Loading...
HomeMy WebLinkAboutDDW-2024-012435Sanitary Survey - Deficiency Report PWS Number:UTAH25034 Deficiency Points:5 Survey Date:10/09/2024 Survey Name:GOOSENEST WATER COMPANY Surveyor:Russ Franklin Sanitary Survey Category: SO SDWIS Severity Code: Minor Deficiency Wells | WS002 | SHULER WELL 84. Wells that pump directly into a distribution system have means to release trapped air from pump discharge piping (for example, pumps directly to a tank, has an air release valve or pump to waste line) Rule: R309-515-6(12)(d)(v)Rule requires a well that pumps directly into the distribution system be equipped with an air release/vacuum relief valve located upstream of the check valve, unless the wellhead valve and piping provide for pumping to waste all trapped air before water is introduced into the distribution system. Notes:No pump to waste line to release trapped air. This pump can pump directly into the system and not only to the tanks. Deficiency Points: 5 Days until points become effective on IPS: 0 SDWIS Deficiency Description: SL01 WELL THAT PUMPS DIRECTLY TO DISTRIBUTION LACKS A MEANS TO RELEASE TRAPPED AIR