HomeMy WebLinkAboutDDW-2024-012414System Number 15044
1.1 Indoor Water Use
Number of residential connections - - - - - - - - - - -- - - - - - - - - - - - - - - - - - -- - - - - - - - -750
Number of other connections - - - ERCs of other connections 0.0
Total Equivalent Residential Connections (ERCs)750.0
gpd/ERC Total (gpm) Gallons/ERC Total (gallons)
800 416.7 400 300,000
1.2 Outdoor Water Use
Is the drinking water used for outdoor irrigation?
Residential ERCs using drinking water for irrigation - - - - - - - - - - - - > > >0
Percentage of Residential ERCs using DW for irrigation - - - - - - - - - - - - > > >0%Map Zones
Average irrigated acreage per residential connection - - - - - - - - - - - - > > >0.00 1
Total irrigated acreage of other connections (park, school, etc.)- - - - - - - - - - - - > > >0.00 2
Irrigation zone 1 3
4
5
6
gpd/ERC Total (gpm) Gallons/ERC Total (gallons)
0 0.0 0 0
1.3 Fire Flow Water Use
Does the water system provide fire protection?
Maximum fire flow demand (in gpm) for water system or pressure zone 0
Maximum fire suppression duration (in hours) for water system or pressure zone 0
Required Fire Suppression Storage (in gallons) - - - - - - - - - - - - - - - - - - - - > > >0
2. Summary of Water System Capacity Requirements
gpd/ERC Total (gpm) Gallons/ERC Total (gallons)
800 416.7 400 300,000
2.1 Does this system have adequate source capacity (per R309-510-7)?
Required Source Capacity 416.7 gpm
Existing Source Capacity 1,199.0 gpm
Source Capacity Deficit None gpm
Existing % of Total Req'd 287.8%
MIN. REQUIREMENTS FOR INDOOR WATER USE
MINIMUM REQUIREMENTS FOR WATER SYSTEM
Division of Drinking Water — Water System Capacity Calculation Sheet (Last Update 3/30/2017)
*Enter the green cells only*
(Example: water use of 2 factories
equals to water use of 55 homes.)
Source
MIN. REQUIREMENTS FOR IRRIGATION USE
System Name
Source
Wasatch Peaks Ranch Resort
Storage
(Enter notes here regarding whether and what %
of irrigation water is supplied by PWS.)
Source (indoor + outdoor)
Storage
Storage (indoor + outdoor + fire)
This source capacity assessment is a general overall system calculation. It may not reflect the variations in individual areas or pressure zones.
Yes No
Yes No
2022 Capacity Calculations Page 1 of 2 10/18/2024
2.2 Does this system have adequate storage capacity (per R309-510-8)?
Total Required Storage 300,000 gal
Existing Storage Capacity 400,000 gal
Storage Capacity Deficit None gal
Required Fire Storage 0 gal
Not
Applicable
Existing % of Total Req'd 133.3%
3. Transient PWS Indoor Water Use — ERC Calcuation (See R309-510, Tables 510-1, 2, & 4 for other facility types.)
GPD/person* GPD/site or pad Gallons/person
Gallon/site
or pad ERC/site or pad Total # of
sites/pads ERCs
60 0 30 0 0.00 0 0.0
20 0 10 0 0.00 0 0.0
5 0 2.5 0 0.00 0 0.0
N/A 100 N/A 50 0.13 0 0.0
Number of people per camp site 0
Source
(GPD/vehicle)
Storage
(Gal./vehicle)
ERC/1000
vehicles served
Vehicles
served/day ERCs
7 3.5 8.8 0 0.0
4. Data Input for Calculating ERCs, Source and Storage 4.2 Summary - Existing Sources (enter in green cells below)
Total Existing Source Capacity (in gpm)1,199
4.1 Projected ERCs Calculation (optional)WS001 WELL A 770
Total Projected ERCs 750 WS003 WELL A2 429
Existing Residential Connections 750
Obligated Future ERCs (enter below)
Maximum ERCs (assuming indoor use only) 2158.2
4.3 Summary - Existing Storage Tanks (enter below)
Total Existing Storage Cap. (in gallons)400,000
ST001 TANK 1 100,000
ST002 TANK 2 100,000
ST003 TANK 3 100,000
ST004 TANK 4 100,000
RV Park
Facility Type
Source
MINIMUM REQUIREMENTS FOR INDOOR USE
Modern Recreation Camp
Storage
Semi-Developed Camp w/ flush toilets
Wasatch Peaks Ranch Resort
Roadway Rest Stop w/ flushometer valves
Semi-Developed Camp w/o flush toilets
This storage capacity assessment is a general overall system calculation. It may not reflect the variations in individual areas or pressure zones.
Is storage deficiency solely due
to fire storage?
2022 Capacity Calculations Page 2 of 2 10/18/2024