LLD Model Red Jacket / VR FX1V
Spill/Overfill/Sm
Delivery
5 gal. Double Walled Spill Bucket /
Automatic shutoff / No
PST Fund/Other
Type Yes / None
Tank/Pipe Rel
Det
TankSIR
PipeAutoLineLeakDetection /
PipeSIR
CP Tank Test None
CP Pipe Test None
INSPECTION COMMENTS
None
2024-10-23 Page 1 of 4
FACILITY RESPONSES
Financial Responsibility
Financial responsibility method is ok?Yes
The above accurately represents the
facility's release detection records Yes
Operator Training
A Operator current?Yes
B Operator current?Yes
Monthly checklist available and
complete?No
Is the site unmanned?No
C Operators trained?Yes
TANK RESPONSES
Tank 1 Spill/Overfill
Tank has a spill prevention device?Yes
Are you able to visually inspect the spill
containment bucket(s) for functionality?
(i.e. are the buckets clean enough to
see cracks, etc?)
Yes
Is the spill containment bucket intact?Yes
Is the spill containment bucket(s) able
to contain a spill? (i.e. is there water,
product, debris, etc in the spill bucket
to prevent it from containing a spill?)
Yes
Tank has an overfill device?Yes
Tank 1 Cathodic Protection
Tanks are protected from corrosion?Yes
Piping is protected from corrosion?Yes
Flex connectors at the tank sub-pumps
are protected from corrosion?Yes
Containment sumps are sealed, free
from water, product, etc?Yes
Tank 1 Pressure Piping Leak Detection
Does the pressurized piping system
have a line leak detector?Yes
Does the pressurized piping system
have a valid line leak detector test?Yes
Does the pressurized piping system
have a valid annual line tightness test
or valid monthly monitoring?
Yes
Tank 1 Spill/Overfill
Does the spill bucket have a valid 3-
year test, valid monthly monitoring for
DW buckets, or the tank is exempt?
Yes
Does the overfill device have a valid 3-
year test or the tank is exempt?Yes
2024-10-23 Page 2 of 4
Tank 1 SIR/MTG
SIR - Dispensers have current
calibration stickers or proper calibration
documentation?
Yes
SIR - Drop tubes are present and
extend to within one foot of the tank
bottom?
Yes
SIR - Inventory readings for product
inputs, withdrawals, and the amount
remaining in the tank are recorded and
available for each operating day?
Yes
SIR - Product inputs are reconciled with
delivery receipts by measurement of
the tank inventory volume before and
after deliveries?
Yes
SIR - Records include the appropriate
number of water readings, and water
readings are used to adjust inventory
balances as necessary?
Yes
SIR/MTG - An appropriate calibration
chart is used to convert product level
readings to gallons, and is available for
review?
Yes
SIR/MTG - Inventory readings are
properly reconciled monthly (weekly
and monthly for MTG) to the
appropriate allowable amount?
Yes
SIR/MTG - Equipment used to take
readings (ATG, Gauge Stick, etc.) is
adequate, accessible, and operational?
Yes
SIR/MTG - Documentation of valid
testing or monitoring is available (must
have records for the two most recent
months and 10 of last 12 months)?
Show results in the RD tab.
Yes
DISPENSER RESPONSES
Dispenser 2
Flex connectors at the dispensers are
protected from corrosion?Yes
Fire valve is anchored properly?Yes
Does the line tightness test port on the
fire valve have the manufacturers plug
installed in it? (no ball valves)
Yes
Is the fire valve located properly below
grade?Yes
Is the fire valve's fuseable link intact?Yes
Dispenser 1
Flex connectors at the dispensers are
protected from corrosion?Yes
Fire valve is anchored properly?Yes
Does the line tightness test port on the
fire valve have the manufacturers plug
installed in it? (no ball valves)
Yes
Is the fire valve located properly below
grade?Yes
Is the fire valve's fuseable link intact?Yes
MONTHLY LEAK DETECTION MONITORING
Oct '23 Nov '23 Dec '23 Jan '24 Feb '24 Mar '24 Apr '24 May '24 Jun '24 Jul '24 Aug '24 Sep '24
Tank 1 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass
Line Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass
NON-COMPLIANCE ITEMS
FACILITY
No Photos
2024-10-23 Page 3 of 4
Prepared by fueloperator.com
Question:Monthly checklist available and complete?
Comments:None
Inspection Information
Inspector:Warner, Sean
Record Created:Oct. 23, 2024, 9:28 a.m.
Inspection Date:Oct. 23, 2024