Find below fixes for item 6,8 and 9. The leak on the hypo tank cannot be fixed till the tank is empty and will
required a short shutdown, so will not be fixed for several weeks. The drain for the two refinery tanks has
not been located and will have to submit this to the DDW when we do. Thanks for your patience.
#3 The chlorinator hypochlorite solution tank was leaking.
We will not be able to fix this leak till the tank is empty.
#6 The lower refinery tank access was locked and unopenable so we could not verify the gasket.
#7 . The drain lines for the upper and lower refinery tanks could not be located. Need to verify they have at
least 12” of freefall from the outlet.
Still have not located the drain for these tanks. Will have to send later to DDW.
#8 & #9 Magna Storage Tank.
With the decommissioning and current demolish of our Power Plant the water from the Magna
Storage Tank is no longer used for culinary purposes and is strictly for process water. We would like this
tank designated as inactive for culinary. We have modified the tank fill pipe to have an air gap into the tank.
Trevor Paulson
Advisor - Water
Rio Tinto Kennecott
4700 Daybreak Parkway, South Jordan Utah 84009
T: (801)304-1256
M: (385)246-7937
From: Brad Johnson <BradJohnson@saltlakecounty.gov>
Sent: Tuesday, September 17, 2024 8:38 AM
To: Paulson, Trevor (RTKC) <Trevor.Paulson@riotinto.com>
Subject: RE: [External] Kennecott Section 21 sanitary survey follow up
Trevor,
Thank you for taking care of those items and providing documentation. I look forward to seeing the rest of
the documentation.
Regards,
Brad Johnson
(he/him)
Environmental Health Scientist
Water Quality & Hazardous Waste Bureau
o 385-468-3898
C 385-228-7540
bradjohnson@saltlakecounty.gov
Please note that my email address is now bradjohnson@saltlakecounty.gov.
My bradjohnson@slco.org address will forward and continue to work for now, but please
update my information in your records.
From: Paulson, Trevor (RTKC) <Trevor.Paulson@riotinto.com>
Sent: Tuesday, September 17, 2024 8:20 AM
To: Brad Johnson <BradJohnson@saltlakecounty.gov>
Subject: RE: [External] Kennecott Section 21 sanitary survey follow up
Brad,
Below find repairs for the below deficiencies. Sorry for the delay. We are working on some of the others
and will get them to you by the end of the week.
Thanks.
1. There was a cross connection observed from a hose placed into a horse water trough next to the
well #14 replacement.
This was fixed by installing an air gap.
2. Well #14 replacement had a broken pressure gauge.
Guage replaced.
3.
4. Well #11 lacks a pressure gauge on the discharge piping.
Guage installed.
5. The upper refinery tank access hatch needs the gasket replaced.
Gasket replaced.
Trevor Paulson
Advisor - Water
Rio Tinto Kennecott
4700 Daybreak Parkway, South Jordan Utah 84009
T: (801)304-1256
M: (385)246-7937
From: Brad Johnson <BradJohnson@saltlakecounty.gov>
Sent: Tuesday, August 27, 2024 3:40 PM
To: Paulson, Trevor (RTKC) <Trevor.Paulson@riotinto.com>
Cc: Fuaad Hararah <FHararah@saltlakecounty.gov>
Subject: [External] Kennecott Section 21 sanitary survey follow up
Trevor,
Thank you again for your time and cooperation today with the Kennecott Section 21 sanitary survey.
Here’s a short list of items observed during the survey that will show up as deficiency points:
1. There was a cross connection observed from a hose placed into a horse water trough next to
the well #14 replacement.
2. Well #14 replacement had a broken pressure gauge.
3. The chlorinator hypochlorite solution tank was leaking.
4. Well #11 lacks a pressure gauge on the discharge piping.
5. The upper refinery tank access hatch needs the gasket replaced.
6. The lower refinery tank access was locked and unopenable so we could not verify the gasket.
7. The drain lines for the upper and lower refinery tanks could not be located. Need to verify they
have at least 12” of freefall from the outlet.
8. The Magna Culinary Reserve tank had three active leaks on the side walls.
9. The Magna Culinary Reserve tank drain and overflow could not be located.
The survey report needs to be sent to the DDW within the next 30 days. If you could provide any updates
on these items in the next week or so before I send the report in, I can send in a correction notice at the
same time as the report to have the points removed. Photos of drain lines, gaskets and other repairs
would suffice.
Let me know if you have any questions or if I can be of further assistance.
Sincerely,
Brad Johnson
(he/him)
Environmental Health Scientist
Water Quality & Hazardous Waste Bureau
o 385-468-3898
C 385-228-7540
bradjohnson@saltlakecounty.gov
Please note that my email address is now bradjohnson@saltlakecounty.gov.
My bradjohnson@slco.org address will forward and continue to work for now, but please
update my information in your records.