Loading...
HomeMy WebLinkAboutDDW-2024-012557Sanitary Survey - Deficiency Report PWS Number:UTAH20010 Deficiency Points:15 Survey Date:10/01/2024 Survey Name:WALES TOWN WATER SYSTEM Surveyor:Jason Hatch Sanitary Survey Category: FW SDWIS Severity Code: Minor Deficiency Storage Tanks | ST001 | STORAGE TANK #1 103A. Mild deterioration or spalling? Rule: R309-545-6(1) and 545-9(1)Rule requires all water storage tanks to have suitable watertight roofs and sidewalls that shall also exclude birds, animals, insects, and excessive dust. Notes:Rusted parts under access lid Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: V021 STORAGE TANK ROOF OR SIDEWALLS SHOW SIGNS OF MILD OR MODERATE DETERIORATION