HomeMy WebLinkAboutDDW-2024-012377
Michael Newberry, Permitting Manager October 18, 2024
Division of Drinking Water
195 North 1950 West
Salt Lake City, UT 84114
RE: Certification of Rule Conformance
Mayflower Mountain Resort Tank #2, Pump Station #1, Flow Control Valve #1
DDW File #16872
Jordanelle Special Services District System #18049
Dear Michael,
Pursuant to the Utah Administrative Code R309-500 through R309-550, I am providing this
certification of rule conformance. I, Nicholas E. Graue, hereby certify that I am a Registered
Professional Engineer holding registration number 10638374-2202 in the State of Utah. I
declare that all UAC Rules were accomplished for the Mayflower Mountain Resort Tank #2,
Pump Station #1, Flow Control Valve #1 Project (DDW File #16872) of the Jordanelle Special
Services District (JSSD) System #18049, I specifically note the following project conditions:
1. No changes to the plans or specifications were made during construction.
2. Record drawings have been provided to the water system owner, Jordanelle Special
Services District (JSSD).
3. Evidence of proper flushing and disinfection in accordance with AWWA standards is
included in this submittal.
Should the Division have any questions or concerns pertaining to this project, please reach out
to me directly. My contact information can be found below.
Sincerely,
Nick Graue, P.E.
AQUA Engineering
nick.graue@aquaeng.com
(801) 683-3733
Copy:
Steve Jackson, Jordanelle Special Services District (steve@jackson-engineering.com)
Kent Fawcett, Extell Development (kfawcett@extell.com)
AQUA Engineering Project #1695.C
A: Absence: R: Routine P: Presence: I: Investigative Page 1 of 1
+ JORDANELLE SPECIAL SERVICE DISTRICT JORDANELLE LABORATORY
Po. Box 519 Phone: 435-333-0475 Heber City Ut. 84032 Form: 28 Fax: 435-333-0513 Microbiological Analysis of Water Samples Standard Methods 20th, 9223B, Presence/ Absence (P/A), Colilert MONTH: October 2024 CUSTOMER: Jordanelle SSD SYSTEM #:
DATE COLLECTED ID CODE UNIQUE LAB ID # SAMPLING POINT TIME R,I CL2 SAMPLER INITIALS RESULT
Total Coliforms E.coli
10/17/2024 B6495 R005643 Hyd 10’ East of flow control valve 0935 I .90 C.R. A A
10/17/2024 B6499 R005644 Hyd 10’ East of flow control valve 0950 I .90 C.R. A A
Analyzed by: T.B. Approved by: Date: 10/18/2024
Wade C. Webster
DDW-Eng-0010 Page 1 of 1 12/8/2015
Utah Division of Drinking Water ― Checklist for Issuing Operating Permits
(Per Utah Administrative Code, Rule R309-500-9)
Water System Name: Jordanelle SSD System Number: 26086
Project Description: Mayflower Flow Control Valve, Pump Station #1, Tank #2 File Number: 16872
Items 1 through 8 below must be submitted to the Division and found to be acceptable prior to operating
permit issuance. However, distribution lines without booster pumps may be placed into service prior to
submitting all of the items if a professional engineer (PE) responsible for the entire water system has been
identified to the Director and has received items 1 through 4 below. [In this case, a public water system will
submit all items needed to obtain an Operating Permit for each distribution system project after the new water lines
have been placed into service as determined by the water system’s designated PE.]
☐ 1. Certification of Rule Conformance by a PE that all conditions of Plan Approval have been
accomplished, and if applicable, changes made during construction were in conformance with
rules R309-500 through 550
☐ 2. As-built or record drawings incorporating all changes to approved plans and specifications,
unless no changes were made to the previously submitted and approved pre-construction
drawings
☐ 3. Confirmation that as-built or record drawings have been received by the water system
☐ 4. Evidence that bacteriological samples have been collected to verify proper flushing and
disinfection in accordance with the appropriate ANSI/AWWA Standards:
☐ ANSI/AWWA C651-14 AWWA Standard for Disinfecting Water Mains
Two consecutive sample sets at least 16 hours apart, none positive (every 1200 feet, end-
of-line, each branch, etc.)
☐ ANSI/AWWA C652-11 AWWA Standard for Disinfection of Water-Storage Facilities
One or more samples, none positive
☐ ANSI/AWWA C653-13 AWWA Standard for Disinfection of Water Treatment Plants
Two consecutive samples per unit, none positive, no less than 30 minutes apart
☐ ANSI/AWWA C654-13 AWWA Standard for Disinfection of Wells
Two consecutive samples, none positive, no less than 30 minutes apart
☐ 5. Water quality data, where appropriate [Guidance: Include appropriate raw and finished water data
that demonstrate satisfactory performance of the new treatment facility. Storage tank water shall be
analyzed for residual volatile organic compounds after tank interior painting or re-coating.]
☐ 6. If applicable, all other documentation that may have been required during the plan review
process
☐ 7. If applicable, confirmation that the water system owner has received the O&M manual for the
new facility
☐ 8. If applicable, location data of new storage tank, treatment facility, or source
A: Absence: R: Routine P: Presence: I: Investigative Page 1 of 1
+ JORDANELLE SPECIAL SERVICE DISTRICT JORDANELLE LABORATORY
Po. Box 519 Phone: 435-333-0475 Heber City Ut. 84032 Form: 28 Fax: 435-333-0513 Microbiological Analysis of Water Samples Standard Methods 20th, 9223B, Presence/ Absence (P/A), Colilert MONTH: September 2024 CUSTOMER: Jordanelle SSD SYSTEM #:
DATE COLLECTED ID CODE UNIQUE LAB ID # SAMPLING POINT TIME R,I CL2 SAMPLER INITIALS RESULT
Total Coliforms E.coli
9/24/2024 B6448 R005596 Sample Tap at Pump Station 1525 I .52 C.R. A A
9/24/2024 B6453 R005597 Sample Tap at Pump Station 1532 I .54 C.R. A A
9/24/2024 B6449 R005598 Sample Tap at Pump Station 1537 I .50 C.R. A A
Analyzed by: M.S. Approved by: Date: 9/26/2024
Wade C. Webster
A: Absence: R: Routine P: Presence: I: Investigative Page 1 of 1
+ JORDANELLE SPECIAL SERVICE DISTRICT JORDANELLE LABORATORY
Po. Box 519 Phone: 435-333-0475 Heber City Ut. 84032 Form: 28 Fax: 435-333-0513 Microbiological Analysis of Water Samples Standard Methods 20th, 9223B, Presence/ Absence (P/A), Colilert MONTH: October 2024 CUSTOMER: Jordanelle SSD SYSTEM #:
DATE COLLECTED ID CODE UNIQUE LAB ID # SAMPLING POINT TIME R,I CL2 SAMPLER INITIALS RESULT
Total Coliforms E.coli
10/16/2024 B6470 R005639 Tank #1 1202 I .79 C.R. A A
10/16/2024 B6458 R005640 Tank #1 1203 I .79 C.R. A A
10/16/24 B6456 R005641 Tank #2 1220 I .00 C.R. A A
10/16/24 B6451 R005642 Tank #2 1225 I .00 C.R A A
Analyzed by: T.B. Approved by: Date: 10/17/2024
Wade C. Webster