HomeMy WebLinkAboutDDW-2024-012360Sanitary Survey - Deficiency Report PWS Number:UTAH19079 Deficiency Points:160 Survey Date:09/18/2024 Survey Name:BLUE MOUNTAIN RANCH RECREATION Surveyor:Curtis Page Sanitary Survey Category: SM SDWIS Severity Code: Minor Deficiency Cross Connection and Operator Certification | DS001 | UTAH19079 DISTRIBUTION SYSTEM 35. Legally adopted authority statement Rule: R309-105-12(2)Rule requires each public water system to have a cross connection control program that includes a legally adopted and functional local authority to enforce the program (i.e., ordinance, bylaw, or policy). Notes:No legally adopted authority statement presented at survey. Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: M003 CCC-LACKS LOCAL AUTHORITY Sanitary Survey Category: SM SDWIS Severity Code: Minor Deficiency Cross Connection and Operator Certification | DS001 | UTAH19079 DISTRIBUTION SYSTEM 36. Documentation of annual public awareness and/or employee training Rule: R309-105-12(2)Rule requires each public water system to have a cross connection control program that includes providing public education or awareness material or presentations. Notes:No evidence of public awareness and/or employee training provided. Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: M004 CCC-NO ANNUAL PUBLIC EDUCATION OR AWARENESS Sanitary Survey Category: SM SDWIS Severity Code: Minor Deficiency Cross Connection and Operator Certification | DS001 | UTAH19079 DISTRIBUTION SYSTEM 38. Does the water system have detailed records of cross connection control activities? (inventories of backflow assemblies, devices, and air gaps installed within the system) Rule: R309-105-12(2)Rule requires each public water system to have a cross connection control program that includes written records of cross connection control activities. Notes:No records of cross connection control activities. Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: M006 CCC-LACKS WRITTEN RECORDS OF CCC ACTIVITIES Sanitary Survey Category: SM SDWIS Severity Code: Minor Deficiency Cross Connection and Operator Certification | DS001 | UTAH19079 DISTRIBUTION SYSTEM 39. Does the water system have records of on-going enforcement activities? (test history, enforcement activities, hazard assessments) Rule: R309-105-12(2)Rule requires each public water system to have a cross connection control program that includes test history and documentation of on-going enforcement activities. Notes:No records of on-going enforcement activities. Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: M007 CCC-LACKS ON-GOING ENFORCEMENT IMPLEMENTATION Sanitary Survey Category: PU SDWIS Severity Code: Significant Deficiency Pump Stations | PF001 | BOOSTER PUMP 128. If the pump station is used to pressurize the distribution system, does it have at least two functioning pumping units? ... if yes, answer the following question(s) Rule: R309-540-5(4)(b)Rule states inline booster pumps, withdrawing water directly from distribution lines without storage and feeding water directly into distribution lines, shall have at least two pumping units. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Only one pump installed. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: PS18 IN-LINE BOOSTER PUMP STATION LACKS REDUNDANCY TO MEET PEAK DEMAND WITH ONE PUMP OUT OF SERVICE Sanitary Survey Category: PU SDWIS Severity Code: Significant Deficiency Pump Stations | PF001 | BOOSTER PUMP 132B. End of air relief piping covered with #14 mesh screen Rule: R309-550-6(6)(b), R309-540-6(2)The open end of the air relief vent pipe from automatic valves shall be provided with a #14 mesh, non-corrodible screen. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:No mesh, add #14 mesh screen to all air vacs. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: PS10 PUMP STATION OR HYDROPNEUMATIC TANK A/V VALVE RELIEF PIPING LACKS NO. 14 SCREEN Sanitary Survey Category: TR SDWIS Severity Code: Significant Deficiency Treatment - Chlorination General | TP001 | BLUE MOUNTAIN CHLORINATOR 162. Chlorine (gas & hypochlorite solution, tablets, granules, ) and chemicals used to generate chlorine solutions and chlorine dioxide meet ANSI/NSF 60. Rule: R309-525-11(5), R309-520-6(2)All chemicals added to drinking water, including chlorine, chloramines and chemicals used to generate hypochlorite solutions and chlorine dioxide, shall be certified as complying with ANSI/NSF Standard 60. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Unable to find ANSI/NSF 60 designation on product container label. Deficiency Points: 50 Days until points become effective on IPS: 120 SDWIS Deficiency Description: TD90 ADDING CHEMICALS THAT DO NOT MEET ANSI NSF 60 STANDARD