HomeMy WebLinkAboutDDW-2024-012343Sanitary Survey - Deficiency Report
PWS Number:UTAH19013 Deficiency Points:285 Survey Date:09/18/2024
Survey Name:EASTLAND SPECIAL
SERVICE DISTRICT
Surveyor:Curtis Page
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Management and Operations | DS001 | UTAH19013 DISTRIBUTION SYSTEM
22. For a community water system with water sources that require power to produce sufficient flow, system is equipped with standby power
option.
Rule: R309-515-6(2)(a)Rule requires a community water system without naturally flowing water sources, such
as springs or flowing wells, to have one or more of the system's sources equipped for
operation during power outages. To ensure continuous service when the primary power
has been interrupted, a redundant power supply is required. A redundant power
supply may include a transfer switch for auxiliary power such as a generator or a
power supply service with coverage from two independent substations. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:No backup power source is available, nor is it wired to accept a portable generator.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S033 COM SYSTEM WITHOUT NATURALLY FLOWING SOURCES LACKS BACKUP
POWER FOR AT LEAST ONE WATER SOURCE
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS003 | T JOHNSON -1986 WELL
100. Wellhead is sealed to prevent contamination.
Rule: R309-515-6(6)(i)R309-515-6(6)(i) and R309-515-6(12)(b,c,d)require a sanitary seal be installed and
maintained at the wellhead and discharge piping. This significant deficiency should be
corrected within 120 days of notification or have a corrective action plan approved by
Notes:There is a conduit that perforates the top of the well head that is not sealed.
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S013 WELL LACKS THE REQUIRED WELL SEAL
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS003 | T JOHNSON -1986 WELL
101A. Vent screened with #14 mesh screen
Rule: R309-515-6(12)(d)(iii)Guidance states provisions should be made for venting the well casing, however if
vented R309-515-6(12)(d)(iii) and R309-550-6(6)(a)require vents be fitted with a #14
mesh or finer non-corrodible screen.
Notes:Screen material has failed. Replace screen.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S006 END OF WELL CASING VENT LACKS NO. 14 SCREEN
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS003 | T JOHNSON -1986 WELL
106. There are no unprotected cross-connections in well discharge piping.
Rule: R309-105-12(1), R309-515-6(12)(d)(iii)Rule requires the well discharge piping to be protected against the entrance of
contamination. This significant deficiency must be corrected within 120 days of
notification or have a corrective action plan approved by DDW.
Notes:There is a hose connected to well discharge piping. Remove hose, or add a vacuum breaker.
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S021 CROSS CONN EXISTS IN WELL HOUSE OR AT WELL HEAD
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST001 | EASTLAND STORAGE TANK
121C. Vent covered with #14 or finer non-corrodible mesh screen.
Rule: R309-545-15(4)Rule requires a water storage tank vent to be fitted with #14 mesh or finer non-
corrodible screen and vents 6-inches or greater in diameter to be fitted with additional
heavy gauge screen or substantial covering to protect the #14 mesh screen from
vandalism or damage. This significant deficiency must be corrected within 120 days of
notification or have a compliance action plan approved by DDW.
Notes:Vent screen is not #14mesh. Replace screen with #14 mesh.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V007 STORAGE TANK VENT LACKS NO. 14 SCREEN
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST001 | EASTLAND STORAGE TANK
128B. Overflow line covered with #4 mesh non-corrodible screen
Rule: R309-545-13(3)Rule requires overflow pipes to be screened with #4 mesh non-corrodible screens
installed at a location least susceptible to damage by vandalism. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:Screen has failed, flush overflow pipe and replace screen with #4mesh material.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V012 END OF STORAGE TANK OVERFLOW PIPE LACKS NO. 4 SCREEN
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Treatment - Chlorination General | TP003 | T JOHNSON CHLORINATOR
151A. System is sampling distribution residuals throughout entire distribution system
Rule: R309-105-7, 8 & 18, R309-100 through
605
Trigger for regulatory followup to address concerns.
Notes:Samples are being taken from one location only.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TGR9 TRIGGER FOR REGULATORY FOLLOWUP TO ADDRESS CONCERNS
Sanitary Survey Category: MR
SDWIS Severity Code: Significant Deficiency
Treatment - Chlorination General | TP003 | T JOHNSON CHLORINATOR
153. Daily operating records reflect chemical dosages and total quantities used
Rule: R309-105-14(3)(a)Rule requires all water system using chemical addition or specialized equipment for the
treatment of drinking water to regularly complete operational reports. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:No log book is being kept to record chemical dosages and total quantities used.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: TG20 DAILY RECORDS DO NOT REFLECT DOSAGES ACCURATELY
Sanitary Survey Category: TR
SDWIS Severity Code: Significant Deficiency
Liquid Hypochlorination | TP003 | T JOHNSON CHLORINATOR
158. Where concentrated hypochlorite solutions are handled in containers of 55 gallons or LESS: some method of emergency eyewash provided
(a full eyewash station and shower is not required)
Rule: R309-520-7(3)(a)(i)Where hypochlorite solutions are used at remote locations or in quantities of 55 gallons
or less on site, safety showers are not required and alternative emergency eyewash may
be provided. This significant deficiency must be corrected within 120 days of
notification or have a corrective action plan approved by DDW.
Notes:No emergency eyewash is on site.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: TD66 HYPOCHLORITE FACILITY LACKS A MEANS OF EMERGENCY EYEWASH
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Liquid Hypochlorination | TP003 | T JOHNSON CHLORINATOR
160. Records are kept to minimize the use of decayed hypochlorite solution
Rule: R309-520-7(3)(b)Rule requires the water system to provide an operational means, such as keeping
records of the delivery date of the hypochlorite solution, to avoid the injection of
significantly decayed hypochlorite solutions.
Notes:No records being kept.
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TD68 NO RECORDS KEPT TO MINIMIZE USE OF DECAYED HYPOCHLORITE SOLUTION
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Liquid Hypochlorination | TP003 | T JOHNSON CHLORINATOR
161. There are adequate spill containment provisions for acid and caustic liquids.
Rule: R309-525-11(6)(a)(iv)(B), R309-525-
11(8)(b)(viii)
Rule requires liquid chemical storage tanks to have an overflow and receiving basin or
drain capable of receiving accidental spills or overflows, and meeting all the
requirements of R309-525-23.
Notes:Spill containment not provided.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TG59 LACKS CONTAINMENT PROVISIONS TO HANDLE SOLUTION TANK SPILLS OR
OVERFLOWS