HomeMy WebLinkAboutDDW-2024-012496Sanitary Survey - Deficiency Report
PWS Number:UTAH25035 Deficiency Points:30 Survey Date:09/20/2024
Survey Name:WILDWOOD SUBDIVISION Surveyor:Russ Franklin
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Management and Operations | DS001 | UTAH25035 DISTRIBUTION SYSTEM
28A. System lacks up to 20% of required source capacity
Rule: R309-510-7(1)Rule requires a water system's source capacity to legally and physically meet the peak
day demand and the average yearly demand.
Notes:Should have 60K on hand and only has 50K tank
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: S091 SYSTEM LACKS UP TO 20% OF REQUIRED SOURCE CAPACITY
Sanitary Survey Category: FW
SDWIS Severity Code: Minor Deficiency
Management and Operations | DS001 | UTAH25035 DISTRIBUTION SYSTEM
29A. System lacks required storage capacity due to fire demand
Rule: R309-510-8(1)(b)Rule requires a public water system to provide equalization storage volume (to meet
average day demands for indoor and irrigation water use), fire flow storage volume (if
equipped with fire hydrants for fire suppression or required by the local fire code
official), and emergency storage (if deemed appropriate by the water system or the
Director).
Notes:Short 10,000 gallons of storage
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: VF34 SYSTEM LACKS REQUIRED STORAGE CAPACITY DUE TO FIRE DEMAND BUT
HAS SOP FOR FOLLOWING FIRE INCIDENT