HomeMy WebLinkAboutDDW-2024-012396
195 North 1950 West • Salt Lake City, UT
Mailing Address: P.O. Box 144830 • Salt Lake City, UT 84114-4830
Telephone (801) 536-4200 • Fax (801) 536-4211 • T.D.D. (801) 536-4414
www.deq.utah.gov
Printed on 100% recycled paper
State of Utah
SPENCER J. COX
Governor
DEIDRE HENDERSON
Lieutenant Governor
Department of
Environmental Quality
Kimberly D. Shelley
Executive Director
DIVISION OF DRINKING WATER
Nathan Lunstad, Ph.D., P.E.
Director of Drinking Water
October 1, 2024
Zachary Lowe
Devils Canyon Campground
USFS-Manti Lasal
599 West Price Dr.
Price, UT 84501
Subject: Corrective Action Plan for Devils Canyon Campground, UTAH19018 (2024-01)
Dear Zachary Lowe:
The Division of Drinking Water (the Division) has received your request for a Corrective Action
Plan to address the significant deficiencies associated with the Devils Canyon Campground water
system. A copy of the Corrective Action Plan is enclosed with this letter. Please review the
agreement and sign a copy if you agree with the terms and return the signed copy to the Division
within 14 days of receipt of this agreement. A copy of the fully executed document will be returned
to you.
Please contact Brandi Smith at (385) 515-1650 or brandismith@utah.gov if you have any questions
regarding this letter or the enclosed copy of Corrective Action Plan.
Sincerely,
Helen Lau
Compliance and Operations Manager
Division of Drinking Water
Enclosures –Devils Canyon Campground Corrective Action Plan 2024-01
cc: Dennis Shumway, San Juan County Health Department, dshumway@sanjuancounty.org
Curtis Page, P.E. Division District Engineer, cmpage@utah.gov
Zachary Lowe, Devils Canyon Campground, Zachary.lowe2@usda.gov
' ) 0 — / C v A ? A C @ C w ? C ˜
Corrective Action Plan (2024-01)
Devils Canyon Campground – UTAH19018
The purpose of this Corrective Action Plan (“CAP”) is to establish terms and conditions of
compliance for Devils Canyon Campground (“System”), system number UTAH19018, to take
actions and correct significant deficiencies identified in Exhibit A.
The Corrective Action Plan terms and conditions are described in detail in Exhibit A. As long as
the System complies with every one of the requirements in Exhibit A, the Division will:
• Temporarily allow the extended deadlines for correcting the identified significant
deficiencies,
• Temporarily hold off assessing additional points for failure to fix violations, and
• Temporarily silence the significant deficiencies and hold off reporting those to US EPA.
Nothing in this Corrective Action Plan prohibits the Division from taking further enforcement
actions if the System fails to comply with any of the requirements in Exhibit A or if an imminent
public risk exists in the System.
We the undersigned parties agree to the terms, conditions and deadlines set forth in the Corrective
Action Plan (see Exhibit A).
___________________________________ ___________________________________
Helen Lau Zachary Lowe
Compliance & Operations Manager Devils Canyon Campground
_______________________, 2024 _______________________, 2024
# - 4 u * 2 Helen Lau (Oct 11, 2024 14:57 MDT)
CAP Page 1
Exhibit A
Corrective Action Plan UTAH19018, 2024-01
System Name: Devils Canyon Campground
System Number: UTAH19018
Administrative Contact: Zachary Lowe
Email: Zachary.lowe2@usda.gov
Phone Number:
Corrective Action Plan Requirements and Due Dates
Distribution System (DS001)
Item #1 Deficiency
Code
Facility
ID
Significant Deficiency Rule Citation
M017 DS001 Water stagnation, biofilm or sediments
contributes to drinking water contamination
R309-200-6, R309105-18,
R309215-4(3)
Corrective Action Requirements Due Date
Ensure that there is no water stagnation, biofilm or sediments
contributes to drinking water contamination
06/01/2025
Item #2 Deficiency
Code
Facility
ID
Significant Deficiency Rule Citation
V012 DS001 End of storage tank overflow pipe lacks a
No.4 Screen
R309-545-13(3)
Corrective Action Requirements Due Date
Ensure that the storage tank overflow pipe has a no.4 screen 05/01/2025
Item #3 Deficiency
Code
Facility
ID
Significant Deficiency Rule Citation
V009 ST002 Storage tank lid lacks a functioning gasket
between the lid and frame
R309-545-14(2)
Corrective Action Requirements Due Date
Ensure that the storage tank lid has a proper gasket between the lid and
frame
05/01/2025
CAP Page 2
Item #4 Deficiency
Code
Facility
ID
Significant Deficiency Rule Citation
SS10 WS001 Spring box lid lacks a gasket R309-515-7(7)(d), R309-
545-14(2)
Corrective Action Requirements Due Date
Ensure that the spring box lid has a proper gasket 05/01/2025
Item #5 Deficiency
Code
Facility
ID
Significant Deficiency Rule Citation
SS20 WS001 Unsealed openings in the spring collection
box
R309-515-7(7)(d), R309545-
9(1) and (2)
Corrective Action Requirements Due Date
Ensure that the openings in the spring box have been properly repaired 06/01/2025
Signature:
Email:zachary.lowe2@usda.gov