HomeMy WebLinkAboutDDW-2024-012435Sanitary Survey - Deficiency Report
PWS Number:UTAH25034 Deficiency Points:5 Survey Date:10/09/2024
Survey Name:GOOSENEST WATER
COMPANY
Surveyor:Russ Franklin
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Wells | WS002 | SHULER WELL
84. Wells that pump directly into a distribution system have means to release trapped air from pump discharge piping (for example, pumps
directly to a tank, has an air release valve or pump to waste line)
Rule: R309-515-6(12)(d)(v)Rule requires a well that pumps directly into the distribution system be equipped with
an air release/vacuum relief valve located upstream of the check valve, unless the
wellhead valve and piping provide for pumping to waste all trapped air before water is
introduced into the distribution system.
Notes:No pump to waste line to release trapped air. This pump can pump directly into the system
and not only to the tanks.
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: SL01 WELL THAT PUMPS DIRECTLY TO DISTRIBUTION LACKS A MEANS TO RELEASE
TRAPPED AIR