HomeMy WebLinkAboutDDW-2024-012550Sanitary Survey - Deficiency Report
PWS Number:UTAH03052 Deficiency Points:5 Survey Date:10/18/2024
Survey Name:ZOLLINGER WAREHOUSE Surveyor:Tom McOmie
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Wells | WS001 | ZOLLINGER WELL
72. Well discharge line has a means to measure flow.
Rule: R309-515-6(12)(d)(iv)Rule requires the discharge piping to be equipped with (in order of placement from the
wellhead) a smooth nosed sampling tap, a check valve, a pressure gauge, a means of
measuring flow, and a shutoff valve.
Notes:Existing Deficiently
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: S026 NO FLOW METER ON WELL DISCHARGE PIPING