Loading...
HomeMy WebLinkAboutDDW-2024-012496Sanitary Survey - Deficiency Report PWS Number:UTAH25035 Deficiency Points:30 Survey Date:09/20/2024 Survey Name:WILDWOOD SUBDIVISION Surveyor:Russ Franklin Sanitary Survey Category: SO SDWIS Severity Code: Minor Deficiency Management and Operations | DS001 | UTAH25035 DISTRIBUTION SYSTEM 28A. System lacks up to 20% of required source capacity Rule: R309-510-7(1)Rule requires a water system's source capacity to legally and physically meet the peak day demand and the average yearly demand. Notes:Should have 60K on hand and only has 50K tank Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: S091 SYSTEM LACKS UP TO 20% OF REQUIRED SOURCE CAPACITY Sanitary Survey Category: FW SDWIS Severity Code: Minor Deficiency Management and Operations | DS001 | UTAH25035 DISTRIBUTION SYSTEM 29A. System lacks required storage capacity due to fire demand Rule: R309-510-8(1)(b)Rule requires a public water system to provide equalization storage volume (to meet average day demands for indoor and irrigation water use), fire flow storage volume (if equipped with fire hydrants for fire suppression or required by the local fire code official), and emergency storage (if deemed appropriate by the water system or the Director). Notes:Short 10,000 gallons of storage Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: VF34 SYSTEM LACKS REQUIRED STORAGE CAPACITY DUE TO FIRE DEMAND BUT HAS SOP FOR FOLLOWING FIRE INCIDENT