HomeMy WebLinkAboutDERR-2024-011506 WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
AUTOMATIC TANK GAUGE OPERATION INSPECTION
Facility Name: Meadowbrook Division Owner: Utah Transit Authority
Address: 3600 South 700 West Address: 200 South 669 West
City, State, Zip: Salt Lake City, Utah 84119 City, State, Zip: Salt Lake City, Utah 84101
Facility I.D.#: 4001131 Phone #: 801-558-5231
Testing Company: Westech Phone #: 801-266-2545 Date: 9/23/24
This procedure is to determine whether the automatic tank gauge (ATG) is operating properly. See PEI/RP1200 Section 8.2 for the inspection
procedure. This procedure is applicable to tank monitor stems that touch the bottom of the tank when in place.
Tank Number 5 6 8
Product Stored 90W 15W/40 Used Oil
ATG Brand and Model Incon Incon Incon
1. Tank Volume, gallons 2,005 1,003 6,045
2. Tank Diameter, inches 64 64 84
3. After removing the ATG from the tank, it has been
inspected and any damaged or missing parts replaced? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
4. Float moves freely on the stem without binding? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
5. Fuel float level agree with the value programmed into
the console? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
6. Water float level agree with the value programmed into
the console? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
7. Inch level from the bottom of the stem when 90% alarm
is triggered? 53 1/2 53 1/2 58 1/2
8. Inch level at which the overfill alarm activates
corresponds with the value programmed in the gauge? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
9. Inch level from the bottom when the water float first
triggers an alarm? 2 2 6
10. Inch level at which the water float alarm activates
corresponds with the value programmed in the gauge? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
If any answers in Lines 3, 4, 5, or 6 are "No" the system has failed the test.
Test Results ☒Pass ☐Fail ☒Pass ☐Fail ☒Pass ☐Fail ☐Pass ☐Fail
Comments:
Tester’s Name Taber DeHart, UT-0394 Tester’s Signature
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
OVERFILL ALARM OPERATION INSPECTION
Facility Name: Meadowbrook Division Owner: Utah Transit Authority
Address: 3600 South 700 West Address: 200 South 669 West
City, State, Zip: Salt Lake City, Utah 84119 City, State, Zip: Salt Lake City, Utah 84101
Facility I.D.#: 4001131 Phone #: 801-558-5231
Testing Company: Westech Phone #: 801-266-2545 Date: 9/23/24
This procedure is to determine whether the automatic tank gauge (ATG) is operating properly. See PEI/RP1200 Section 8.2 for the inspection
procedure. This procedure is applicable to tank monitor stems the touch the bottom of the tank when in place.
Tank Number 5 6 8
Product Stored 90W 15W/40 Used Oil
ATG Brand and Model Incon Incon Incon
1. Tank Volume, gallons 2,005 1,003 6,045
2. Tank Diameter, inches 64 64 84
3. Overfill alarm activates in the test mode at the
console? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
4. When activated, overfill alarm can be heard or seen
while delivering to the tank? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
5. After removing the probe from the tank, it has been
inspected and any damaged or missing parts replaced? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
6. Float moves freely on stem without binding? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
7. Moving product level float up the stem trigger
alarm? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
8. Inch level from bottom of stem when 90% alarm is
triggered? 53 ½ 53 ½ 58 ½
9. Tank volume at inch level in Line 8. 1,804 902 4,495
10. Calculate (Line 9 / Line 1) X 100 90% 90% 74%
11. Is line 10 less than 90%? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
12. Fuel float level on the console agrees with the
gauge stick reading? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
13. Overfill alarm activates at any product level above
90% tank capacity? ☐Yes ☒No ☐Yes ☒No ☐Yes ☒No ☐Yes ☐No
If any answers in Lines 3, 4, 5, 6, 7, or 11 are "No," or Line 13 is “Yes,” the system has failed the test.
Test Results ☒Pass ☐Fail ☒Pass ☐Fail ☒Pass ☐Fail ☐Pass ☐Fail
Comments:
Tester’s Name Taber DeHart, UT-0394 Tester’s Signature
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
SPILL BUCKET INTEGRITY TESTING HYDROSTATIC TEST METHOD
SINGLE- AND DOUBLE-WALLED VACUUM TEST METHOD
Facility Name: Meadowbrook Division Owner: Utah Transit Authority
Address: 3600 South 700 West Address: 200 South 669 West
City, State, Zip: Salt Lake City, Utah 84119 City, State, Zip: Salt Lake City, Utah 84101
Facility I.D.#: 4001131 Phone #: 801-558-5231
Testing Company: Westech Phone #: 801-266-2545 Date: 9/23/24
This procedure is to test the leak integrity of single- and double-walled spill buckets. See PEI/RP1200 Section 6.2 for hydrostatic test
method, Section 6.3 for single-walled vacuum test method and Section 6.4 for double-walled vacuum test method.
Tank Number 5 6
Product Stored 90W 15W/40
Spill Bucket Capacity 5-Gallon 5-Gallon
Manufacturer OPW OPW
Construction ☐Double-walled
☒Single-walled
☐Double-walled
☒Single-walled
☐Double-walled
☐Single-walled
☐Double-walled
☐Single-walled
Test Type
☒Hydrostatic
☐Vacuum
☐Double-walled
☐Single-walled
☒Hydrostatic
☐Vacuum
☐Double-walled
☐Single-walled
☐Hydrostatic
☐Vacuum
☐Double-walled
☐Single-walled
☐Hydrostatic
☐Vacuum
☐Double-walled
☐Single-walled
Spill Bucket Type ☒Product
☐Vapor
☒Product
☐Vapor
☐Product
☐Vapor
☐Product
☐Vapor
Liquid and debris remove from spill
bucket?* ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No
Visual Inspection (no cracks, loose
parts or separation of the bucket from
the fill pipe.)
☒Yes ☐No ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No
Tank Riser cap included in test? ☐Yes ☒No
☐NA
☒Yes ☐No
☐NA
☐Yes ☐No
☐NA
☐Yes ☐No
☐NA
Drain valve included in test? ☐Yes ☐No
☒NA
☐Yes ☐No
☒NA
☐Yes ☐No
☐NA
☐Yes ☐No
☐NA
Starting Level 8 3/8” 10”
Test Start Time 1:31 1:31
Ending Level 8 3/8” 10”
Test End Time 2:31 2:31
Test Period 1 Hour 1 Hour
Level Change 0 o
Pass/fail criteria: Must pass visual inspection. Hydrostatic: Water level drop of less than 1/8 inch; Vacuum single-walled only: Maintain at least 26 inches water
column; Vacuum double-walled: maintain at least 12 inches water column.
Test Results ☒Pass ☐Fail ☒Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail
Comments:
*All liquids and debris must be disposed of properly
Tester’s Name Taber DeHart, UT-0394 Tester’s Signature