PRODUCT PIPING INTEGRITY TESTING
Facility Name: Swire Coca Cola Owner: Swire Coca Cola, USA
Address: 12634 South 265 West Address: 12634 South 265 West
City, State, Zip: Draper, Utah 84020 City, State, Zip: Draper, Utah 84020
Facility I.D.#: 4002647 Phone #: 385-256-4026
Testing Company: Westech Phone #: 801-266-2545 Date: 8/1/24
This procedure is to test the integrity of product piping. Tests were performed with Petro-Tite line tester.
Tank Number 1 2
Product Stored RUL DSL
Piping Run Only Only
Piping Type Flex D/W Flew D/W
Test Pressure (PSI) 50 50
Test Duration (minutes) 30 30
Leak Rate (GPH) 0.001 0.000
Test Results ☒Pass ☐Fail ☒Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail
Comments:
Tester’s Name Taber DeHart, UT-0394 Tester’s Signature
DSLRUL
RUL RUL
DSL
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
PRESSURE/VACUUM VENT CAP
LEAK RATES AND OPENING PRESSURES
Facility Name: Swire Coca Cola Owner: Swire Coca Cola, USA
Address: 12634 South 265 West Address: 12634 South 265 West
City, State, Zip: Draper, Utah 84020 City, State, Zip: Draper, Utah 84020
Facility I.D.#: 4002647 Phone #: 385-256-4026
Testing Company: Westech Phone #: 801-266-2545 Date: 8/1/24
This procedure is to determine pressure/vent cap specifications. See 40 CFR 63 CCCCCC for the inspection procedure.
Tank Number 1
Product Grade RUL
PV Manufacturer OPW
Model Number 623V
PRESSURE TEST
Passing 2” Leak Rate (CFH) <0.05
Measured 2” Leak Rate (CFH) New Cap
Passing Positive Opening Pressure (Inches WC) 2.5 – 6.0
Measured Positive Opening Pressure (Inches WC) New Cap
VACUUM TEST
Passing -4” Leak Rate (CFH) <0.21
Measured -4” Leak Rate (CFH) New Cap
Passing Negative Opening Pressure (Inched WC) 6.0 – 10.0
Measured Negative Opening Pressure (Inched WC) New Cap
Test Results ☒Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail
New P/V cap installed 8/1/24
Tester’s Name Taber DeHart, UT-0394 Tester’s Signature